FUNCTION AND CONTROL
Protection
Protection is the same as that under the cooling mode.
(3) Heating Mode
Working conditions and process of heating
If Tamb.≤Tpreset+36°F, the unit enters heating mode, in which case the
If T amb≥T. preset+41°F, the compressor will stop, the outdoor fan will stop with a time lag of 30s, and the indoor fan will stop after
If Tpreset+36°F<T amb<. Tpreset +41°F, the unit will maintain its original operating status.
Under this mode, the
Condition and process of defrost
When duration of successive heating operation is more than 45 minutes, or accumulated heating time more than 90 minutes, and one of the following conditions is reached, the unit will enter the defrost mode after 3 minutes.
a.Toutdoor amb.≥A°F, Toutdoor tube ≤W°F;
b.A°F≤Toutdoor amb.<B°F, Toutdoor tube ≤X°F;
c.B°F≤Toutdoor amb.<C°F, Toutdoor tube ≤Y°F;
d.Touter amb.<C°F, Touter tube ≤Z°F
At that time, the indoor fan stops and the compressor stops, and after 30 seconds the outdoor fan will stop, and then after 30 seconds, the
When the compressor has operated under defrost mode for 7.5 minutes, or Touter tube ≥E°F, the compressor will be converted to 53Hz operation. After 30 seconds, the compressor will stop. And after another 30 seconds, the
3.Protection
Cold air prevention
The unit is started under heating mode (the compressor is ON):
In the case of Tindoor amb.<75°F : if T tube ≤104°F and the indoor fan is at stop state, the indoor fan will begin to run at low speed with a time lag of 2 minutes. Within 2 minutes, if Ttube >40, the indoor fan also will run at low speed; and after
In the case of Tindoor amb.≥75°F: if Ttube ≤108°F, the indoor fan will run at low speed, and after one minute, the indoor fan will be converted to preset speed. With in
to preset speed.
Note: Tindoor amb.1 2 refers to, under initially heating mode, the indoor ambient temperature before the
command to start the compressor is performed according to the program, or after the unit is withdrawn from defrost, the indoor ambient temperature before the defrost symbol is cleared.
Total current up and frequency down protection
If the total current Itotal ≤W, frequency rise will be allowed; if Itotal ≥X, frequency rise will not be allowed; if Itotal ≥Y, the compressor will run at reduced frequency; and if Itotal ≥Z, the compressor will stop and the outdoor fan will stop with a time lag of 30s.
(4) Fan Mode
Under the mode, the indoor fan will run at preset speed and the compressor, the outdoor fan, the
Under the mode, temperature can beset within a range of 61°F - 86°F.
(5) AUTO Mode
Working conditions and process of AUTO mode
Under AUTO mode, standard cooling temperature Tpreset is 77°F and standard heating temperature Tpreset is 64.4°F.
a.Once energized, if Tamb.≤68°F, the unit will be started under heating mode; if 68°F < Tamb.< 77°F, the unit will run
under fan mode and the operation indicator lamp will be bright; and if Tamb.≥77°F, the unit will be started under cooling mode.
28