WIRE DRIVE OPERATION

The most frequently used Wire Drive settings are external; some features are accessed by internal set- tings.

WIRE DRIVE SETTINGS -- EXTERNAL

2 STEP / 4 STEP SWITCH:

The Wire Drive has a 2 Step / 4 Step switch located on the gun side of the Status LED. This switch has no effect in CC modes of operation, such as stick welding.

When using 2 Step Logic:

1.Closing the gun trigger initiates the welding sequence (preflow, run in, etc.).

2.Opening the gun trigger ends the welding sequence (burnback, postflow, etc.).

When using 4 Step Logic With Crater Fill “OFF”:

1.Closing the gun trigger initiates the welding sequence (preflow, run in, etc.).

2.Opening the trigger after the welding arc is estab- lished allows the weld to continue as long as cur- rent flows. If the arc goes out, the 4 step cycle is reset.

3.Closing the trigger again allows the weld to contin- ue.

4.Opening the trigger again ends the welding sequence (burnback, postflow, etc.).

When using 4 Step Logic With Crater Fill “ON”:

1.Closing the gun trigger initiates the welding sequence (preflow, run in, etc.).

2.Opening the trigger after the welding arc is estab- lished allows the weld to continue as long as cur- rent flows. If the arc goes out, the 4 step cycle is reset.

3.Closing the trigger again changes the wire feed

speed and the Volts/Trim to the Crater values, and the weld to continues

4.Opening the trigger again ends the welding sequence (burnback, postflow, etc.).

COLD FEED / GAS PURGE SWITCH:

The Wire Drive has a Cold Feed/Gas Purge Switch located near the gun connector. This is an up/down center-off momentary toggle switch.

When held in the up position, the Wire Drive will feed wire, but neither the power source nor the gas sole- noid will be energized. When cold feeding, the feed speed can be adjusted by rotating the WFS encoder knob on the Control Box. Adjusting the cold feed will not affect the run in or welding wire feed speed. When the cold feed switch is released, the cold feed value is saved.

When this switch is held in the down position, the gas solenoid valve is energized, but neither the power source nor the drive motor will be energized.

POWER FEED 10 DUAL

Image 27
Contents OPERATOR’S Manual Safety Electric Shock can kill Iii Welding and Cutting Sparks can Cause fire or explosionSûreté Pour Soudage a LʼArc Précautions DE SûretéThank You Table of Contents Section E Section FP346 Series Installation Safety Precautions Mounting the Wire Drive UnitBoom Mounting of Wire Drive Unit Control Cable Connections Mounting on Power SourceControl Cable Mounting the Control BOX Boom or Separated Bench ModelsControl Cable Specifications Available Cable AssembliesElectrode Cable Connections Selecting the Proper Gear Ratio Wire Drive Gear Ratio High or LOW SpeedChanging the Wire Drive Ratio Work Cable ConnectionsRatio Change Procedure Setting DIP Switches in the Control BOX DIP Switch SetupLSB Figure A.4 Setting DIP Switches in the Wire DriveGUN and Cable Assemblies with FAST-MATECONNECTION Wire Feed Drive Roll KitsProcedure to Install Drive Rolls and Wire Guides GUN and Cable Assemblies with Standard ConnectionMagnum 200 / 300 / 400 Guns General GUN Connection GuidelinesWater Connections for Water Cooled Guns Wire Spindle PlacementWire Feed Shut Down Circuit Optional Gmaw Shielding GASGeneral Panel Installation Guidelines Boom and Bench ConversionsOptional Panels for Control BOX Control BOX Operation Product DescriptionRecommended Processes and Equipment Duty CycleK1542-14 Head Select Panel K1542-13 Dual Procedure / Memory Panel K1542-11 MX2 Panel Control BOX Panels -- ʻLARGEʼ Option Panels CV/Gouge PanelStd K1542-6 M PanelK1542-12 MSP2 Panel Control BOX Panels -- SET UP Controls DescriptionControl BOX -- PC Board Adjustments Control BOX -- Using Operating LimitsWhen using 4 Step Logic With Crater Fill OFF Wire Drive OperationWire Drive Settings -- External When using 2 Step LogicWire Reel Loading READI-REELS, Spools or Coils Electrode PolarityGear BOX Ratio Figure B.1 GAS Guard Regulator Setting Feeding Electrode and Brake AdjustmentDrive Roll Pressure Setting Procedure for Setting Angle of Feed PlateWire Reel Changing Wire Feed Overload ProtectionMaking a Weld Status Light States Component Status LightsStatus Light States CONʼT Roll DH Drive 4-Driven Wire Size Solid Steel ElectrodeCored Electrode Aluminum ElectrodeDescription and Installation of Optional Control BOX Panels Constant Voltage CV/Weld, CV/MIG, CV/Flux Cored Procedures CC/STICK/GOUGE ModeK1542-11 MX2 Panel Large Panel 10 MS/STT Panel Large Panel K1542-14 Head Select Panel Small Panel K1542-13 Dual Procedure Memory Panel Small PanelK1543, K1544 and K1545 Input Cable Assemblies K1548-1 Linc NET Receptacle KIT Input and Output Feeder Head Enclosure ProcedureK363P READI-REEL Adapter K162-1 Wire Spindle AdapterK1504-1 Coil Adapter K435 Coil AdapterGUN Receiver Bushings and Adapters Guns and GUN AdaptersDual Procedure Switch Options Using Dual Procedure with FAST-MATE GunsConduit Adapters K1556-1 Light Duty Caster KIT K590-6 Water Connection KIT for Drive onlyK1536-1 Water Flow Sensor KIT K659-1 GAS Guard RegulatorDrive Rolls and Guide Tubes MaintenanceWire Drive Motor and Gearbox Gun and Cable MaintenanceHOW to USE Troubleshooting Guide 1TROUBLESHOOTINGE-1Troubleshooting Possible Cause Recommended Symptoms Course of Action Field Service FacilityYour local Lincoln Authorized Troubleshooting Course of Action Possible CauseEither of these fail, the problem is Change Or harness disconnected from Fails the continuity test, repair or Possible Cause Err 005 Err 001Err 003 Err 004Err 201 Err 020Err 100 Err 200Err 212 Err 211Diagrams Control BOX Dimension Print Wire Feeder Bench Model Dimension Print DIAGRAMSF-4 Print Power Feed 10 Dual Precaucion Warnung