Troubleshooting
The fan does not run when it is set to supply air.
The indoor fan motor is burned or bre- aks or has the heat protector malfun- ction.
The
Wrong connection
The fan capacitor has open circuit or is damaged
Replace the fan motor or the defective part.
Replace the fan motor
Make the correction connection based on the circuit drawing.
Replace the fan capacitor of the same type and same specification.
|
|
|
| The outdoor fan motor is damaged. |
|
| Replace the fan motor |
|
|
|
|
|
|
|
|
|
|
In the cooling and |
|
|
|
|
|
|
|
|
heating mode, the |
|
|
| Wrong connection |
|
| Make the correct connection based on the circuit | |
compressor runs, |
|
|
|
|
| drawing. | ||
|
|
|
|
|
| |||
but the outdoor |
|
|
|
|
|
|
|
|
fan does not run. |
|
|
|
|
|
| Replace the fan capacitor |
|
|
|
|
| The outdoor fan capacitor is damaged. |
|
|
| |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
Malfunction of compressor
Replace the compressor
When cooling or heating, outdoor fanruns,compr- essor doesn't run.
| Breakage of running capacitor of |
|
| Replace the capacitor |
| compressor |
|
| |
|
|
| ||
|
|
|
| |
|
|
|
|
|
|
| The voltage is too low or too high. |
|
| Manostat is recommended. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Wrong wire connection |
|
| Connect the circuit diagram correctly |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| The protector itself has malfunction. |
|
| Use the multimeter to check whether the contact of | |
|
|
|
| the compressor is on when it is not overheated. If it | ||
|
|
|
|
| ||
|
|
|
|
| is not on, then replace the protector | |
|
|
|
|
| ||
|
|
|
|
|
|
|
The compressor is too hot and leads to the action of the protector.
The swing fan
DOES not run.
| The refrigerant is not enough or is too |
|
|
|
|
| Adjust the volume of the refrigerant |
|
| much. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| The capillary is blocked and the temp- |
|
|
|
|
| Replace the capillary |
|
| erature rises. |
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| The compressor does not run smoothly |
|
|
|
|
| Replace the compressor |
|
| or is stuck. The air discharge valve is |
|
|
|
|
|
| |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
| damaged |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| ||
| The protector itself has malfunction. |
|
|
|
| Replace the protector |
| |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| ||
| The torque of the swing motor is not |
|
|
|
|
| ||
| enough |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| First, check whether the connection is wrong. If no, | |
| wrong connection |
|
|
|
|
| ||
|
|
|
|
|
| replace the parts | ||
|
|
|
|
|
| |||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| The controller is damaged IC2003 is |
|
|
|
|
|
|
|
| damaged, the swing relay can not close, |
|
|
|
|
|
| |
| etc |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
47