Friedrich MW12C1H, MW09C1H, MR09C1H, MR12C1H manual Function and Control

Page 28

FUNCTION AND CONTROL

Protection

Protection is the same as that under the cooling mode.

(3) Heating Mode

Working conditions and process of heating

If Tamb.≤Tpreset+36°F, the unit enters heating mode, in which case the four-way valve, the compressor and the outdoor fan will operate simultaneously, and the indoor fan will run at preset speed in the condition of preset cold air prevention.

If T amb≥T. preset+41°F, the compressor will stop, the outdoor fan will stop with a time lag of 30s, and the indoor fan will stop after 60-second blow at low speed

If Tpreset+36°F<T amb<. Tpreset +41°F, the unit will maintain its original operating status.

Under this mode, the four-way valve is energized and temperature can be set within a range of 61 - 86°F . The operating symbol, the heating symbol and preset temperature are revealed on the display.

Condition and process of defrost

When duration of successive heating operation is more than 45 minutes, or accumulated heating time more than 90 minutes, and one of the following conditions is reached, the unit will enter the defrost mode after 3 minutes.

a.Toutdoor amb.≥A°F, Toutdoor tube ≤W°F;

b.A°F≤Toutdoor amb.<B°F, Toutdoor tube ≤X°F;

c.B°F≤Toutdoor amb.<C°F, Toutdoor tube ≤Y°F;

d.Touter amb.<C°F, Touter tube ≤Z°F

At that time, the indoor fan stops and the compressor stops, and after 30 seconds the outdoor fan will stop, and then after 30 seconds, the four-way valve will stop. After 30 seconds, thecompressor is initiated for raising the frequency to defrost frequency.

When the compressor has operated under defrost mode for 7.5 minutes, or Touter tube ≥E°F, the compressor will be converted to 53Hz operation. After 30 seconds, the compressor will stop. And after another 30 seconds, the four-way valve will be opened, and after 60 seconds, the compressor and the outdoor fan will be started, the indoor fan will run under preset cold air prevention conditions, and H1 will be displayed at temperature display area on the display panel. Defrost frequency is 70Hz.

3.Protection

Cold air prevention

The unit is started under heating mode (the compressor is ON):

In the case of Tindoor amb.<75°F : if T tube ≤104°F and the indoor fan is at stop state, the indoor fan will begin to run at low speed with a time lag of 2 minutes. Within 2 minutes, if Ttube >40, the indoor fan also will run at low speed; and after

1-minute operation at low speed, the indoor fan will be converted to operation at preset speed. Within 1-minute low speed operation or 2-minute non-operation, if Ttube >108°F , the fan will run at present speed.

In the case of Tindoor amb.≥75°F: if Ttube ≤108°F, the indoor fan will run at low speed, and after one minute, the indoor fan will be converted to preset speed. With in one-minute low speed operation, if Ttube >108°F , the indoor fan will be converted

to preset speed.

Note: Tindoor amb.1 2 refers to, under initially heating mode, the indoor ambient temperature before the

command to start the compressor is performed according to the program, or after the unit is withdrawn from defrost, the indoor ambient temperature before the defrost symbol is cleared.

Total current up and frequency down protection

If the total current Itotal ≤W, frequency rise will be allowed; if Itotal ≥X, frequency rise will not be allowed; if Itotal ≥Y, the compressor will run at reduced frequency; and if Itotal ≥Z, the compressor will stop and the outdoor fan will stop with a time lag of 30s.

(4) Fan Mode

Under the mode, the indoor fan will run at preset speed and the compressor, the outdoor fan, the four-way valve and the electric heater will stop.

Under the mode, temperature can beset within a range of 61°F - 86°F.

(5) AUTO Mode

Working conditions and process of AUTO mode

Under AUTO mode, standard cooling temperature Tpreset is 77°F and standard heating temperature Tpreset is 64.4°F.

a.Once energized, if Tamb.≤68°F, the unit will be started under heating mode; if 68°F < Tamb.< 77°F, the unit will run

under fan mode and the operation indicator lamp will be bright; and if Tamb.≥77°F, the unit will be started under cooling mode.

28

Image 28
Contents Split Type Room AIR Conditioner Wall Mounted Type Table of Contents Model and product code Summary and features Important Safety Information Refrigeration System Repair Hazards Property Damage Hazards Specifications 115 MR09C1H MR12C1H Appending date Expanded capacity data tables for both cooling and heating Operation Characteristic Curve 09KUnits Construction Views Refrigerant System Diagram Electrical wiring Electrical DateCooling Models TOP View Bottom View Bottom View Remote Control Operations Function and ControlAuto Timer on Displayed. If the light is tunrned off Disappears Replacement of Batteries Description of Each Control Operation Function and Control Function and Control Setting+ 2, medium speed Tring ≤ Tsetting 2, low speed P2 Maximum cooling and heating Detection of temperature sensor malfunction Frequency Control3-minutes Standby Compressor Protection FunctionInput Current Control Discharge Pipe ControlFreeze-up Protection Control Detail Conditions for Start Controlling Fan Control Tap Control in indoor/outdoor unit silent operationImportant Notices Ground requirements Installation dimension diagram Boring Piping Hole Installing Indoor Unit Electric wiring Installing Outdoor UnitCheck after Installation Check after Installation and Operation TestInstallation and Maintenance of Healthy FilterOptional Installation of Healthy FilterTroubleshooting Can not start up Malfunction of four-way valve Is not on, then replace the protector Adjust support washer of compressor, Troubleshooting YELLOW-LED4 GREEN-LED2 RED-LED3 Analysis or processing of some of the malfunction display How to Check simply the main part Troubleshooting Comp Page AP1 Troubleshooting Is stop time of the compressor longer than 3 minutes? Minutes after the complete unit is powered off Start If the fault is eliminated? Troubleshooting Flow chart for outdoor communitcation circuit detecting Troubleshooting Guide Troubleshooting Guide Temp Resistance 2-way, 3-way Valve Appearance Way Valve Liquid SideProcedure Close Close Open Close Balance Refrigerant of the 3-way Valve Procedure EvacuationGas Charging After EvacuationRemoval Procedure Removal Procedure Removal Procedure Removal Procedure of Outdoor Unit Removal Procedure Removal Procedure MW09C1H / MW12C1H Exploded Diagram MW09C1H Parts List MW12C1H Parts List MR09C1H Exploded Diagram MR09C1H Parts List MR12C1H Exploded View MR12C1H Parts List Page Friedrich AIR Conditioning CO