Troubleshooting
| Table 2 | Troubleshooting |
Symptom | Possible Cause | Possible Remedy |
|
|
|
Reduced power sold | AC source voltage is driven high | When the inverter senses a rise in grid voltage while selling, it |
to the utility grid. | when the inverter sells large | reduces the sell current, to avoid forcing the voltage to |
| amounts of power. | unacceptable levels. Check AC input voltage while selling. The |
|
| inverter may be behaving correctly. |
|
|
|
| Erratic AC source voltage. | Check AC voltage on the inverter’s input test points. (See page |
|
| 33.) If not consistent, the problem is external. |
|
| MATE3 system display only: AC source voltage may have dipped or |
|
| hovered at a low enough point to crash a sensitive load before |
|
| the inverter could take over. This can happen if the inverter’s Grid |
|
| AC Input Voltage Limits or Gen AC Input Voltage Limits were |
|
| turned down to accommodate a problematic AC source. To make |
|
| the inverter respond sooner, raise the lower limit setting in the |
|
| appropriate menu. (If this setting was intentional, then no action |
|
| is required.) |
|
|
|
| Inverter set to Search (Search | The unit will take a moment to come out of Search mode after |
| mode). | transferring. |
Loads drop out or |
| MATE3 system display only: If constant power is required, set to |
crash during |
| |
| ON with the INVERTER hot key. (If this setting was intentional, | |
transfer. |
| |
| then no action is required.) | |
|
| |
|
|
|
| Loads sensitive to inverter’s | MATE3 system display only: Most of the inverter’s input modes |
| transfer time. UPS mode not in | feature an approximately 12 ms transfer time. Certain loads (such |
| use on the appropriate input. | as highly sensitive computers) may not respond well. The UPS |
|
| input mode has a transfer time of less than 4 ms. Select this mode |
|
| for the appropriate input. (See page 12.) |
|
|
|
| Loads too large. | The unit can transfer more power than it can invert. If loads are |
|
| oversized, the unit will falter or crash when switching to batteries. |
|
| Reduce the size of the loads. |
|
|
|
| Undersized battery cables. | Battery cables smaller than recommended will cause a significant |
|
| voltage drop when switching to batteries, acting like either an |
|
| overload or a |
|
|
|
Unit reads AC input, | Internal transfer relay may be | Disconnect AC input wires and turn inverter on. Test the AC input |
even though no | damaged. | and neutral test points with an AC voltmeter. (See page 33.) If |
source is present. |
| voltage appears there, the transfer relay may be jammed. Contact |
|
| OutBack Technical Support (see inside front cover of this manual). |
|
| This problem is not common. If this occurs, it will likely occur on |
|
| only the Grid or Gen input — not both. |
|
|
|
| Inverter’s output has been | Disconnect the wires from the inverter’s AC input or AC output |
| connected to its input. Voltage | terminals, or both. If the problem immediately disappears, it is an |
| shifts are the result of trying to | external wiring issue. The inverter’s AC HOT IN and AC HOT OUT |
Inverter clicks | match its own voltage. | must remain isolated from each other. |
|
| |
repeatedly. AC | Low AC input voltage. Can be | Test AC hot and neutral input test points with an AC voltmeter. |
output voltage rises | caused by weak AC source, or | (See page 33.) If low or fluctuating, this is an external problem. |
or drops to unusual | by faulty input connection. |
|
levels with every |
|
|
|
| |
click. | A generator is connected to the | The inverter is not intended to sell power to a generator. The |
| input terminals while the unit is | selling activity will drive the generator voltage up to the |
| in the Grid Tied input mode. | disconnection point. It will then reconnect to the generator and |
|
| try again. Change input modes, or move the generator to an |
|
| input with a different mode selected. |
|
|
|
36 |