Page 24

Operation

This setting is typically lower than the Float voltage setting. Although the batteries are not discharged, they are maintained at a somewhat lower voltage so that the maximum amount of power can be exported. It is recommended that this item be set at the batteries’ natural rest voltage.

In the Grid Tied input mode, excess power is sent first to any loads on the inverter’s output, using the Offset function (see page 19). If the exported power exceeds the load requirements, the excess is sold back to the utility grid, using the inverter’s AC input terminals. The unit will maintain this activity for as long as excess power is available. See page 11 for more notes on the Grid Tied input mode.

Regardless of the input mode setting, if no renewable energy is present, the inverter will exit (or skip) this step and enter Silent.

Silent

This is not a charging stage, but a quiescent period between stages. The inverter remains on the AC source, but the charger is inactive. It enters this condition upon completing the Absorption stage and concluding (or skipping) Offset operation.

In Silent, the batteries are not in significant use by the inverter, but they are also not being charged. The battery voltage will naturally decrease when not maintained by another means such as a renewable source.

The term “Silent” is also used in the context of stacking inverters and Power Save levels. See page 28.

Target point: Re-Float Voltage setting. When the battery voltage decreases to this point, the charger becomes active again. The default set point is 50.0 Vdc.

NOTE: If the Radian inverter is placed in the Generator input mode, the charger skips Silent and proceeds directly to Float stage (see Figure 4 on page 21). It will remain in Float until AC power is disconnected, which usually means that the generator was stopped manually or automatically.

See page 9 for more information on this mode.

Float Stage

This is the third stage of charging. It is a constant-voltage stage. Current varies as needed to maintain the voltage, but typically drops to a low number. This stage offsets the batteries’ tendency to self-discharge (as well as offsetting the draw of any other DC loads), and maintains them at 100% of capacity.

Target point: Float Voltage setting. The default set point is 54.4 Vdc.

Time limit: Float Time setting.

NOTE: The remaining stages below do not apply in the Generator input mode. The next activity that can occur is a new charging cycle. The criteria for beginning a new cycle are described on page 23.

Float Timer

This is part of Float stage and is not a separate stage of charging. On the charts on page 21, it is marked as a separate step to note that the timer only begins running upon reaching the Float set point. It does not begin running at the beginning of Float stage. (The Float timer is reset to its maximum amount whenever the batteries drop to the Re-Float voltage.)

Repeated Silent

The unit re-enters the Silent stage as it did previously. The unit remains on the AC source, but the charger is inactive.

Target point: Re-Float Voltage setting. The default set point is 50.0 Vdc.

22

900-0020-01-00 Rev A

Image 24
Contents Radian Series Inverter/Charger GS8048Trademarks Symbols Used AudienceDefinitions Terms and DefinitionsGeneral Safety Important Safety InstructionsTable of Contents Table of Contents List of TablesList of Figures Introduction MATE3 System Display and Controller Pre-startup Procedures CommissioningFunctional Test StartupPowering Down Firmware UpdatesAdding New Devices CommissioningOperation Input ModesGenerator Support OperationGrid Tied UPS Uninterruptible Power Supply Backup Mini GridOperation Functions InvertingSearch InputAC Current Settings AC Source AcceptanceTransfer Offset Battery Charging Charging StepsNo Charging Bulk StageOffset Charging Stages Over Time1Float Timer SilentFloat Stage Repeated SilentAbsorption Timer New Charging CycleNew Absorption Stage Battery Temperature Compensation EqualizationExamples Multiple-Inverter Installations Stacking OutBack HUB4 and MATE3Example of Parallel Stacking Arrangement Three Inverters Power Save Levels Auxiliary Terminals Operation Operation High Battery Transfer System Display-Based FunctionsAdvanced Generator Start AGS Grid Use TimeTroubleshooting Basic TroubleshootingTroubleshooting Symptom Possible Cause Possible Remedy Troubleshooting TroubleshootingSymptom Possible Cause Possible Remedy Hot or neutral Not be bonded Inverter may be behaving correctly Inverter output is being fed Troubleshooting Error Messages Error Troubleshooting Message Causes Possible RemedyMessage Definition Possible Remedy AC Freq Too HighCapacitors Disconnect Messages Voltage MaximumSell Status Sell Status MessagesSell Status Definition Troubleshooting Specifications Specifications for Model GS8048Electrical Specifications for Model GS8048 Value Mechanical Specifications for Model GS8048Environmental Specifications Regulatory SpecificationsSpecifications Environmental Specifications for All Models ValueDefault Settings and Ranges GS8048 Inverter SettingsFirmware Revision Field Default Minimum Maximum OutBack Power Technologies Product RegistrationExtended Warranty Product RegistrationWarranty Year Limited Warranty for Radian ProductsHow to Arrange for Warranty Service TroubleshootingReturn Material Authorization RMA WarrantyOut of Warranty Returning Product to OutBackThis page Intentionally Left Blank Year Warranty IndexIndex Input Modes 11, 17, 20, 22This page Intentionally Left Blank