Specifications
Environmental Specifications
Table 9 Environmental Specifications for All Models
Specification | Value |
Rated Temperature Range (meets all specifications) | 32°F to 122°F |
| (0°C to 50°C) |
Operational Temperature Range (functions, but does not necessarily meet all specifications) | |
| |
Storage Temperature Range | |
| |
Regulatory Specifications |
|
Canadian Electrical Code, Part I (CSA C22.2 No.
UL 1741, 2nd Edition, Revised January 28, 2010, Static Inverter and Charge Controllers for Use in Photovoltaic Power Systems
Inverters intended for
The OutBack
The output of the Radian series exceeds the minimum power factor of 0.85 with a typical power factor of 0.96 or better.
The individual harmonics do not exceed the limits specified in Table 3 of IEEE 1547 Section 4.3.3. The THD of the root mean square (RMS) current is less than 5%.
The Radian inverters cease to export power to the simulated utility source under islanding conditions specified in IEEE 1547 Section 4.4.1.
The Radian inverters also cease to export power to the simulated utility source after the output voltage or frequency of the simulated utility source are adjusted to each of the conditions specified in IEEE 1547 Section 4.2.3 Table 1 and Section 4.2.4 Table 2 within the times specified in those tables. All Radian inverters manufactured for use in the United States and Canada are tested to comply with the table below.
Table 10 Radian Series Interconnection Response Times to
Abnormal Voltages or Frequencies (per leg)
Voltage Range | Frequency | Seconds | Cycles |
(AC Volts) | (Hz) | Allowed | Allowed |
V < 60.0 | 60.0 | 0.16 | 9.6 |
60.0 < V < 105.6 | 60.0 | 2.0 | 120.0 |
105.6 < V < 132.0 | 60.0 | no cessation | no cessation |
132.0 < V < 144.0 | 60.0 | 1.0 | 60.0 |
V > 144.0 | 60.0 | 0.16 | 9.6 |
120.0 | < 59.3 | 0.16 | 9.6 |
120.0 | > 60.5 | 0.16 | 9.6 |