Friedrich MW09C1H Discharge Pipe Control, Input Current Control, Freeze-up Protection Control

Page 33

Function and Control

6.7 Discharge Pipe Control

Outline

The discharge pipe temperature is used as the compressor’s internal temperature. If the discharge pipe temperature rises above a certain level, the operating frequency upper limit is set to keep this temperature from going up further.

Detail

Divide the Zone

 

Stop zone

 

Drooping zone

 

Keep zone

 

Up zone

Heat exchanger

Reset zone

thermistor

 

temperature

 

Management within the Zones

 

 

Zone

Control contents

 

 

Stop zone

When the temperature reaches the stop zone, stop the compressor and

 

correct abnormality.

 

 

Drooping zone

Start the timer, and the frequency will be drooping.

 

 

Keep zone

Keep the upper limit of frequency.

 

 

Return / Reset zone

Cancel the upper limit of frequency.

 

 

6.8 Input Current Control

Outline

Detect an input current by the CT during the compressor is running, and set the frequency upper limit from such input current.

In case of heat pump model, this control is the upper limit control function of the frequency which takes priority of the lower limit of four way valve activating compensation.

Detail

The frequency control will be made within the following zones.

2 Hz drooping

 

 

 

 

1.0second after

 

After 2.5 seconds

rushing in the

 

 

 

Compressor stops

 

 

 

drooping zone

 

 

 

 

 

 

 

 

1

 

 

 

Stop zone

 

 

 

 

2

 

 

 

Drooping zone

 

 

 

 

3

 

 

 

Keep zone

 

 

 

 

 

 

Reset zone

When a “stop current” continues for 2.5 seconds after rushing on the stop zone, the compressor operation stops.

If a “drooping current” is continues for 1.0 second after rushing on the drooping zone, the frequency will be 2 Hz drooping. Repeating the above drooping continues until the current rushes on the drooping zone without change.

In the keep zone, the frequency limit will remain.

In the return / reset zone, the frequency limit will be cancelled.

Limitation of current drooping and stop value according to the outdoor air temperature

1. In case the operation mode is cooling

*The current droops when outdoor air temperature becomes higher than a certain level (model by model). 2. In case the operation mode is heating

*The current droops when outdoor air temperature becomes higher than a certain level (model by model).

6.9 Freeze-up Protection Control

Outline

33

Image 33
Contents Split Type Room AIR Conditioner Wall Mounted Type Table of Contents Model and product code Summary and features Important Safety Information Refrigeration System Repair Hazards Property Damage Hazards Specifications 115 MR09C1H MR12C1H Appending date Expanded capacity data tables for both cooling and heating Operation Characteristic Curve 09KUnits Construction Views Refrigerant System Diagram Electrical Date Electrical wiringCooling Models TOP View Bottom View Bottom View Function and Control Remote Control OperationsAuto Timer on Displayed. If the light is tunrned off Disappears Replacement of Batteries Description of Each Control Operation Function and Control Function and Control Setting+ 2, medium speed Tring ≤ Tsetting 2, low speed P2 Maximum cooling and heating Frequency Control Detection of temperature sensor malfunction3-minutes Standby Compressor Protection FunctionDischarge Pipe Control Input Current ControlFreeze-up Protection Control Detail Conditions for Start Controlling Tap Control in indoor/outdoor unit silent operation Fan ControlImportant Notices Ground requirements Installation dimension diagram Boring Piping Hole Installing Indoor Unit Installing Outdoor Unit Electric wiringCheck after Installation and Operation Test Check after InstallationInstallation of Healthy Filter Installation and Maintenance of Healthy FilterOptionalTroubleshooting Can not start up Malfunction of four-way valve Is not on, then replace the protector Adjust support washer of compressor, Troubleshooting YELLOW-LED4 GREEN-LED2 RED-LED3 Analysis or processing of some of the malfunction display How to Check simply the main part Troubleshooting Comp Page AP1 Troubleshooting Is stop time of the compressor longer than 3 minutes? Minutes after the complete unit is powered off Start If the fault is eliminated? Troubleshooting Flow chart for outdoor communitcation circuit detecting Troubleshooting Guide Troubleshooting Guide Temp Resistance Way Valve Liquid Side 2-way, 3-way Valve AppearanceProcedure Close Close Open Close Balance Refrigerant of the 3-way Valve Evacuation ProcedureAfter Evacuation Gas ChargingRemoval Procedure Removal Procedure Removal Procedure Removal Procedure of Outdoor Unit Removal Procedure Removal Procedure MW09C1H / MW12C1H Exploded Diagram MW09C1H Parts List MW12C1H Parts List MR09C1H Exploded Diagram MR09C1H Parts List MR12C1H Exploded View MR12C1H Parts List Page Friedrich AIR Conditioning CO