Hitachi SJ700-2 Series service manual Pid

Page 9

 

 

 

 

 

Default

 

 

Code

Function name

Monitored data or setting

 

 

 

Note

 

 

 

 

_FF

_FEF

_FUF

 

 

 

 

 

 

 

 

 

 

A041

Torque boost method selection

00 (manual torque boost), 01 (automatic torque boost)

 

00

 

 

 

A241

Torque boost method selection,

00 (manual torque boost), 01 (automatic torque boost)

 

00

 

 

 

2nd motor

 

 

 

 

 

 

 

 

 

 

 

A042

Manual torque boost value

0.0 to 20.0 (%)

 

1.0

 

 

 

A242

Manual torque boost value, 2nd

0.0 to 20.0 (%)

 

1.0

 

 

 

motor

 

 

 

 

 

 

 

 

 

 

 

A342

Manual torque boost value, 3rd

0.0 to 20.0 (%)

 

1.0

 

 

 

motor

 

 

 

 

 

 

 

 

 

 

 

A043

Manual torque boost frequency

0.0 to 50.0 (%)

 

5.0

 

 

 

adjustment

 

 

 

 

 

 

 

 

 

 

 

A243

Manual torque boost frequency

0.0 to 50.0 (%)

 

5.0

 

 

 

adjustment, 2nd motor

 

 

 

 

 

 

 

 

 

 

 

A343

Manual torque boost frequency

0.0 to 50.0 (%)

 

5.0

 

 

characteristic

adjustment, 3rd motor

 

 

 

 

 

 

 

 

 

A044

V/F characteristic curve

00 (VC), 01 (VP), 02 (free V/f), 03 (sensorless vector control), 04 (0Hz-range

 

00

 

 

selection, 1st motor

sensorless vector), 05 (vector with sensor)

 

 

 

 

 

 

 

 

A244

V/F characteristic curve

00 (VC), 01 (VP), 02 (free V/f), 03 (sensorless vector control), 04 (0Hz-range

 

00

 

 

selection, 2nd motor

sensorless vector)

 

 

 

V/f

 

 

 

 

 

A344

V/F characteristic curve

00(VC), 01(VP)

 

00

 

 

 

 

 

 

 

selection, 3rd motor

 

 

 

 

 

 

 

 

 

 

 

A045

V/f gain setting

20. to 100. (%)

 

100.

 

 

 

 

Voltage compensation gain

 

 

 

 

 

 

A046

setting for automatic torque

0. to 255.

 

100.

 

 

 

 

boost. 1st motor

 

 

 

 

 

 

 

Voltage compensation gain

 

 

 

 

 

 

A246

setting for automatic torque

0. to 255.

 

100.

 

 

 

 

boost, 2nd motor

 

 

 

 

 

 

 

Slippage compensation gain

 

 

 

 

 

 

A047

setting for automatic torque

0. to 255.

 

100.

 

 

 

 

boost, 1st motor

 

 

 

 

 

 

 

Slippage compensation gain

 

 

 

 

 

 

A247

setting for automatic torque

0. to 255.

 

100.

 

 

 

 

boost, 2nd motor

 

 

 

 

 

 

A051

DC braking enable

00 (disabling), 01 (enabling), 02 (set frequency only)

 

00

 

 

 

A052

DC braking frequency setting

0.00 to 99.99, 100.0 to 400.0 (Hz)

 

0.50

 

 

 

A053

DC braking wait time

0.0 to 5.0 (s)

 

0.0

 

 

 

A054

DC braking force during

0. to 100. (%)

 

0.

 

 

braking

deceleration

 

 

 

 

 

 

 

 

 

A055

DC braking time for deceleration

0.0 to 60.0 (s)

 

0.0

 

 

 

DC braking/edge or level

 

 

 

 

 

DC

A056

00 (edge operation), 01 (level operation)

 

01

 

 

detection for [DB] input

 

 

 

 

 

 

 

 

 

 

 

A057

DC braking force for starting

0. to 100.(%)

 

0.

 

 

 

A058

DC braking time for starting

0.0 to 60.0(s)

 

0.0

 

 

 

A059

DC braking carrier frequency

0.5 to 15.0(kHz)

 

5.0

 

 

 

setting

 

 

 

 

 

 

 

 

 

 

 

A061

Frequency upper limit setting

0.00 or "1st minimum frequency limit" to "maximum frequency" (Hz)

 

0.00

 

 

 

A261

Frequency upper limit setting,

0.00 or "2nd minimum frequency limit" to "maximum frequency, 2nd motor" (Hz)

 

0.00

 

 

 

2nd motor

 

 

 

 

 

 

 

 

 

 

frequency

A062

Frequency lower limit setting

0.00 or "start frequency" to "maximum frequency limit"

 

0.00

 

 

(Hz)

 

 

 

 

 

 

 

