Troubleshooting

Mainly detect:

Detect the indoor and outdoor units connection wire and indoor and outdoor units inside wiring is connect well or not, if is there any damage?

Is there any damage for the indoor unit mainboard communication circuit? Is communication circuit damaged? The flow chart for malfunction detect:

Start

Did the equipment operate

normally before the failure

Yoccurs?

N

Check the wiring of the indoor and

outdoor units with reference to the wiring diagram

The AP1 voltage detection circuit is at fault

If the fault is eliminated?

Y

N

Check wiring inside of

the indoor and outdoor Y

units N

Are wires broken?

N

Check the communication circuit of the outdoor unit

The communication

 

 

 

 

 

Replace the main board

 

Y

 

circuit is abnormal

 

 

 

AP1 of the outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

 

If the fault is eliminated?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

Replace the main board

 

 

 

 

 

 

 

 

of the indoor unit

 

 

 

 

 

 

 

Is the connection right?

N

Correctly connect the corresponding wires for the indoor and outdoor units with reference to the wiring diagram

If the fault is eliminated?

Y

Y End Y

61

Image 61
Contents Split Type Room AIR Conditioner Wall Mounted Type Table of Contents Model and product code Summary and features Important Safety Information Refrigeration System Repair Hazards Property Damage Hazards Specifications 115 MR09C1H MR12C1H Appending date Expanded capacity data tables for both cooling and heating Operation Characteristic Curve 09KUnits Construction Views Refrigerant System Diagram Electrical Date Electrical wiringCooling Models TOP View Bottom View Bottom View Function and Control Remote Control OperationsAuto Timer on Displayed. If the light is tunrned off Disappears Replacement of Batteries Description of Each Control Operation Function and Control Function and Control Setting+ 2, medium speed Tring ≤ Tsetting 2, low speed P2 Maximum cooling and heating Frequency Control Detection of temperature sensor malfunction3-minutes Standby Compressor Protection FunctionInput Current Control Discharge Pipe ControlFreeze-up Protection Control Detail Conditions for Start Controlling Tap Control in indoor/outdoor unit silent operation Fan ControlImportant Notices Ground requirements Installation dimension diagram Boring Piping Hole Installing Indoor Unit Installing Outdoor Unit Electric wiringCheck after Installation and Operation Test Check after InstallationInstallation of Healthy Filter Installation and Maintenance of Healthy FilterOptionalTroubleshooting Can not start up Malfunction of four-way valve Is not on, then replace the protector Adjust support washer of compressor, Troubleshooting YELLOW-LED4 GREEN-LED2 RED-LED3 Analysis or processing of some of the malfunction display How to Check simply the main part Troubleshooting Comp Page AP1 Troubleshooting Is stop time of the compressor longer than 3 minutes? Minutes after the complete unit is powered off Start If the fault is eliminated? Troubleshooting Flow chart for outdoor communitcation circuit detecting Troubleshooting Guide Troubleshooting Guide Temp Resistance Way Valve Liquid Side 2-way, 3-way Valve AppearanceProcedure Close Close Open Close Balance Refrigerant of the 3-way Valve Evacuation ProcedureAfter Evacuation Gas ChargingRemoval Procedure Removal Procedure Removal Procedure Removal Procedure of Outdoor Unit Removal Procedure Removal Procedure MW09C1H / MW12C1H Exploded Diagram MW09C1H Parts List MW12C1H Parts List MR09C1H Exploded Diagram MR09C1H Parts List MR12C1H Exploded View MR12C1H Parts List Page Friedrich AIR Conditioning CO