Name | Description |
|
| Display on |
| Display on remote | Troubleshooting and corrective action | ||||||||
| digital operator |
|
| operator | |||||||||||
|
|
|
|
|
|
|
| ||||||||
| The inverter detects errors in the option |
|
|
|
|
|
|
|
|
|
| Check whether the option board is | |||
| board mounted in the optional slot 2. |
|
|
|
|
|
|
|
| mounted correctly. | |||||
Option 2 | For details, refer to the instruction |
|
|
|
|
|
|
|
|
|
| (Check the board mounting.) | |||
| to |
|
|
|
|
| |||||||||
manual for the mounted option board. |
|
|
|
|
|
| Check whether the option board is used | ||||||||
error |
|
|
|
|
|
|
|
|
|
|
|
|
|
| correctly. |
|
|
|
|
|
|
|
|
|
|
|
|
| (Check the instruction manual for the | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| option board.) |
| If the input voltage falls, the inverter will |
|
|
|
|
|
|
|
|
|
| Check whether the power supply voltage | |||
| shut off its output, display the code |
|
|
|
|
|
|
|
|
|
| has fallen. | |||
| shown on the right, and wait for the |
|
|
|
|
|
|
|
|
|
| (Recover the power supply.) | |||
Waiting in | recovery of the input voltage. |
|
|
|
|
|
|
|
|
|
| Check the MCB and magnetic contactors | |||
The inverter will display the same error |
|
|
|
|
|
| UV.WAIT |
|
| for poor contacts. | |||||
undervoltage | code also during an instantaneous |
|
|
|
|
|
|
|
|
|
| (Replace the MCB and magnetic | |||
|
|
|
|
|
|
|
|
|
| ||||||
status | power failure. |
|
|
|
|
|
|
|
|
|
|
| contactors.) | ||
| (remark) Inverter trips with under |
|
|
|
|
|
|
|
|
|
| Check whether the voltage across the P | |||
| voltage when this status continues for |
|
|
|
|
|
|
|
|
|
| and N terminals is normal. | |||
| 40 seconds. |
|
|
|
|
|
|
|
|
|
|
| (Check the voltage across the P and N | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| terminals.) |
| If a problem occurs in the |
|
|
|
|
|
|
|
|
|
|
| Check whether the relay plug is fitted | ||
Communica- | communication between the digital |
|
|
|
|
|
| correctly. | |||||||
operator and inverter, the inverter will |
|
|
|
|
|
|
|
|
|
| (Check the relay plug for connection.) | ||||
tion error | display the code shown on the right. |
|
|
|
|
|
| Check whether the digital operator is | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| connected correctly. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| (Check the digital operator for connection.) |
| When the retry after instantaneous |
|
|
|
|
|
|
|
|
|
|
| |||
Waiting for | power failure or tripping has been |
|
|
|
|
|
| RESTART |
|
|
| ||||
enabled, the inverter displays the code |
|
|
|
|
|
|
|
|
| ||||||
retry | shown on the right while awaiting retry |
|
|
|
|
|
|
|
|
|
|
| |||
| after an instantaneous power failure or |
|
|
|
|
|
| ADJUST |
|
|
| ||||
| tripping. |
|
|
|
|
|
|
|
|
|
|
|
| ||
The inverter displays the code shown |
|
|
|
|
|
|
|
|
|
|
| ||||
on the right when the inverter power is |
|
|
|
|
|
| POWER OFF |
|
|
| |||||
| turned off. |
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| When an operation direction has been |
|
|
|
|
|
|
|
|
|
|
| |||
Restricted | restricted by the setting of "b035", the |
|
|
|
|
|
|
|
|
|
|
| |||
operation | inverter will display the error code |
|
|
|
|
|
| RUN.CMD DISABLE |
| ||||||
shown on the right if the operation |
|
|
|
|
|
|
| ||||||||
command |
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| |||||
command specifying the restricted |
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| ||||
| operation direction is input. |
|
|
|
|
|
|
|
|
|
|
| |||
Empty trip | If the inverter has not tripped before,the |
|
|
|
|
|
|
|
|
|
|
| |||
history | inverter displays |
|
| . |
|
|
|
|
|
|
| ? |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2- 4