Operation

Gen Alert is used as a controller for an AC generator with a remote start feature, although it has limited functionality. (The generator recharges batteries using the inverter’s battery charger.) When the battery voltage falls to a low set point for a settable delay, the AUX output is activated. The AUX output is used to energize a relay. The relay contacts then activate the remote start/stop circuit on the generator. This is illustrated in the Radian Series Inverter/Charger Installation Manual.) The AUX output will be deactivated once the battery voltage rises to a high voltage setting for a settable delay period.

Parameters include:

Low and high DC voltage

On and off delay

Gen Alert control logic is located in the inverter. It has the advantage of functioning when the system display is removed. However, it may not completely charge the batteries and does not have all the advantages of the Advanced Generator Start (AGS) feature that is found in the system display. For many users, the AGS feature may prove more useful than Gen Alert. Gen Alert, however, could be used as a literal “Generator Alert”, a signal to the user to manually start a generator.

Fault enables the AUX output when the inverter shuts down due to an error condition (see page 39). It can activate a light or alarm to show that the inverter has failed. With the appropriate devices, it could send an alarm signal through a radio, pager, or telephone dialer.

This function does not have settable parameters.

This function is not triggered by the Phase Loss error, as that error does not shut down the inverter.

Vent Fan enables the AUX output in response to a high DC (battery) voltage set point. It can run a small fan to ventilate the battery compartment to eliminate gases that result from battery charging. When the voltage falls below this set point for a settable delay period, the AUX output turns off.

Parameters include:

High DC voltage

Off delay

Cool Fan enables the AUX output when the inverter reaches a high internal temperature. It is intended to trigger a small external fan for additional cooling. See the Warning Troubleshooting table on page 40 for a description of the fan criteria.

This function does not have settable parameters.

DC Divert enables the AUX output to divert excess renewable energy to a DC load, such as a resistor, a heater, or a fuel cell. When battery voltage rises above a settable high voltage level, the AUX output is activated after a settable delay. The AUX output controls a larger relay, which allows current to flow from the batteries to a dedicated DC load when energized. (This is illustrated in the Radian Series Inverter/Charger Installation Manual.) Diversion is activated by high DC voltage and is usually used to regulate battery charging. The resistor must be sized to dissipate all of the energy from the renewable source if necessary. Diversion will turn off following a delay when a low DC voltage setting is reached.

Parameters include:

Low and high DC voltage

On and off delay

IEEE enables the AUX function as an alert that the utility grid does not meet IEEE parameters for the grid-interactive function (see page 46). It can activate a light or alarm to show that the grid-interactive function has shut down and that there may be problems with the grid. The AUX output will cycle on and off if IEEE parameters are met and the IEEE timer is counting down.

This function does not have settable parameters.

30

900-0020-01-00 Rev A

Image 32
Contents Radian Series Inverter/Charger GS8048Trademarks Symbols Used AudienceDefinitions Terms and DefinitionsGeneral Safety Important Safety InstructionsTable of Contents List of Figures Table of ContentsList of Tables Introduction MATE3 System Display and Controller Pre-startup Procedures CommissioningFunctional Test StartupPowering Down Firmware UpdatesAdding New Devices CommissioningGenerator OperationInput Modes Support OperationGrid Tied UPS Uninterruptible Power Supply Backup Mini GridOperation Functions InvertingSearch InputAC Current Settings AC Source AcceptanceTransfer Offset Battery Charging Charging StepsNo Charging Bulk StageOffset Charging Stages Over Time1Float Timer SilentFloat Stage Repeated SilentNew Absorption Stage Absorption TimerNew Charging Cycle Battery Temperature Compensation EqualizationExamples Multiple-Inverter Installations Stacking OutBack HUB4 and MATE3 Example of Parallel Stacking Arrangement Three Inverters Power Save Levels Auxiliary Terminals Operation Operation High Battery Transfer System Display-Based FunctionsAdvanced Generator Start AGS Grid Use TimeTroubleshooting Symptom Possible Cause Possible Remedy TroubleshootingBasic Troubleshooting Symptom Possible Cause Possible Remedy TroubleshootingTroubleshooting Hot or neutral Not be bonded Inverter may be behaving correctly Inverter output is being fed Troubleshooting Error Messages Error Troubleshooting Message Causes Possible RemedyMessage Definition Possible Remedy AC Freq Too HighCapacitors Disconnect Messages Voltage MaximumSell Status Definition Sell StatusSell Status Messages Troubleshooting Specifications Specifications for Model GS8048Electrical Specifications for Model GS8048 Value Mechanical Specifications for Model GS8048Environmental Specifications Regulatory SpecificationsSpecifications Environmental Specifications for All Models ValueFirmware Revision Default Settings and RangesGS8048 Inverter Settings Field Default Minimum Maximum OutBack Power Technologies Product RegistrationExtended Warranty Product RegistrationWarranty Year Limited Warranty for Radian ProductsHow to Arrange for Warranty Service TroubleshootingReturn Material Authorization RMA WarrantyOut of Warranty Returning Product to OutBackThis page Intentionally Left Blank Year Warranty IndexIndex Input Modes 11, 17, 20, 22This page Intentionally Left Blank