3.2 Function Modes
No. | Function name | Function code | Range of data |
5 | Function for factory adjustment | Change inhibited | |
6 | Region code for inverter | C195 | JP (intended for Japan) |
7 | Capacity code for inverter | C196 | 0.2 to 55.0 (kW) |
8 | Voltage class code for inverter | C197 | 200 (200 V class) or 400 (400 V class) |
9 | Inverter mode | C198 | 00(SJ700) |
3.3 How To Reference the Data Area (d105) Corresponding to Trip History
In the data area you can directly reference the factors (determined by the gate array) of the past six trips. Do not change the value set as "C172".
(1)Specify "FFFF" for "C170".
(2)Specify "A56A" for "C171".
(3)Reference the data of "C172". Record the last two digits of the data. (The range of data is "**00" to "**05".)
(4)Specify one of the values listed in the table below for "C171" according to the target trip history data and the value of "C172".
Target |
|
| Value of "C172" |
|
| |
history | **00 | **01 | **02 | **03 | **04 | **05 |
data |
|
|
|
|
|
|
d081 | A56E | A582 | A596 | A5AA | A5BE | A5D2 |
d082 | A5D2 | A56E | A582 | A596 | A5AA | A5BE |
d083 | A5BE | A5D2 | A56E | A582 | A596 | A5AA |
d084 | A5AA | A5BE | A5D2 | A56E | A582 | A596 |
d085 | A596 | A5AA | A5BE | A5D2 | A56E | A582 |
d086 | A582 | A596 | A5AA | A5BE | A5D2 | A56E |
Example 1: Referencing the history data of "d083" when "C172" is "**02"
(1)As shown in the above table, the data of "d083" is "A56E" when "C172" is "**02".
(2)Specify "A56E" for "C171".
(5)Reference the value displayed as "C172". The first two digits of the
□□□□
Code of the trip factor determined by gate array
Example 2:
When the value of "C172" is "08**", the trip factor is overvoltage protection because bit 3 is "1".