Hitachi SJ700-2 Series service manual

Page 52

3)Removing the sheet-metal-case type of cooling-fan unit <1> Remove the terminal block cover and front cover. <2> Make sure that the Charge lamp goes off.

<3> Remove the screws at the top.

<4> Lift the cooling-fan mounting plate to remove it from the inverter. <5> Remove the fan connector.

<6> Remove the cooling fans from the cooling-fan mounting plate.

4) Mounting the sheet-metal-case type of cooling-fan unit

<1> Attach the cooling fans to the cooling-fan mounting plate so that the fans are oriented correctly.

<2> Connect the fan connector to terminal J21, J22, or J23 (depending on the inverter model) of the main circuit board.

<3> Mount the cooling-fan mounting plate on the inverter and secure it with screws. <4> Mount the front cover and terminal block cover.

Position the cooling-fan unit so that its nameplate faces this side.

(2) Smoothing capacitors

The DC section of the inverter main circuit uses high-capacity aluminum electrolytic capacitors as smoothing filter components. Since chemical reactions occur inside the capacitors, the service life of these parts largely depends on the ambient temperature and operating conditions. Capacitors used in a standard operating environment must be replaced after about 10 years. However, each capacitor must be immediately replaced if found abnormal upon a visual inspection or if periodic inspection finds capacity to be 80% or less of the rating.

1) Removing the molded-case type of smoothing capacitors

(note)This feature to remove the smoothing capacitor easily is not available for the mold case type(up to 11Kw) <1> Remove the terminal block cover.

<2> Make sure that the Charge lamp goes off. <3> Remove the backing plate.

<4> Remove the screws connecting the capacitor unit to the main circuit terminal block. <5> Remove the screws fixing the capacitor mounting plate to the inverter casing.

<6> Pull down the capacitor mounting plate.

<7> Remove the capacitor unit from the capacitor mounting plate.

5 - 6

Image 52
Contents SJ700-2 Series NTS204X Table of contents Appendix Specification labelModel name,Manufacturing numberMFG Investigation of the inverterPrecautions for Data Setting Function Mode Extended Function Mode PID FEF FUF AVR Electronic thermal characteristic, 2nd B034 Free-setting V/f frequency To 400. Hz FEF FUF FEF FUF FF FEF FUF Term inal C111 FEF FUF FEF FUF RPM Specification FEF FUF FEF FUF Code display system and key operations Page Corresponding to the function code. Data display *1*2 Example of operation in full display mode b037 = STR key after changing the dataPressing the STR key Troubleshooting Inverter trip contents,remedy,adviseCPU GA.COM Adjust Option boards error codes OFFInput mode specified by switch settings Setting of MAC ID DIP switches No to No Error code is output when the relevant program runs Trip conditions monitoring 305 A004/A204/A304 A202/A220/A320 *2 006 Initialization setting Page Debug Mode Monitor ModesFunction Modes Inverter Setting Setting procedureConfirming the completion of initialization HFF/-HFUF/-HFEFControl signal VDCPage Daily inspection CleaningPeriodic inspection Daily and Periodic Inspections Ground Resistance Test with a Megger Method of Checking the Inverter and Converter Circuits Replacing Parts Page Page Inverter Replacement Control board SJ700-055-110LF**2 Circuit Diagram SJ700-150LF**2 185LF**2 Circuit Diagram Ground Terminal With JumperSJ700-220LF**2 Circuit Diagram SJ700-300LF**2 Circuit Diagram SJ700-370LF**2 Circuit Diagram SJ700-450LF**2 Circuit Diagram Driver BoardSJ700-550LF**2 Circuit Diagram SJ700-055-110HF**2 Circuit Diagram SJ700-150HF**2 Circuit Diagram SJ700-185HF**2 220HF**2 Circuit Diagram Circuit Diagram SJ700-300HF**2SJ700-370HF**2 Circuit Diagram TMC CN1 Page Page Page Page Page Page Page Page Page Page Page