Troubleshooting
Balance Refrigerant of the 3-way Valve
(Gas leakage)
Indoor unit | Liquid side |
|
Outdoor unit
valve Open
Gas side
valve Open
Lo
OPEN CLOSE
• Procedure
(1)Confirm that both the
(2)Connect the charge set to the
–Leave the valve on the charge set closed.
–Connect the charge hose to the service port.
(3)Open the valve (Lo side) on the charge set and discharge the refrigerant until the gauge indi- cates 0 kg/cm2G.
–If there is no air in the refrigerant cycle (the pressure when the air conditioner is not running is higher than 1 kg/cm2G), discharge the refrig- erant until the gauge indicates 0.5 to 1 kg/cm2G. if this is the case, it will not be neces- sary to apply a evacuatin.
–Discharge the refrigerant gradually; if it is dis- charged too suddenly, the refrigeration oil will also be discharged.
71