Outback Power Systems Effective Use of AUX Terminals in GS8048 Inverter Operations

Page 31

Operation

Auxiliary Terminals

The Radian inverter has two sets of terminals which can respond to different criteria and control many functions. The 12V AUX terminals provide a 12 Vdc output that can deliver up to 0.7 Adc to control external loads. The RELAY AUX terminals are “dry” relay contacts with no voltage. Each set of terminals has its own set of programmed criteria. Each has identical options available. (When the options described below refer generically to the “AUX output”, it can mean either set of terminals.)

Each AUX output has three states available: continuous Off, continuous On, and Auto, which allows that output to be activated using the automatic auxiliary functions. (All functions on both sets of terminals are defaulted to Off.) These functions are based in the Radian inverter and accessed using the MATE3. The MATE3 and other devices also have programming, such as AGS, that can control the AUX outputs. To avoid conflicts, the output should be turned Off when the AGS function is active. (See page 32.)

For the Radian automatic functions, typical applications include signaling a generator to start, sending a fault alarm signal, or running a small fan to ventilate the batteries. See the Radian Series Inverter/Charger Installation Manual for more information on hooking up each set of terminals. See the MATE3 Owner’s Manual for instructions on programming each function.

The AUX terminals have a series of set points which are used by various functions. Both sets of terminals have the same options available, but they are programmed independently. Not all set points are used by all functions. Each AUX mode description below will detail the set points that are used for that mode.

Low DC voltage settings

High DC voltage settings

On delay settings, in increments of 0.1 minutes

Off delay settings, in increments of 0.1 minutes

There are nine functions, each geared toward a different application. The first item on this list may not be the default function displayed in either menu.

Load Shed can perform load management. When battery voltage rises above a settable high voltage level, the AUX output is activated after a settable delay. The AUX output is used to energize a relay, which is connected to non-vital loads. The AUX output will be deactivated once the battery voltage falls below a low voltage setting for a settable delay period.

Load Shed will turn off when the inverter enters a high-temperature condition or when the AC output voltage drops below 105 Vac for more than three seconds. It will also turn off if the input current exceeds the Input AC Limit setting while the inverter is using an AC source.

Parameters include:

Low and high DC voltage

On and off delay

900-0020-01-00 Rev A

29

Image 31
Contents GS8048 Radian Series Inverter/ChargerTrademarks Terms and Definitions Symbols UsedAudience DefinitionsImportant Safety Instructions General SafetyTable of Contents List of Tables Table of ContentsList of Figures Introduction MATE3 System Display and Controller Startup Pre-startup ProceduresCommissioning Functional TestCommissioning Powering DownFirmware Updates Adding New DevicesInput Modes OperationGenerator Operation SupportGrid Tied UPS Uninterruptible Power Supply Mini Grid BackupOperation Inverting FunctionsInput SearchAC Source Acceptance AC Current SettingsTransfer Offset Bulk Stage Battery ChargingCharging Steps No ChargingCharging Stages Over Time1 OffsetRepeated Silent Float TimerSilent Float StageNew Charging Cycle Absorption TimerNew Absorption Stage Equalization Battery Temperature CompensationExamples OutBack HUB4 and MATE3 Multiple-Inverter Installations StackingExample of Parallel Stacking Arrangement Three Inverters Power Save Levels Auxiliary Terminals Operation Operation Grid Use Time High Battery TransferSystem Display-Based Functions Advanced Generator Start AGSBasic Troubleshooting TroubleshootingTroubleshooting Symptom Possible Cause Possible Remedy Troubleshooting TroubleshootingSymptom Possible Cause Possible Remedy Hot or neutral Not be bonded Inverter may be behaving correctly Inverter output is being fed Troubleshooting Error Troubleshooting Message Causes Possible Remedy Error MessagesAC Freq Too High Message Definition Possible RemedyCapacitors Voltage Maximum Disconnect MessagesSell Status Messages Sell StatusSell Status Definition Troubleshooting Mechanical Specifications for Model GS8048 SpecificationsSpecifications for Model GS8048 Electrical Specifications for Model GS8048 ValueEnvironmental Specifications for All Models Value Environmental SpecificationsRegulatory Specifications SpecificationsGS8048 Inverter Settings Default Settings and RangesFirmware Revision Field Default Minimum Maximum Product Registration OutBack Power TechnologiesProduct Registration Extended WarrantyYear Limited Warranty for Radian Products WarrantyWarranty How to Arrange for Warranty ServiceTroubleshooting Return Material Authorization RMAReturning Product to OutBack Out of WarrantyThis page Intentionally Left Blank Index Year WarrantyInput Modes 11, 17, 20, 22 IndexThis page Intentionally Left Blank