Hitachi SJ700-2 Series service manual

Page 25

1.3.1Example of operation in basic display mode ("b037" = "04" [factory setting])

-Only basic parameters can be displayed in basic display mode. (All parameters in monitor mode, four parameters in function mode, or 20 parameters in extended function mode)

-Other parameters are not displayed. To display all parameters, select the full display mode ("b037" = "00").

<Displayable parameters and sequence of display>

No.

Display code

Item

1

d001 to d104

Monitor display

2

F001

Output frequency setting

3

F002

Acceleration (1) time setting

4

F003

Deceleration (1) time setting

5

F004

Operation direction setting

6

A001

Frequency source setting

7

A002

Run command source setting

8

A003

Base frequency setting

9

A004

Maximum frequency setting

10

A005

[AT] selection

11

A020

Multispeed frequency setting

12

A021

Multispeed 1 setting

13

A022

Multispeed 2 setting

14

A023

Multispeed 3 setting

15

A044

1st control method

16

A045

V/f gain setting

17

A085

Operation mode selection

18

b001

Selection of restart mode

19

b002

Allowable under-voltage power failure time

20

b008

Retry-after-trip selection

21

b011

Retry wait time after trip

22

b037

Function code display restriction

23

b083

Carrier frequency setting

24

b084

Initialization mode selection

25

b130

Selection of overvoltage suppression

function

 

 

26

b131

Setting of overvoltage suppression level

27

C021

Setting of intelligent output terminal 11

28

C022

Setting of intelligent output terminal 12

29

C036

Alarm relay active state

Note:

If a desired parameter is not displayed, check the setting of function "b037" (function code display restriction). To display all parameters, specify "00" for "b037".

1 - 21

Image 25
Contents SJ700-2 Series NTS204X Table of contents Appendix Investigation of the inverter Specification labelModel name,Manufacturing numberMFGPrecautions for Data Setting Function Mode Extended Function Mode PID FEF FUF AVR Electronic thermal characteristic, 2nd B034 Free-setting V/f frequency To 400. Hz FEF FUF FEF FUF FF FEF FUF Term inal C111 FEF FUF FEF FUF RPM Specification FEF FUF FEF FUF Code display system and key operations Page Corresponding to the function code. Data display *1*2 STR key after changing the data Example of operation in full display mode b037 =Pressing the STR key Inverter trip contents,remedy,advise TroubleshootingCPU GA.COM Adjust OFF Option boards error codesInput mode specified by switch settings Setting of MAC ID DIP switches No to No Error code is output when the relevant program runs Trip conditions monitoring 305 A004/A204/A304 A202/A220/A320 *2 006 Initialization setting Page Monitor Modes Debug ModeFunction Modes Setting procedure Inverter SettingHFF/-HFUF/-HFEF Confirming the completion of initializationVDC Control signalPage Daily inspection CleaningPeriodic inspection Daily and Periodic Inspections Ground Resistance Test with a Megger Method of Checking the Inverter and Converter Circuits Replacing Parts Page Page Inverter Replacement Control board SJ700-055-110LF**2 Circuit Diagram Ground Terminal With Jumper SJ700-150LF**2 185LF**2 Circuit DiagramSJ700-220LF**2 Circuit Diagram SJ700-300LF**2 Circuit Diagram SJ700-370LF**2 Circuit Diagram Driver Board SJ700-450LF**2 Circuit DiagramSJ700-550LF**2 Circuit Diagram SJ700-055-110HF**2 Circuit Diagram SJ700-150HF**2 Circuit Diagram SJ700-185HF**2 220HF**2 Circuit Diagram SJ700-300HF**2 Circuit DiagramSJ700-370HF**2 Circuit Diagram TMC CN1 Page Page Page Page Page Page Page Page Page Page Page