Outback Power Systems GS8048 manual Generator, Transfer

Page 20

Operation

Generator

A generator should be sized to provide enough power for all inverters, both for loads and for battery charging.

It is usually recommended that the generator be sized at twice the wattage of the inverter system. Many generators may not be able to maintain AC voltage or frequency for long periods of time if they are loaded more than 80% of rated capacity.

The generator is required to have a stable output before its power is accepted by the inverter. Some generators with less stable or uneven outputs may not be accepted. The use of the Generator input mode may assist with this problem.

Transfer

The inverter uses a transfer relay to alternate between the states of inverting and of accepting an AC source. Until the relay energizes, the L1 and L2 output terminals are electrically isolated from the input that is in use. When it closes, the L1 input and output terminals become electrically common. The same is true for the L2 input and output terminals. (The terminals for the unused input remain isolated during this time.) When the relay changes states, the physical transfer delay is approximately 12 milliseconds (with the exception of the UPS input mode).

The relay contacts are limited to 55 amps per phase or leg. The continuous loads on that output should never exceed this number. When connected to an AC source, the Radian inverter cannot limit the load current. An overload condition is possible.

CAUTION: Equipment Damage

Current draw in excess of the inverter’s transfer relay rating can damage the transfer relay. This damage is not covered by warranty.

The inverter does not filter or clean up the power from the AC source. The voltage and power quality received by the output loads is the same as that of the source. If the voltage or quality do not meet the inverter’s input requirements (see page 17), it will disconnect and return to the inverting mode.

If the AC source meets the inverter’s requirements but is irregular, any fluctuations will be transferred to the loads. If the loads are sensitive, it may be necessary to improve the quality of the AC source.

To ensure a smoother transition, it may be advisable to raise the inverter’s lower acceptance limit. The default setting is 108 Vac on each leg. A higher setting will cause the inverter to transfer sooner in the event of a quality problem.

The Generator input mode is intended to accept irregular or unfiltered AC sources and is more likely to do so than other modes. Since it will transfer the irregular power to the output as noted above, this should be considered before using this mode with sensitive loads. (See page 9.)

In a stacked system, slaves are ordered to transfer at the same time as the master. If a slave does not sense an AC source at the same time as the master, it will continue inverting, and will experience a Phase Loss error (see page 39). This appears as an Event on the MATE3 system display, as described in the MATE3 Owner’s Manual.

18

900-0020-01-00 Rev A

Image 20
Contents Radian Series Inverter/Charger GS8048Trademarks Symbols Used AudienceDefinitions Terms and DefinitionsGeneral Safety Important Safety InstructionsTable of Contents List of Figures Table of ContentsList of Tables Introduction MATE3 System Display and Controller Pre-startup Procedures CommissioningFunctional Test StartupPowering Down Firmware UpdatesAdding New Devices CommissioningGenerator OperationInput Modes Support OperationGrid Tied UPS Uninterruptible Power Supply Backup Mini GridOperation Functions InvertingSearch InputAC Current Settings AC Source AcceptanceTransfer Offset Battery Charging Charging StepsNo Charging Bulk StageOffset Charging Stages Over Time1Float Timer SilentFloat Stage Repeated SilentNew Absorption Stage Absorption TimerNew Charging Cycle Battery Temperature Compensation EqualizationExamples Multiple-Inverter Installations Stacking OutBack HUB4 and MATE3Example of Parallel Stacking Arrangement Three Inverters Power Save Levels Auxiliary Terminals Operation Operation High Battery Transfer System Display-Based FunctionsAdvanced Generator Start AGS Grid Use TimeTroubleshooting Symptom Possible Cause Possible Remedy TroubleshootingBasic Troubleshooting Symptom Possible Cause Possible Remedy TroubleshootingTroubleshooting Hot or neutral Not be bonded Inverter may be behaving correctly Inverter output is being fed Troubleshooting Error Messages Error Troubleshooting Message Causes Possible RemedyMessage Definition Possible Remedy AC Freq Too HighCapacitors Disconnect Messages Voltage MaximumSell Status Definition Sell StatusSell Status Messages Troubleshooting Specifications Specifications for Model GS8048Electrical Specifications for Model GS8048 Value Mechanical Specifications for Model GS8048Environmental Specifications Regulatory SpecificationsSpecifications Environmental Specifications for All Models ValueFirmware Revision Default Settings and RangesGS8048 Inverter Settings Field Default Minimum Maximum OutBack Power Technologies Product RegistrationExtended Warranty Product RegistrationWarranty Year Limited Warranty for Radian ProductsHow to Arrange for Warranty Service TroubleshootingReturn Material Authorization RMA WarrantyOut of Warranty Returning Product to OutBackThis page Intentionally Left Blank Year Warranty IndexIndex Input Modes 11, 17, 20, 22This page Intentionally Left Blank