Hitachi SJ700-2 Series service manual Function Modes

Page 42

3.2 Function Modes

No.

Function name

Function code

Range of data

5

Function for factory adjustment

C170-C194

Change inhibited

6

Region code for inverter

C195

JP (intended for Japan)

7

Capacity code for inverter

C196

0.2 to 55.0 (kW)

8

Voltage class code for inverter

C197

200 (200 V class) or 400 (400 V class)

9

Inverter mode

C198

00(SJ700)

3.3 How To Reference the Data Area (d105) Corresponding to Trip History

In the data area you can directly reference the factors (determined by the gate array) of the past six trips. Do not change the value set as "C172".

(1)Specify "FFFF" for "C170".

(2)Specify "A56A" for "C171".

(3)Reference the data of "C172". Record the last two digits of the data. (The range of data is "**00" to "**05".)

(4)Specify one of the values listed in the table below for "C171" according to the target trip history data and the value of "C172".

Target

 

 

Value of "C172"

 

 

history

**00

**01

**02

**03

**04

**05

data

 

 

 

 

 

 

d081

A56E

A582

A596

A5AA

A5BE

A5D2

d082

A5D2

A56E

A582

A596

A5AA

A5BE

d083

A5BE

A5D2

A56E

A582

A596

A5AA

d084

A5AA

A5BE

A5D2

A56E

A582

A596

d085

A596

A5AA

A5BE

A5D2

A56E

A582

d086

A582

A596

A5AA

A5BE

A5D2

A56E

Example 1: Referencing the history data of "d083" when "C172" is "**02"

(1)As shown in the above table, the data of "d083" is "A56E" when "C172" is "**02".

(2)Specify "A56E" for "C171".

(5)Reference the value displayed as "C172". The first two digits of the 4-digit value displayed correspond to the value of "d105".

□□□□

Code of the trip factor determined by gate array

Example 2:

When the value of "C172" is "08**", the trip factor is overvoltage protection because bit 3 is "1".

3-2

Image 42
Contents SJ700-2 Series NTS204X Table of contents Appendix Specification labelModel name,Manufacturing numberMFG Investigation of the inverterPrecautions for Data Setting Function Mode Extended Function Mode PID FEF FUF AVR Electronic thermal characteristic, 2nd B034 Free-setting V/f frequency To 400. Hz FEF FUF FEF FUF FF FEF FUF Term inal C111 FEF FUF FEF FUF RPM Specification FEF FUF FEF FUF Code display system and key operations Page Corresponding to the function code. Data display *1*2 Example of operation in full display mode b037 = STR key after changing the dataPressing the STR key Troubleshooting Inverter trip contents,remedy,adviseCPU GA.COM Adjust Option boards error codes OFFInput mode specified by switch settings Setting of MAC ID DIP switches No to No Error code is output when the relevant program runs Trip conditions monitoring 305 A004/A204/A304 A202/A220/A320 *2 006 Initialization setting Page Debug Mode Monitor ModesFunction Modes Inverter Setting Setting procedureConfirming the completion of initialization HFF/-HFUF/-HFEFControl signal VDCPage Cleaning Daily inspectionPeriodic inspection Daily and Periodic Inspections Ground Resistance Test with a Megger Method of Checking the Inverter and Converter Circuits Replacing Parts Page Page Inverter Replacement Control board SJ700-055-110LF**2 Circuit Diagram SJ700-150LF**2 185LF**2 Circuit Diagram Ground Terminal With JumperSJ700-220LF**2 Circuit Diagram SJ700-300LF**2 Circuit Diagram SJ700-370LF**2 Circuit Diagram SJ700-450LF**2 Circuit Diagram Driver BoardSJ700-550LF**2 Circuit Diagram SJ700-055-110HF**2 Circuit Diagram SJ700-150HF**2 Circuit Diagram SJ700-185HF**2 220HF**2 Circuit Diagram Circuit Diagram SJ700-300HF**2SJ700-370HF**2 Circuit Diagram TMC CN1 Page Page Page Page Page Page Page Page Page Page Page