SERVICING
S-111 CAPILLARY TUBES/RESTRICTOR ORIFICES
The capillary tubes/restrictor orifices used in conjunction with the indoor and outdoor coil, are a predetermined length and bore (I.D.).
They are designed to control the rate of liquid refrigerant flow into an evaporator coil.
The amount of refrigerant that flows through the capillary tube/ restrictor orifice is regulated by the pressure difference between the high and low sides of the system.
In the cooling cycle when the outdoor air temperature rises, the high side condensing pressure rises. At the same time, the cooling load on the indoor coil increases, causing the low side pressure to rise, but at a slower rate.
Since the high side pressure rises faster when the tempera- ture increases, more refrigerant flows to the evaporator, increasing the cooling capacity of the system.
When the outdoor temperature falls, the reverse takes place. The condensing pressure falls, and the cooling loads on the indoor coil decrease, causing less refrigerant flow.
A strainer is placed on the entering side of the tubes to prevent any foreign material from becoming lodged inside the capil- lary tubes.
If a restriction should become evident, proceed as follows:
1.Capture the refrigerant charge.
2.Removethecapillarytubes/restrictororificeortubestrainer assembly. and replace.
3.Replace liquid line drier, evacuate and recharge.
Discharge and suction pressures will be low, giving the appearance of an undercharged unit. However, the unit will have normal to high subcooling.
Locate the restriction, replace the restricted part, replace drier, evacuate and recharge.
S-113 OVERCHARGE OF REFRIGERANT
An overcharge of refrigerant is normally indicated by an excessively high head pressure.
An evaporator coil, using an expansion valve metering device, will basically modulate and control a flooded evaporator and prevent liquid return to the compressor.
An evaporator coil, using a capillary tube metering device, could allow refrigerant to return to the compressor under extreme overcharge conditions. Also with a capillary tube metering device, extreme cases of insufficient indoor air can cause icing of the indoor coil and liquid return to the compres- sor, but the head pressure would be lower.
There are other causes for high head pressure which may be found in the "Service Problem Analysis Guide."
If other causes check out normal, an overcharge or a system containing
If this system is observed:
1.Start the system.
2.Remove and capture small quantities of gas from the suction line dill valve until the head pressure is reduced to normal.
3.Observe the system while running a cooling performance test. If a shortage of refrigerant is indicated, then the system contains
Capillary Tubes/Orifice Assembly
CHECKING EQUALIZATION TIME
During the "OFF" cycle, the high side pressure bleeds to the low side through the capillary tubes/restrictor orifices. Check equalization time as follows:
1.Attach a gauge manifold to the suction and liquid line dill valves.
2.Start the system and allow the pressures to stabilize.
3.Stop the system and check the time it takes for the high and low pressure gauge readings to equalize.
If it takes more than seven (7) minutes the capillary tubes/ restrictor orifices are inoperative. Replace, install a liquid line drier, evacuate and recharge.
S-112 CHECKING RESTRICTED LIQUID LINE
When the system is operating, the liquid line is warm to the touch. If the liquid line is restricted, a definite temperature drop will be noticed at the point of restriction. In severe cases, frost will form at the restriction and extend down the line in the direction of the flow.
S-114 NON-CONDENSABLES
If
S-115 COMPRESSOR BURNOUT
When a compressor burns out, high temperature develops causing the refrigerant, oil and motor insulation to decom- pose forming acids and sludge.
If a compressor is suspected of being
56