Outback Power Systems GS8048 manual Disconnect Messages, Voltage Maximum

Page 44

Troubleshooting

Disconnect Messages

Disconnect messages explain the reason that the inverter rejected an AC source. The unit returns to inverting mode if turned on. This screen is viewed using the AC INPUT hot key on the MATE3. (See

the MATE3 manual for more instructions.) One or more messages will display Y (yes). If a message says N (no), it is not the cause of the disconnect. The MATE3 system display may generate a concurrent Event and Warning message following the disconnect. (See previous page.) If the AC source is removed, the Warning will be blank, but the cause of the last disconnect will remain.

Disconnect messages only display the reason for the disconnection; they cannot correct it. It is usually the result of external conditions, not an inverter fault. If the condition is corrected, the inverter will reconnect. A few settings can be changed to accommodate problems with the AC source.

The reasons shown in the Sell Status menu for ceasing to sell power (see next page) are not the same as disconnect messages, although they may be caused by the same circumstance. A grid-interactive unit can stop selling and still remain connected to the utility grid.

Table 5 Disconnect Troubleshooting

Message

Definition

Possible Remedy

 

 

 

Frequency Too High

The AC source has exceeded

Check AC source. If it is a generator, reduce speed.

 

66 Hz.

 

 

 

 

Frequency Too Low

The AC source has dropped below

Check AC source. If it is a generator, increase speed.

 

54 Hz.

 

 

 

 

Voltage > Maximum

The AC source has exceeded

Check AC source. The inverter’s acceptance range

 

140 Vac (default value) on either

is adjustable.

 

L1 or L2.

NOTE: Adjusting the range may accommodate a

 

 

 

 

problematic AC source, but it will not fix it.

 

 

 

Voltage < Minimum

The AC source has dropped below

Check AC source. The inverter’s acceptance range

 

108 Vac (default value) on either

is adjustable.

 

L1 or L2.

NOTE: Adjusting the range may accommodate a

 

 

 

 

problematic AC source, but it will not fix it.

 

 

 

Backfeed

Usually indicates another AC

Disconnect the AC OUT wires. Check the wires

 

power source (out of phase with

(not the inverter) with an AC voltmeter. If an AC

 

the inverter) was connected to the

source is present, shut it off. (This is more often

 

unit’s AC output.

accompanied by an AC Output Backfeed error.)

 

Can also occur if an out-of-phase

Check input source and wiring. This can be caused

 

AC source is connected to the

by a source with phase problems. It can also be

 

inverter’s AC input.

caused by transferring from one AC source to

 

 

another before the inverter can synchronize itself.

 

 

 

Phase Lock

The unit cannot remain in phase

Check AC source. This can be caused by a

 

with an erratic AC source.

generator with a poorly regulated output. Some

 

NOTE: This is not an “Error” as

generators behave this way when running out of

 

fuel. If necessary, set the Radian inverter to the

 

defined on page 39 and is not

 

Generator input mode. (See page 9.)

 

accompanied by a shutdown.

 

 

 

 

 

Island Detect

The unit detects something other

Check all input circuit breakers for an open circuit.

 

than normal grid conditions. This

This may (rarely) happen with a generator. If

 

is usually the result of an open AC

necessary, set the inverter to the Generator input

 

input circuit.

mode. (See page 9.)

 

 

 

42

900-0020-01-00 Rev A

Image 44
Contents Radian Series Inverter/Charger GS8048Trademarks Symbols Used AudienceDefinitions Terms and DefinitionsGeneral Safety Important Safety InstructionsTable of Contents List of Figures Table of ContentsList of Tables Introduction MATE3 System Display and Controller Pre-startup Procedures CommissioningFunctional Test StartupPowering Down Firmware UpdatesAdding New Devices CommissioningGenerator OperationInput Modes Support OperationGrid Tied UPS Uninterruptible Power Supply Backup Mini GridOperation Functions InvertingSearch InputAC Current Settings AC Source AcceptanceTransfer Offset Battery Charging Charging StepsNo Charging Bulk StageOffset Charging Stages Over Time1Float Timer SilentFloat Stage Repeated SilentNew Absorption Stage Absorption TimerNew Charging Cycle Battery Temperature Compensation EqualizationExamples Multiple-Inverter Installations Stacking OutBack HUB4 and MATE3Example of Parallel Stacking Arrangement Three Inverters Power Save Levels Auxiliary Terminals Operation Operation High Battery Transfer System Display-Based FunctionsAdvanced Generator Start AGS Grid Use TimeTroubleshooting Symptom Possible Cause Possible Remedy TroubleshootingBasic Troubleshooting Symptom Possible Cause Possible Remedy TroubleshootingTroubleshooting Hot or neutral Not be bonded Inverter may be behaving correctly Inverter output is being fed Troubleshooting Error Messages Error Troubleshooting Message Causes Possible RemedyMessage Definition Possible Remedy AC Freq Too HighCapacitors Disconnect Messages Voltage MaximumSell Status Definition Sell StatusSell Status Messages Troubleshooting Specifications Specifications for Model GS8048Electrical Specifications for Model GS8048 Value Mechanical Specifications for Model GS8048Environmental Specifications Regulatory SpecificationsSpecifications Environmental Specifications for All Models ValueFirmware Revision Default Settings and RangesGS8048 Inverter Settings Field Default Minimum Maximum OutBack Power Technologies Product RegistrationExtended Warranty Product RegistrationWarranty Year Limited Warranty for Radian ProductsHow to Arrange for Warranty Service TroubleshootingReturn Material Authorization RMA WarrantyOut of Warranty Returning Product to OutBackThis page Intentionally Left Blank Year Warranty IndexIndex Input Modes 11, 17, 20, 22This page Intentionally Left Blank