Goodman Mfg RT6100004R13 manual Checking Compressor Efficiency

Page 52

SERVICING

CAUTION

Use refrigerant certified to AHRI standards. Used refrigerant may cause compressor damage and will void the warranty. Most portable machines cannot clean used refrigerant to meet AHRI standards.

CAUTION

Operating the compressor with the suction valve closed will void the warranty and cause serious compressor damage.

Charge the system with the exact amount of refrigerant.

Refer to the specification section or check the unit name- plates for the correct refrigerant charge.

An inaccurately charged system will cause future prob- lems.

1.When using an ambient compensated calibrated charg- ing cylinder, allow liquid refrigerant only to enter the high side.

2.After the system will take all it will take, close the valve on the high side of the charging manifold.

3.Start the system and charge the balance of the refriger- ant through the low side. DO NOT charge in a liquid form.

4.With the system still running, close the valve on the charg- ing cylinder. At this time, you may still have some liquid refrigerant in the charging cylinder hose and will definitely have liquid in the liquid hose. Reseat the liquid line core. Slowly open the high side manifold valve and transfer the liquid refrigerant from the liquid line hose and charging cylinder hose into the suction service valve port. CARE- FUL: Watch so that liquid refrigerant does not enter the compressor.

5.With the system still running, reseat the suction valve core, remove hose and reinstall both valve core caps.

6.Check system for leaks.

NOTE: This charging procedure can only be done in the cooling mode of operation. (Early production "a" models only.) All models with compressor process tube access valve can be processed in heating cycle if this valve is used.

When charging a remote condensing unit with a non-match- ing evaporator coil, or a system where the charge quantity is unknown, alternate charging methods must be used. These systems must be charged according to subcooling or super- heat.

SYSTEM SUPERHEAT

Ambient Condenser

 

Return Air Temperature

 

Inlet Temp.

 

 

(°F Drybulb)

 

 

(°F Drybulb)

 

 

 

 

 

 

 

 

65

70

 

75

 

80

85

 

 

 

 

 

 

 

 

115

 

 

 

 

 

 

3

100

 

 

 

 

 

5

5

95

 

 

 

5

 

5

5

90

 

 

 

7

 

12

18

85

 

5

 

10

 

17

20

80

 

5

 

12

 

21

26

75

5

10

 

17

 

25

29

70

5

14

 

20

 

28

32

65

13

19

 

26

 

32

35

60

17

25

 

30

 

33

37

Table 7

Coils having flow control restrictors should be charged to match the System Superheat chart above. Coils with ther- mostatic expansion valves (TXV's) should be charged by sub- cooling. See "Checking Subcooling and Superheat" sec- tions in this manual.

Due to their design, Scroll compressors are inherently more tolerant of liquid refrigerant.

NOTE: Even though the compressor section of a Scroll com- pressor is more tolerant of liquid refrigerant, continued flood- back or flooded start conditions may wash oil from the bear- ing surfaces causing premature bearing failure.

If a restriction is located, replace the restricted part, replace drier, evacuate and recharge.

S-104 CHECKING COMPRESSOR EFFICIENCY

The reason for compressor inefficiency is broken or dam- aged suction and/or discharge valves, or scroll flanks on Scroll compressors, reducing the ability of the compressor to pump refrigerant vapor.

The condition of the valves or scroll flanks is checked in the following manner.

1.Attach gauges to the high and low side of the system.

2.Start the system and run a "Cooling Performance Test. If the test shows:

a. Below normal high side pressure. b. Above normal low side pressure.

c. Low temperature difference across coil. d. Low amp draw at compressor.

and the charge is correct. The compressor is faulty - replace the compressor. NOTE: THIS TEST CANNOT BE DONE IN THE HEATING MODE

Verification of proper rotation of Scroll Compressors is made as follows.

52

Image 52
Contents Service Instructions Table of Contents Important InformationSafe Refrigerant Handling Product Identification Split System Air Conditioners R-22Split System Air Conditioners R-22 Split System Heat Pumps R-22 Product Identification Single Piece Air Handlers Single Piece Air Handlers MBR/MBE Air Handlers 036 036 120 3642 1824 Accessories ASC01CPKF24 CPKF36 CPKF42 CPKF48 CPKF60 CPKF61 Expansion Valve Kits FSK01A Coil Accessories Product Design Condensing UnitProduct Design System Operation HeatingCooling Cycle System Operation Indoor Coil Outdoor Thermostatic Expansion Valve AFE18-60A Control Board DescriptionTroubleshooting Chart COOLING/HP Analysis ChartServicing Table of Contents Checking Voltage Checking Wiring Checking THERMOSTAT, WIRING, and Anticipator3A Thermostat and Wiring Servicing3B Cooling Anticipator 3C Heating AnticipatorChecking Time Delay Relay Testing Coil CircuitChecking Transformer Control Circuit Checking Cycle ProtectorTesting Compressor Contactor Testing FAN RelayChecking Contactor AND/OR Relays Checking Contactor ContactsCopeland Comfort Alert Diagnostics Applies to ASC13 & ASH13Diagnostics Table Red TripHard Start KIT Wiring Testing Capacitor ResistanceChecking Loss of Charge Protector Checking CapacitorTesting Capacitance 15B Capacitance Check16A Checking FAN and Blower Motor Windings PSC Motors 16B Checking FAN and Blower Motor ECM Motors16D ECM CFM Adjustments 16C Checking ECM Motor WindingsChart on Next Chart from Previous Itc h 16E Checking GE X13TM Motors Checking Compressor17A Resistance Test GE X13TM Motor ConnectionsTesting Compressor Windings 17B Ground Test17D Operation Test Compressor Ground TestTesting Crankcase Heater Optional Item Testing Defrost ControlTesting Defrost Thermostat Checking Reversing Valve and Solenoid40 AR*F & MBR Electronic Blowers Time Delay Relay Sequence of OperationAR*F & MBR With Single Stage Condensers AR*F & MBR With Single Stage Heat PumpsAEP* & MBE Electronic Blower Time Delay Relay 41 AEP* & MBE with Single Stage CON Densers41A AEP* & MBE with Single Stage Heat Pumps Electric Heater Optional Item Temperature Rise F @ CFM 61A Checking Heater Limit ControlsLeak Testing Nitrogen or NITROGEN-TRACED 61B Checking Heater Fuse Link Optional Electric HeatersChecking Heater Elements Refrigeration Repair PracticeCharging EvacuationEvacuation Checking Compressor Efficiency An inaccurately charged system will cause future prob- lems105B Thermostatic Expansion Valve Overfeeding UnderfeedingSuperheat Thermostatic Expansion ValvesChecking Subcooling Checking Expansion Valve OperationOvercharge of Refrigerant Checking Restricted Liquid LineNON-CONDENSABLES Compressor BurnoutSuction Line Drier Clean-Up Method Refrigerant PipingInstallation Requirements Reversing Valve Replacement System ChargingAIR Handler External Static Coil Static Pressure DropTotal External Static Static Pressure DropALL Fuel System AFE18-60A Control Board Accessories Wiring DiagramsALL Fuel System Control Board AFE18-60A 10kw and Below, One Stage Electric Heat OT/EHR18-60 #2 GRD PLM PLF XFMR-R XFMR-C After Installing Optional Heat KIT, Mark AN X Provided Above HKR Heat Kit GRD PLM PLF Accessories Wiring Diagrams