Troubleshooting

9.4 How to Check simply the main part

Main Check Points:

Units of 115V: Use AC voltmeter to check wether the voltage between terminal L and N on the wiring board is 115V AC

Units of 115V: Whether the reactor (L) is correctly connected? Whether the connection is loose or fallen? Whether the reactor

(L) is damaged ?

Fault diagnosis process:

Switch on the unit and wait 1 minute

Use DC voltmeter to measure the voltage on the two ends of electrolytic capacitor (test3)

Voltage higher than 103.5V?

 

Fault with the

Replace the

 

 

 

 

 

 

For 115V Units

Y

voltage testing

 

 

control panel

 

 

Voltage higher than 187V?

 

 

 

circuit on contr-

 

 

 

AP1

 

 

 

 

 

 

For 208~230V Units

 

ol panel AP1

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

Measure the AC voltage between

 

 

 

 

 

terminal L and N on wiring board

 

 

 

 

 

 

XT

 

 

 

 

 

 

 

 

Switch off the

 

 

 

 

 

power and repair

 

 

 

Voltage within 103.5~126.5V?

 

the supply power

Re-energize

If the fault is

 

N

to restore the volt-

and switch

Y

For 115V Units

eliminated?

 

age to 103.5~126.5

on the unit

 

 

 

 

 

 

 

VVAC

For 115V

 

 

 

 

 

Units

 

 

 

 

Y

 

 

 

 

 

 

Switch off the power and wait 20 minutes;

 

 

 

 

or use DC voltmeter to measure the volt-

 

N

 

 

age on the use DC voltmeter to measure

 

 

 

 

 

 

 

the voltage on the two ends of capacitor

 

 

 

 

(test3), until the voltage is lower than 20V

 

 

 

 

Check the

 

 

 

 

 

 

connection of reactor

 

 

 

 

 

 

(L in the Electrical

 

 

 

 

 

 

Wiring Diagram)

 

 

 

 

 

 

 

 

Connect the rea-

Re-energize

 

 

If the wiring of

 

ctor L according to

If the fault

 

N

and switch on

Y

 

 

 

reactor L is normal?

Electrical Wiring

is eliminated?

 

the unit

 

 

 

Diagram

 

 

 

 

 

 

 

 

 

Y

 

 

 

 

 

 

Replace the control

 

 

 

N

 

 

panel AP1

 

 

 

 

 

 

 

 

 

 

 

End

 

 

 

 

 

 

52

Image 52
Contents Split Type Room AIR Conditioner Wall Mounted Type Table of Contents Model and product code Summary and features Important Safety Information Refrigeration System Repair Hazards Property Damage Hazards Specifications 115 MR09C1H MR12C1H Appending date Expanded capacity data tables for both cooling and heating Operation Characteristic Curve 09KUnits Construction Views Refrigerant System Diagram Electrical wiring Electrical DateCooling Models TOP View Bottom View Bottom View Remote Control Operations Function and ControlAuto Timer on Displayed. If the light is tunrned off Disappears Replacement of Batteries Description of Each Control Operation Function and Control Function and Control Setting+ 2, medium speed Tring ≤ Tsetting 2, low speed P2 Maximum cooling and heating Detection of temperature sensor malfunction Frequency Control3-minutes Standby Compressor Protection FunctionInput Current Control Discharge Pipe ControlFreeze-up Protection Control Detail Conditions for Start Controlling Fan Control Tap Control in indoor/outdoor unit silent operationImportant Notices Ground requirements Installation dimension diagram Boring Piping Hole Installing Indoor Unit Electric wiring Installing Outdoor UnitCheck after Installation Check after Installation and Operation TestInstallation and Maintenance of Healthy FilterOptional Installation of Healthy FilterTroubleshooting Can not start up Malfunction of four-way valve Is not on, then replace the protector Adjust support washer of compressor, Troubleshooting YELLOW-LED4 GREEN-LED2 RED-LED3 Analysis or processing of some of the malfunction display How to Check simply the main part Troubleshooting Comp Page AP1 Troubleshooting Is stop time of the compressor longer than 3 minutes? Minutes after the complete unit is powered off Start If the fault is eliminated? Troubleshooting Flow chart for outdoor communitcation circuit detecting Troubleshooting Guide Troubleshooting Guide Temp Resistance 2-way, 3-way Valve Appearance Way Valve Liquid SideProcedure Close Close Open Close Balance Refrigerant of the 3-way Valve Procedure EvacuationGas Charging After EvacuationRemoval Procedure Removal Procedure Removal Procedure Removal Procedure of Outdoor Unit Removal Procedure Removal Procedure MW09C1H / MW12C1H Exploded Diagram MW09C1H Parts List MW12C1H Parts List MR09C1H Exploded Diagram MR09C1H Parts List MR12C1H Exploded View MR12C1H Parts List Page Friedrich AIR Conditioning CO