Friedrich MR09C1H, MW12C1H, MW09C1H, MR12C1H manual Malfunction of four-way valve

Page 46

Troubleshooting

 

Improper set of temperature

 

 

Adjust set temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If cooling (heating) load is

 

 

 

Check the forecasted load of cooling (heating)

 

 

 

 

 

proper

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Malfunction of refrigerant flow

The refrigerant has leakage or is insufficient

Leakage between the high pres- sure and the low pressure in- side the compressor

Malfunction of four-way valve

heck and fill the leakage, then vacuumize it and supplement the re- frigerant as required

Replace the compressor

Replace the four-way valve

COOL(HEAT) operation

Local block of capillary

Blockage of cooling system

Replace the capillary

Judge whether the system is blocked by observing the condensation of evapora- tor and the pressure value of the high pressure manometer and take measures to deal with the system.

Poor

Heat insulation for the connection

 

Make sure that heat insulation for the thick and thin pipes

 

 

pipes of the indoor unit and the out-

 

is good. Heat insulation must also be provided for the

 

door unit is bad.

 

 

joint andthe exposed part of the copper pipe .

 

 

Block of outdoor heat ex-

 

 

 

 

 

 

 

Clean the dust accumulated on the surface of

 

 

 

changer

 

 

the heat exchanger.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air circulation is insufficient

Air filter were blocked

Fan speed was set too slow

Fan rotation speed becomes

low

Clean the filter

To set the fan speed to high or middle speed

 

 

 

 

Replace the capaci-

Capacitor

 

 

 

 

tor

damage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor damage

 

 

 

Replace the motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The installation position of the

 

 

Good ventilation must be provided for the

outdoor unit is not appropriate.

installation position of the outdoor unit.

 

 

 

 

 

 

 

 

 

 

 

Properly install the rainproof plate or the sunproof plate. If the

The outdoor temperature is too high.

 

 

 

 

 

 

 

 

 

 

 

maximum cool air still can not meet the requirement, it is sug-

 

 

 

 

gested to replace the air conditioner.

 

 

 

 

 

 

 

 

 

 

The air tightness is not enough. People

 

 

 

Keep certain air tightness indoors, try not to use

come in and out too frequently. There

 

 

 

 

 

 

electricalappliance with large quantity of heat

are heating devices indoors.

 

 

 

 

 

 

 

 

 

 

 

 

46

Image 46
Contents Split Type Room AIR Conditioner Wall Mounted Type Table of Contents Model and product code Summary and features Important Safety Information Refrigeration System Repair Hazards Property Damage Hazards Specifications 115 MR09C1H MR12C1H Appending date Expanded capacity data tables for both cooling and heating Operation Characteristic Curve 09KUnits Construction Views Refrigerant System Diagram Electrical wiring Electrical DateCooling Models TOP View Bottom View Bottom View Remote Control Operations Function and ControlAuto Timer on Displayed. If the light is tunrned off Disappears Replacement of Batteries Description of Each Control Operation Function and Control Function and Control Setting+ 2, medium speed Tring ≤ Tsetting 2, low speed P2 Maximum cooling and heating 3-minutes Standby Detection of temperature sensor malfunctionFrequency Control Compressor Protection FunctionInput Current Control Discharge Pipe ControlFreeze-up Protection Control Detail Conditions for Start Controlling Fan Control Tap Control in indoor/outdoor unit silent operationImportant Notices Ground requirements Installation dimension diagram Boring Piping Hole Installing Indoor Unit Electric wiring Installing Outdoor UnitCheck after Installation Check after Installation and Operation TestInstallation and Maintenance of Healthy FilterOptional Installation of Healthy FilterTroubleshooting Can not start up Malfunction of four-way valve Is not on, then replace the protector Adjust support washer of compressor, Troubleshooting YELLOW-LED4 GREEN-LED2 RED-LED3 Analysis or processing of some of the malfunction display How to Check simply the main part Troubleshooting Comp Page AP1 Troubleshooting Is stop time of the compressor longer than 3 minutes? Minutes after the complete unit is powered off Start If the fault is eliminated? Troubleshooting Flow chart for outdoor communitcation circuit detecting Troubleshooting Guide Troubleshooting Guide Temp Resistance 2-way, 3-way Valve Appearance Way Valve Liquid SideProcedure Close Close Open Close Balance Refrigerant of the 3-way Valve Procedure EvacuationGas Charging After EvacuationRemoval Procedure Removal Procedure Removal Procedure Removal Procedure of Outdoor Unit Removal Procedure Removal Procedure MW09C1H / MW12C1H Exploded Diagram MW09C1H Parts List MW12C1H Parts List MR09C1H Exploded Diagram MR09C1H Parts List MR12C1H Exploded View MR12C1H Parts List Page Friedrich AIR Conditioning CO