3.4 Inverter Setting

The logic board is common to all inverter models. If you change the inverter capacity or voltage class, you must also adjust the relevant settings of the logic board to those of the inverter.

3.4.1 Setting procedure

(1) Prepare for power-on.

(1.1) Connect the digital operator to the inverter.

(2) Turn the inverter power on.

(2.1) Select "00" (ALL) for the display selection (b037).

(3)Set the region, output capacity, voltage class, and default data codes. (3.1) Switch the inverter to debug mode.

(Setting method)

Display code "C091" on the monitor, press the FUNC key, enter "01", and then press the STR key. (3.2)Set the region code.

(Setting method)

Display code "C195" on the monitor, press the FUNC key, select one of the codes listed in the table below, and then press the STR key.

Region where to

Region code

use the inverter

(C195)

Japan

JP

Europe

EU

U.S.A.

USA

Note: Do not set any code other than "JP".

(3.3) Set the capacity code. (Setting method)

Display code "C196" on the monitor, press the FUNC key, select one of the codes listed in the table below, and then press the STR key.

Inverter model

Capacity code

(C196)

 

150LF**/150HF**

15.0

185LF**/185HF**

18.5

220LF**/220HF**

22.0

300LF**/300HF**

30.0

370LF**/370HF**

37.0

(3.4) Set the voltage class code. (Setting method)

Display code "C196" on the monitor, press the FUNC key, select one of the codes listed in the table below, and then press the STR key.

Voltage class

Voltage class

(C197)

 

200 V class

200

400 V class

400

(3.5) Select default data. (Setting method)

Display code "b085" on the monitor, press the FUNC key, select one of the codes listed in the table below, and then press the STR key.

Region where to

Default data code

use the inverter

(b085)

for Japan

00

for Europe

01

for the U.S.A.

02

(4)Perform data initialization. (See Section 2.5.)

(5)After initialization ends (with code "d001" displayed on the monitor), turn the inverter power off.

(6)Turn the inverter power on.

3-3

Image 43
Contents SJ700-2 Series NTS204X Table of contents Appendix Investigation of the inverter Specification labelModel name,Manufacturing numberMFGPrecautions for Data Setting Function Mode Extended Function Mode PID FEF FUF AVR Electronic thermal characteristic, 2nd B034 Free-setting V/f frequency To 400. Hz FEF FUF FEF FUF FF FEF FUF Term inal C111 FEF FUF FEF FUF RPM Specification FEF FUF FEF FUF Code display system and key operations Page Corresponding to the function code. Data display *1*2 STR key after changing the data Example of operation in full display mode b037 =Pressing the STR key Inverter trip contents,remedy,advise TroubleshootingCPU GA.COM Adjust OFF Option boards error codesInput mode specified by switch settings Setting of MAC ID DIP switches No to No Error code is output when the relevant program runs Trip conditions monitoring 305 A004/A204/A304 A202/A220/A320 *2 006 Initialization setting Page Monitor Modes Debug ModeFunction Modes Setting procedure Inverter SettingHFF/-HFUF/-HFEF Confirming the completion of initializationVDC Control signalPage Daily inspection CleaningPeriodic inspection Daily and Periodic Inspections Ground Resistance Test with a Megger Method of Checking the Inverter and Converter Circuits Replacing Parts Page Page Inverter Replacement Control board SJ700-055-110LF**2 Circuit Diagram Ground Terminal With Jumper SJ700-150LF**2 185LF**2 Circuit DiagramSJ700-220LF**2 Circuit Diagram SJ700-300LF**2 Circuit Diagram SJ700-370LF**2 Circuit Diagram Driver Board SJ700-450LF**2 Circuit DiagramSJ700-550LF**2 Circuit Diagram SJ700-055-110HF**2 Circuit Diagram SJ700-150HF**2 Circuit Diagram SJ700-185HF**2 220HF**2 Circuit Diagram SJ700-300HF**2 Circuit DiagramSJ700-370HF**2 Circuit Diagram TMC CN1 Page Page Page Page Page Page Page Page Page Page Page