Outback Power Systems GS8048 manual Field Default Minimum Maximum

Page 50

Specifications

Table 11 GS8048 Inverter Settings

Field

Item

Default

Minimum

Maximum

 

Aux Control

Off

 

Off, Auto or On

 

Aux Mode

Vent Fan

Load Shed, Gen Alert, Fault, Vent Fan, Cool Fan,

 

DC Divert, IEEE, Source Status, AC Divert

 

 

 

 

(Load Shed) ON: Batt >

56 Vdc

40 Vdc

 

72 Vdc

 

(Load Shed ON) Delay

30 Secs

6 Secs

 

1500 Secs

 

(Load Shed) OFF: Batt <

56 Vdc

48 Vdc

 

72 Vdc

 

(Load Shed OFF) Delay

18 Secs

6 Secs

 

1500 Secs

 

(Gen Alert) ON: Batt <

44 Vdc

40 Vdc

 

56 Vdc

 

(Gen Alert ON) Delay

30 Secs

6 Secs

 

1500 Secs

 

(Gen Alert) OFF: Batt >

56 Vdc

48 Vdc

 

72 Vdc

Auxiliary Output

(Gen Alert OFF) Delay

30 Secs

6 Secs

 

1500 Secs

 

(Vent Fan) ON: Batt >

56 Vdc

48 Vdc

 

72 Vdc

 

(Vent Fan) Off Delay

18 Secs

6 Secs

 

1500 Secs

 

(DC Divert) ON: Batt >

56 Vdc

48 Vdc

 

72 Vdc

 

(DC Divert ON) Delay

30 Secs

6 Secs

 

1500 Secs

 

(DC Divert) OFF: Batt <

44 Vdc

40 Vdc

 

56 Vdc

 

(DC Divert OFF) Delay

30 Secs

6 Secs

 

1500 Secs

 

(AC Divert) ON: Batt >

56 Vdc

48 Vdc

 

72 Vdc

 

(AC Divert ON) Delay

30 Secs

6 Secs

 

1500 Secs

 

(AC Divert) OFF: Batt <

44 Vdc

40 vdc

 

56 Vdc

 

(AC Divert OFF) Delay

30 Secs

6 Secs

 

1500 Secs

 

Aux Control

Off

 

Off, Auto or On

 

Aux Mode

Gen Alert

Load Shed, Gen Alert, Fault, Vent Fan, Cool Fan,

 

DC Divert, IEEE, Source Status, AC Divert

 

 

 

 

(Load Shed) ON: Batt >

56 Vdc

40 Vdc

 

72 Vdc

 

(Load Shed ON) Delay

30 Secs

6 Secs

 

1500 Secs

 

(Load Shed) OFF: Batt <

56 Vdc

48 Vdc

 

72 Vdc

 

(Load Shed OFF) Delay

18 Secs

6 Secs

 

1500 Secs

 

(Gen Alert) ON: Batt <

44 Vdc

40 Vdc

 

56 Vdc

 

(Gen Alert ON) Delay

30 Secs

6 Secs

 

1500 Secs

Auxiliary

(Gen Alert) OFF: Batt >

56 Vdc

48 Vdc

 

72 Vdc

(Gen Alert OFF) Delay

30 Secs

6 Secs

 

1500 Secs

Relay

 

(Vent Fan) ON: Batt >

56 Vdc

48 Vdc

 

72 Vdc

 

 

 

(Vent Fan) Off Delay

18 Secs

6 Secs

 

1500 Secs

 

(DC Divert) ON: Batt >

56 Vdc

48 Vdc

 

72 Vdc

 

(DC Divert ON) Delay

30 Secs

6 Secs

 

1500 Secs

 

(DC Divert) OFF: Batt <

44 Vdc

40 Vdc

 

56 Vdc

 

(DC Divert OFF) Delay

30 Secs

6 Secs

 

1500 Secs

 

(AC Divert) ON: Batt >

56 Vdc

48 Vdc

 

72 Vdc

 

(AC Divert ON) Delay

30 Secs

6 Secs

 

1500 Secs

 

(AC Divert) OFF: Batt <

44 Vdc

40 vdc

 

56 Vdc

 

(AC Divert OFF) Delay

30 Secs

6 Secs

 

1500 Secs

Inverter Stacking

Stack Mode

Master

 

Master, Slave

 

 

 

 

 

 

Power Save

Master Power Save Level

0

0

 

31

(in Stacking Menu)

Slave Power Save Level

1

1

 

31

 

Grid-Tie Enable

Y

 

Y or N

Grid-Tie Sell

Sell Voltage

52 Vdc

40 Vdc

 

60 Vdc

 

Grid-Tie Window

IEEE

 

IEEE or user

 

Input Voltage

0

-7

 

7

Calibrate

Output Voltage

0

-7

 

7

 

Battery Voltage

0

-0.8

 

0.8

48

900-0020-01-00 Rev A

Image 50
Contents Radian Series Inverter/Charger GS8048Trademarks Definitions Symbols UsedAudience Terms and DefinitionsGeneral Safety Important Safety InstructionsTable of Contents List of Figures Table of ContentsList of Tables Introduction MATE3 System Display and Controller Functional Test Pre-startup ProceduresCommissioning StartupAdding New Devices Powering DownFirmware Updates CommissioningGenerator OperationInput Modes Support OperationGrid Tied UPS Uninterruptible Power Supply Backup Mini GridOperation Functions InvertingSearch InputAC Current Settings AC Source AcceptanceTransfer Offset No Charging Battery ChargingCharging Steps Bulk StageOffset Charging Stages Over Time1Float Stage Float TimerSilent Repeated SilentNew Absorption Stage Absorption TimerNew Charging Cycle Battery Temperature Compensation EqualizationExamples Multiple-Inverter Installations Stacking OutBack HUB4 and MATE3Example of Parallel Stacking Arrangement Three Inverters Power Save Levels Auxiliary Terminals Operation Operation Advanced Generator Start AGS High Battery TransferSystem Display-Based Functions Grid Use TimeTroubleshooting Symptom Possible Cause Possible Remedy TroubleshootingBasic Troubleshooting Symptom Possible Cause Possible Remedy TroubleshootingTroubleshooting Hot or neutral Not be bonded Inverter may be behaving correctly Inverter output is being fed Troubleshooting Error Messages Error Troubleshooting Message Causes Possible RemedyMessage Definition Possible Remedy AC Freq Too HighCapacitors Disconnect Messages Voltage MaximumSell Status Definition Sell StatusSell Status Messages Troubleshooting Electrical Specifications for Model GS8048 Value SpecificationsSpecifications for Model GS8048 Mechanical Specifications for Model GS8048Specifications Environmental SpecificationsRegulatory Specifications Environmental Specifications for All Models ValueFirmware Revision Default Settings and RangesGS8048 Inverter Settings Field Default Minimum Maximum OutBack Power Technologies Product RegistrationExtended Warranty Product RegistrationWarranty Year Limited Warranty for Radian ProductsReturn Material Authorization RMA How to Arrange for Warranty ServiceTroubleshooting WarrantyOut of Warranty Returning Product to OutBackThis page Intentionally Left Blank Year Warranty IndexIndex Input Modes 11, 17, 20, 22This page Intentionally Left Blank