Troubleshooting
Warning Messages
A Warning message is caused by a
NOTE: The Radian series has no external indicators and requires the MATE3 system display to identify a Warning.
Some warnings can become errors if left unattended. Frequency and voltage warnings are meant to warn of a problematic AC source. Often the inverter will disconnect from the source. This will occur if the condition lasts longer than the inverter’s transfer delay settings. If the inverter disconnects, the warning will display as long as the source is present, accompanied by a Disconnect message. (See next page.)
Warning screens can only display warnings; they cannot clear them. The way to correct the fault may be obvious from the message.
Table 4 Warning Troubleshooting
Message | Definition | Possible Remedy |
|
|
|
AC Freq Too High | The AC source is above the upper acceptable | Check the AC source. If it is a generator, reduce |
| frequency limit (66 Hz) and prevents | its speed. |
| connection. |
|
|
|
|
AC Freq Too Low | The AC source is below the lower acceptable | Check the AC source. If it is a generator, increase |
| frequency limit (54 Hz) and prevents | its speed. |
| connection. |
|
|
|
|
Voltage Too High | The AC source is above the upper acceptable | Check the AC source. The inverter’s acceptance |
| voltage limit on either L1 or L2 (132 Vac | range is adjustable. |
| default setting) and prevents connection. | NOTE: Adjusting the range may accommodate a |
|
| |
|
| problematic AC source, but it will not fix it. |
|
|
|
Voltage Too Low | The AC source is below the lower acceptable | Check the AC source. Check the AC wiring. The |
| voltage limit on either L1 or L2 (108 Vac | inverter’s acceptance range is adjustable. |
| default setting) and prevents connection. | NOTE: Adjusting the range may accommodate a |
|
| |
|
| problematic AC source, but it will not fix it. |
|
|
|
Input Amps > Max | AC loads are drawing more current from the | Check the loads. Oversized loads can open circuit |
| AC source than allowed by the input setting. | breakers. If they exceed the inverter’s transfer |
|
| relay size, the relay can be damaged. |
|
| This issue is usually the result of a |
|
| load, as opposed to a wiring problem. |
|
|
|
Temp Sensor Bad | An internal inverter temperature sensor may | In the MATE3, the three readings are labeled |
| be malfunctioning. One of the three internal | Transformer, Output FETs, and Capacitors. |
| sensor meters may give an unusual reading. | These values are given in degrees Celsius. See |
|
| next page. |
|
|
|
Comm Fault | The inverter has suffered an internal | Unit still functions, but may require repair. |
| communication failure. | Contact OutBack Technical Support (see inside |
|
| front cover of this manual). |
|
|
|
40 |