Hitachi SJ700-2 Series service manual Precautions for Data Setting

Page 6

1.2 Precautions for Data Setting

The default display mode limits the screens (parameters) that can be displayed on the monitor. To enable the display of all parameters, specify "00" (full display) for the function code display restriction (b037).

To enable the parameters to be changed while the inverter is operating, specify "10" for the software lock mode selection (b031).

1.2.1 Monitoring Mode

Code

Function name

 

 

 

 

 

 

 

 

 

 

 

 

 

Monitored data or setting

Default

Note

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d001

Output frequency monitoring

0.00 to 99.99, 100.0 to 400.0 (Hz)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d002

Output current monitoring

0.0 to 999.9, 1000 to 9999 (A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d003

Rotation direction minitoring

F (forward rotation), o (stopped), r (reverse rotation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d004

Process variable (PV), PID feedback

0.00 to 99.99, 100.0 to 999.9, 1000. to 9999.

 

 

 

 

monitoring

1000 to 9999 (10000 to 99990), 100 to 999 (100000 to 999000)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d005

Intelligent input terminal status

 

 

FW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Example)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminals FW, 7, 2, and 1: ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminals 8, 6, 5, 4, and 3: OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

7

 

5

3

 

2

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d006

Intelligent output terminal status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Example)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminals 12 and 11: ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminals AL, 15, 14, and 13: OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL

15 14

13 12

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d007

Scaled output frequency monitoring

0.00 to 99.99, 100.0 to 999.9, 1000. to 9999., 1000 to 3996 (10000 to 39960)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d008

Actual-frequency monitoring

-400. to -100., -99.9 to 0.00 to 99.99, 100.0 to 400.0 (Hz)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d009

Torque command monitoring

-200. to +200. (%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d010

Torque bias monitoring

-200. to +200. (%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d012

Torque monitoring

-200. to +200. (%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d013

Output voltage monitoring

0.0 to 600.0 (V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d014

Power monitoring

0.0 to 999.9 (kW)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d015

Cumulative power monitoring

0.0 to 999.9, 1000. to 9999.

 

 

 

 

 

 

 

 

 

 

 

1000 to 9999 (10000 to 99990), 100 to 999 (100000 to 999000)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d016

Cumulative operation RUN time

0. to 9999., 1000 to 9999 (10000 to 99990),

100 to

999 (100000 to 999000) (hr)

 

 

 

monitoring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d017

Cumulative power-on time monitoring

0. to 9999., 1000 to 9999 (10000 to 99990),

100 to

999 (100000 to 999000) (hr)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d018

Heat sink temperature monitoring

-020. to 200.0 ( C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d019

Motor temperature monitoring

-020. to 200.0 ( C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d022

Life-check monitoring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1: Capacitor on main circuit board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2: Cooling-fan speed drop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d023

Program counter

0 to 1024

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d024

Program number monitoring

0000 to 9999

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 - 2

Image 6
Contents SJ700-2 Series NTS204X Table of contents Appendix Specification labelModel name,Manufacturing numberMFG Investigation of the inverterPrecautions for Data Setting Function Mode Extended Function Mode PID FEF FUF AVR Electronic thermal characteristic, 2nd B034 Free-setting V/f frequency To 400. Hz FEF FUF FEF FUF FF FEF FUF Term inal C111 FEF FUF FEF FUF RPM Specification FEF FUF FEF FUF Code display system and key operations Page Corresponding to the function code. Data display *1*2 Example of operation in full display mode b037 = STR key after changing the dataPressing the STR key Troubleshooting Inverter trip contents,remedy,adviseCPU GA.COM Adjust Option boards error codes OFFInput mode specified by switch settings Setting of MAC ID DIP switches No to No Error code is output when the relevant program runs Trip conditions monitoring 305 A004/A204/A304 A202/A220/A320 *2 006 Initialization setting Page Debug Mode Monitor ModesFunction Modes Inverter Setting Setting procedureConfirming the completion of initialization HFF/-HFUF/-HFEFControl signal VDCPage Cleaning Daily inspectionPeriodic inspection Daily and Periodic Inspections Ground Resistance Test with a Megger Method of Checking the Inverter and Converter Circuits Replacing Parts Page Page Inverter Replacement Control board SJ700-055-110LF**2 Circuit Diagram SJ700-150LF**2 185LF**2 Circuit Diagram Ground Terminal With JumperSJ700-220LF**2 Circuit Diagram SJ700-300LF**2 Circuit Diagram SJ700-370LF**2 Circuit Diagram SJ700-450LF**2 Circuit Diagram Driver BoardSJ700-550LF**2 Circuit Diagram SJ700-055-110HF**2 Circuit Diagram SJ700-150HF**2 Circuit Diagram SJ700-185HF**2 220HF**2 Circuit Diagram Circuit Diagram SJ700-300HF**2SJ700-370HF**2 Circuit Diagram TMC CN1 Page Page Page Page Page Page Page Page Page Page Page