Goodman Mfg RT6100004R13 manual 105B Thermostatic Expansion Valve

Page 53

SERVICING

NOTE: The compressor may run backwards (noisy opera- tion) for 1 or 2 seconds at shutdown. This is normal and does not harm the compressor.

S-105A PISTON KIT CHART FOR ASC13, GSC13, VSC13, GSC14, ASH13, GSH13, VSH14, GSH14 UNITS

1.Install gauges and verify that the suction pressure drops while the discharge pressure increases.

2.Listen for normal compressor sound levels. Reverse rota- tion results in elevated or unusual sound levels.

3.Reverse rotation will result in substantially reduced amp draw from tabulated values.

To correct improper rotation, switch any two power supply leads at the outdoor unit contactor.

The 3 phase Scroll Compressors are direction of rotation sen- sitive. They will rotate in either direction depending on the phasing of the power. There is no negative impact on durabil- ity caused by operating 3 phase compressors in reversed rotation. The compressors internal protector will trip, de-en- ergizing the compressor. Continued operation of 3 phase scroll compressors with the rotation reversed will contribute to com- pressor failure. All 3 phase scroll compressors should be checked for correct phase rotation.

Air Conditioners

Orifice

Size

 

G/VSC130181A*

.055

GSC130181B*

.055

G/VSC130241A*

.059

GSC130241C*

 

AC30, ACNF24

.059

AWB24/AWUF24

.059

# All other ARI Matches

.061

G/VSC130301A* / D*

 

GSC130303A*

 

AC36, ACNF30

.065

AWB36, AWUF36

.068

# All other ARI Matches

.065

G/VSC130361A*

 

GSC130363A* / B*

.071

AWB36, AWUF36

.071

# All other ARI Matches

.074

GSC130361B* / F*

.071

G/VSC130421A*

.078

G/VSC130481A

.082

GSC130483A*/ 4A*

.082

G/VSC130601A*

.093

GSC130603A*/ 4A*

.093

ASC130181A*

.055

ASC130241A*

.061

ASC130301A*

.065

ASC130361A*

.071

ASC130421A*

.078

ASC130481A*

.082

ASC130601A*

.093

GSC140181A*

.053

GSC140241A*

.061

GSC140301A*

.067

GSC140361A*

.074

GSC140421A*

.078

GSC140481A*

.084

GSC140601A*

.096

GSC140181B*

.055

GSC140241B*

.062

GSC140301B*

.067

GSC140361B*

.073

GSC140421B*

.080

Heat Pumps

Orifice

Size

 

G/VSH130181A*

.052

GSH130181B*

.055

G/VSH130191A*

.052

G/VSH130241A*

.061

GSH130241B*

.061

G/VSH130251A*

.061

G/VSH130301A*

.068

GSH130301B*

.070

G/VSH130311A*

.065

G/VSH130361A*

.073

GSH1303613A*/1B*

.082

G/VSH130421A*

.082

G/VSH130481A*

.084

GSH1304813A*/ 4A*

.084

G/VSH130601A*

.093

GSH1306013A*/ 4A*

.093

ASH130181A*

.052

ASH130241A*

.062

ASH130301A*

.065

ASH130361A*

.073

ASH130421A*

.082

ASH130481A*

.084

ASH130601A*

.093

GSH140361A*

.076

GSH140421A*

.078

GSH140481A*

.088

S-105B THERMOSTATIC EXPANSION VALVE

The expansion valve is designed to control the rate of liquid refrigerant flow into an evaporator coil in exact proportion to the rate of evaporation of the refrigerant in the coil. The amount of refrigerant entering the coil is regulated since the valve responds to temperature of the refrigerant gas leaving the coil (feeler bulb contact) and the pressure of the refrigerant in the coil. This regulation of the flow prevents the return of liquid refrigerant to the compressor.

The illustration below shows typical heat pump TXV/check valve operation in the heating and cooling modes.

53

Image 53
Contents Service Instructions Important Information Table of ContentsSafe Refrigerant Handling Split System Air Conditioners R-22 Product IdentificationSplit System Air Conditioners R-22 Split System Heat Pumps R-22 Product Identification Single Piece Air Handlers Single Piece Air Handlers MBR/MBE Air Handlers 036 036 120 3642 1824 ASC01 AccessoriesCPKF24 CPKF36 CPKF42 CPKF48 CPKF60 CPKF61 Expansion Valve Kits FSK01A Coil Accessories Condensing Unit Product DesignProduct Design Heating System OperationCooling Cycle System Operation Indoor Coil Outdoor Thermostatic Expansion Valve Description AFE18-60A Control BoardCOOLING/HP Analysis Chart Troubleshooting ChartServicing Table of Contents Checking THERMOSTAT, WIRING, and Anticipator Checking Voltage Checking Wiring3A Thermostat and Wiring Servicing3C Heating Anticipator 3B Cooling AnticipatorTesting Coil Circuit Checking Time Delay RelayChecking Transformer Control Circuit Checking Cycle ProtectorTesting FAN Relay Testing Compressor ContactorChecking Contactor AND/OR Relays Checking Contactor ContactsApplies to ASC13 & ASH13 Copeland Comfort Alert DiagnosticsRed Trip Diagnostics TableTesting Capacitor Resistance Hard Start KIT WiringChecking Loss of Charge Protector Checking Capacitor15B Capacitance Check Testing Capacitance16A Checking FAN and Blower Motor Windings PSC Motors 16B Checking FAN and Blower Motor ECM Motors16C Checking ECM Motor Windings 16D ECM CFM AdjustmentsChart on Next Chart from Previous Itc h Checking Compressor 16E Checking GE X13TM Motors17A Resistance Test GE X13TM Motor Connections17B Ground Test Testing Compressor Windings17D Operation Test Compressor Ground TestTesting Defrost Control Testing Crankcase Heater Optional ItemTesting Defrost Thermostat Checking Reversing Valve and SolenoidSequence of Operation 40 AR*F & MBR Electronic Blowers Time Delay RelayAR*F & MBR With Single Stage Condensers AR*F & MBR With Single Stage Heat Pumps41 AEP* & MBE with Single Stage CON Densers AEP* & MBE Electronic Blower Time Delay Relay41A AEP* & MBE with Single Stage Heat Pumps Electric Heater Optional Item 61A Checking Heater Limit Controls Temperature Rise F @ CFM61B Checking Heater Fuse Link Optional Electric Heaters Leak Testing Nitrogen or NITROGEN-TRACEDChecking Heater Elements Refrigeration Repair PracticeEvacuation EvacuationCharging An inaccurately charged system will cause future prob- lems Checking Compressor Efficiency105B Thermostatic Expansion Valve Underfeeding OverfeedingSuperheat Thermostatic Expansion ValvesChecking Expansion Valve Operation Checking SubcoolingChecking Restricted Liquid Line Overcharge of RefrigerantNON-CONDENSABLES Compressor BurnoutRefrigerant Piping Suction Line Drier Clean-Up MethodInstallation Requirements System Charging Reversing Valve ReplacementCoil Static Pressure Drop AIR Handler External StaticTotal External Static Static Pressure DropALL Fuel System Control Board AFE18-60A Accessories Wiring DiagramsALL Fuel System AFE18-60A Control Board 10kw and Below, One Stage Electric Heat OT/EHR18-60 #2 GRD PLM PLF XFMR-R XFMR-C After Installing Optional Heat KIT, Mark AN X Provided Above HKR Heat Kit GRD PLM PLF Accessories Wiring Diagrams