 

 

A262

Frequency lower limit setting,

0.00 or "start frequency" to "maximum frequency, 2nd motor limit"

 

0.00

 

 

2nd motor

(Hz)

 

 

 

 

 

 

 

 

jump

A063

Jump (center) frequency setting

0.00 to 99.99, 100.0 to 400.0 (Hz)

 

0.00

 

 

1

 

 

 

and

A064

Jump (hysteresis) frequency

0.00 to 10.00 (Hz)

 

0.50

 

 

limit

width setting 1

 

 

 

 

 

 

 

 

 

 

Jump (center) frequency setting

 

 

 

 

 

upper/lower

A065

0.00 to 99.99, 100.0 to 400.0 (Hz)

 

0.00

 

 

2

 

 

 

 

 

 

 

 

 

A066

Jump (hysteresis) frequency

0.00 to 10.00 (Hz)

 

0.50

 

 

width setting 2

 

 

 

 

 

 

 

 

 

 

Jump (center) frequency setting

 

 

 

 

 

Frequency

A067

0.00 to 99.99, 100.0 to 400.0 (Hz)

 

0.00

 

 

3

 

 

 

 

 

 

 

 

 

A068

Jump (hysteresis) frequency

0.00 to 10.00 (Hz)

 

0.50

 

 

width setting 3

 

 

 

 

A069

Acceleration stop frequency

0.00 to 99.99, 100.0 to 400.0 (Hz)

 

0.00

 

 

 

setting

 

 

 

 

 

 

 

 

 

 

 

A070

Acceleration stop time frequency

0.0 to 60.0 (s)

 

0.0

 

 

 

 

setting

 

 

 

 

 

 

A071

PID Function Enable

00 (disabling), 01 (enabling), 02 (enabling inverted-data output)

 

00

 

 

 

A072

PID proportional gain

0.2 to 5.0

 

1.0

 

 

 

A073

PID integral time constant

0.0 to 999.9, 1000. to 3600. (s)

 

1.0

 

 

control

A074

PID derivative gain

0.00 to 99.99, 100.0 (s)

 

0.00

 

 

A075

PV scale conversion

0.01 to 99.99

 

1.00

 

 

 

 

00 (input via OI), 01 (input via O), 02 (external communication), 03 (pulse-string

 

 

 

 

PID

A076

PV source setting

 

00

 

 

frequency input), 10 (operation result output)

 

 

 

 

 

 

 

 

 

 

 

A077

Output of inverted PID deviation

00(OFF), 01 (ON)

 

00

 

 

 

A078

PID variation range

0.0 to 100.0 (%)

 

0.00

 

 

 

A079

PID feed forward selection

00 (disabled), 01 (O input), 02 (OI input), 03 (O2 input)

 

00

 

 

1 - 5

Image 9
Contents SJ700-2 Series NTS204X Table of contents Appendix Investigation of the inverter Specification labelModel name,Manufacturing numberMFGPrecautions for Data Setting Function Mode Extended Function Mode PID FEF FUF AVR Electronic thermal characteristic, 2nd B034 Free-setting V/f frequency To 400. Hz FEF FUF FEF FUF FF FEF FUF Term inal C111 FEF FUF FEF FUF RPM Specification FEF FUF FEF FUF Code display system and key operations Page Corresponding to the function code. Data display *1*2 STR key after changing the data Example of operation in full display mode b037 =Pressing the STR key Inverter trip contents,remedy,advise TroubleshootingCPU GA.COM Adjust OFF Option boards error codesInput mode specified by switch settings Setting of MAC ID DIP switches No to No Error code is output when the relevant program runs Trip conditions monitoring 305 A004/A204/A304 A202/A220/A320 *2 006 Initialization setting Page Monitor Modes Debug ModeFunction Modes Setting procedure Inverter SettingHFF/-HFUF/-HFEF Confirming the completion of initializationVDC Control signalPage Cleaning Daily inspectionPeriodic inspection Daily and Periodic Inspections Ground Resistance Test with a Megger Method of Checking the Inverter and Converter Circuits Replacing Parts Page Page Inverter Replacement Control board SJ700-055-110LF**2 Circuit Diagram Ground Terminal With Jumper SJ700-150LF**2 185LF**2 Circuit DiagramSJ700-220LF**2 Circuit Diagram SJ700-300LF**2 Circuit Diagram SJ700-370LF**2 Circuit Diagram Driver Board SJ700-450LF**2 Circuit DiagramSJ700-550LF**2 Circuit Diagram SJ700-055-110HF**2 Circuit Diagram SJ700-150HF**2 Circuit Diagram SJ700-185HF**2 220HF**2 Circuit Diagram SJ700-300HF**2 Circuit DiagramSJ700-370HF**2 Circuit Diagram TMC CN1 Page Page Page Page Page Page Page Page Page Page Page