Troubleshooting

Indoor unit

Liquid side

 

Open

Outdoor unit

2-Way valve

Gas side

Closed

3-Way valve

Lo

CLOSE CLOSE

Purge the air

• Procedure

(1)Confirm that both the 2-way and 3-way valves are set to the open position.

Remove the valve stem caps and confirm that the valve stems are in the raised position.

Be sure to use a hexagonal wrench to operate the valve stems.

(2)Operate the unit for 10 to 15 minutes.

(3)Stop operation and wait for 3 minutes, then connect the charge set to the service port of the 3-way valve.

– Connect the charge hose with the push pin to the service port.

(4) Air purging of the charge hose.

Open the low-pressure valve on the charge set slightly to air purge from the charge hose.

(5)Set the 2-way valve to the closed position.

(6)Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 1kg/cm2g.

(7) Immediately set the 3-way valve to the closed position.

Do this quickly so that the gauge ends up indicating 3 to 5kg/ cm2g.

(8)Disconnect the charge set, and mount the 2-way and 3- way valve’s stem nuts and the service port nut.

Use torque wrench to tighten the service port nut to a torque of 1.8 kg.m.

Be sure to check for gas leakage.

69

Image 69
Contents Split Type Room AIR Conditioner Wall Mounted Type Table of Contents Model and product code Summary and features Important Safety Information Refrigeration System Repair Hazards Property Damage Hazards Specifications 115 MR09C1H MR12C1H Appending date Expanded capacity data tables for both cooling and heating Operation Characteristic Curve 09KUnits Construction Views Refrigerant System Diagram Electrical Date Electrical wiringCooling Models TOP View Bottom View Bottom View Function and Control Remote Control OperationsAuto Timer on Displayed. If the light is tunrned off Disappears Replacement of Batteries Description of Each Control Operation Function and Control Function and Control Setting+ 2, medium speed Tring ≤ Tsetting 2, low speed P2 Maximum cooling and heating Frequency Control Detection of temperature sensor malfunction3-minutes Standby Compressor Protection FunctionDischarge Pipe Control Input Current ControlFreeze-up Protection Control Detail Conditions for Start Controlling Tap Control in indoor/outdoor unit silent operation Fan ControlImportant Notices Ground requirements Installation dimension diagram Boring Piping Hole Installing Indoor Unit Installing Outdoor Unit Electric wiringCheck after Installation and Operation Test Check after InstallationInstallation of Healthy Filter Installation and Maintenance of Healthy FilterOptionalTroubleshooting Can not start up Malfunction of four-way valve Is not on, then replace the protector Adjust support washer of compressor, Troubleshooting YELLOW-LED4 GREEN-LED2 RED-LED3 Analysis or processing of some of the malfunction display How to Check simply the main part Troubleshooting Comp Page AP1 Troubleshooting Is stop time of the compressor longer than 3 minutes? Minutes after the complete unit is powered off Start If the fault is eliminated? Troubleshooting Flow chart for outdoor communitcation circuit detecting Troubleshooting Guide Troubleshooting Guide Temp Resistance Way Valve Liquid Side 2-way, 3-way Valve AppearanceProcedure Close Close Open Close Balance Refrigerant of the 3-way Valve Evacuation ProcedureAfter Evacuation Gas ChargingRemoval Procedure Removal Procedure Removal Procedure Removal Procedure of Outdoor Unit Removal Procedure Removal Procedure MW09C1H / MW12C1H Exploded Diagram MW09C1H Parts List MW12C1H Parts List MR09C1H Exploded Diagram MR09C1H Parts List MR12C1H Exploded View MR12C1H Parts List Page Friedrich AIR Conditioning CO