Friedrich MW12C1H, MW09C1H, MR09C1H, MR12C1H manual Troubleshooting

Page 44

Troubleshooting

9. Troubleshooting

9.1 Precautions before Performing Inspection or Repair

Be cautious during installation and maintenance. Do operation following the regulations to avoid electric shock and casualty or even death due to drop from high altitude.

* Static maintenance is the maintenance during de-energization of the air conditioner.

For static maintenance, make sure that the unit is de-energized and the plug is disconnected.

* Dynamic maintenance is the maintenance during energization of the unit.

Before dynamic maintenance, check the electricity and ensure that there is ground wire on the site. Check if there is electricity on the housing and connection copper pipe of the air conditioner with voltage tester. After ensure insulation place and the safety, the mainte- nance can be performed.

Take sufficient care to avoid directly touching any of the circuit parts without first turning off the power.

At times such as when the circuit board is to be replaced, place the circuit board assembly in a vertical position.

Normally,diagnose troubles according to the trouble diagnosis procedure as described below.(Refer to the check points in servicing written on the wiring diagrams attached to the indoor/outdoor units.)

No. Troubleshooting procedure

1Confirmation

2Judgement by Flashing LED of Indoor/Outdoor Unit

3 How to Check simply the main part

Precautions when inspecting the control section of the outdoor

unit:

A large-capacity electrolytic capacitor is used in the outdoor unit controller (inverter).Therefore,if the power supply is turned off,charge(charging volt- age DC280V to 380V)remains and discharging takes a lot of time.. After turning off the power source,if touching the charging section before discharging, an electrical shock may be caused.

Please open the outdoor unit after the unit is power off for 20min.

9.2 Confirmation

(1)Confirmation of Power Supply

Confirm that the power breaker operates(ON) normally;

(2)Confirmation of Power Voltage

Confirm that power voltage is AC115 ± 10%.

If power voltage is not in this range, the unit may not operate normally.

9.3 Judgement by Flashing LED of Indoor/Outdoor Unit

*Trouble shooting is for cooling and Heat Pump models.

44

Image 44
Contents Split Type Room AIR Conditioner Wall Mounted Type Table of Contents Model and product code Summary and features Important Safety Information Refrigeration System Repair Hazards Property Damage Hazards Specifications 115 MR09C1H MR12C1H Appending date Expanded capacity data tables for both cooling and heating Operation Characteristic Curve 09KUnits Construction Views Refrigerant System Diagram Electrical wiring Electrical DateCooling Models TOP View Bottom View Bottom View Remote Control Operations Function and ControlAuto Timer on Displayed. If the light is tunrned off Disappears Replacement of Batteries Description of Each Control Operation Function and Control Function and Control Setting+ 2, medium speed Tring ≤ Tsetting 2, low speed P2 Maximum cooling and heating Detection of temperature sensor malfunction Frequency Control3-minutes Standby Compressor Protection FunctionFreeze-up Protection Control Discharge Pipe ControlInput Current Control Detail Conditions for Start Controlling Fan Control Tap Control in indoor/outdoor unit silent operationImportant Notices Ground requirements Installation dimension diagram Boring Piping Hole Installing Indoor Unit Electric wiring Installing Outdoor UnitCheck after Installation Check after Installation and Operation TestInstallation and Maintenance of Healthy FilterOptional Installation of Healthy FilterTroubleshooting Can not start up Malfunction of four-way valve Is not on, then replace the protector Adjust support washer of compressor, Troubleshooting YELLOW-LED4 GREEN-LED2 RED-LED3 Analysis or processing of some of the malfunction display How to Check simply the main part Troubleshooting Comp Page AP1 Troubleshooting Is stop time of the compressor longer than 3 minutes? Minutes after the complete unit is powered off Start If the fault is eliminated? Troubleshooting Flow chart for outdoor communitcation circuit detecting Troubleshooting Guide Troubleshooting Guide Temp Resistance 2-way, 3-way Valve Appearance Way Valve Liquid SideProcedure Close Close Open Close Balance Refrigerant of the 3-way Valve Procedure EvacuationGas Charging After EvacuationRemoval Procedure Removal Procedure Removal Procedure Removal Procedure of Outdoor Unit Removal Procedure Removal Procedure MW09C1H / MW12C1H Exploded Diagram MW09C1H Parts List MW12C1H Parts List MR09C1H Exploded Diagram MR09C1H Parts List MR12C1H Exploded View MR12C1H Parts List Page Friedrich AIR Conditioning CO