Outback Power Systems Essential Specifications and Firmware Information for Inverter/Chargers

Page 49

Specifications

The acceptance ranges are selected using the system display. In the MATE3, the options are IEEE

and user.

The IEEE option allows a range of 108 – 132 Vac at 59.3 – 60.5 Hz

The user option does not have a fixed voltage setting. It follows the upper and lower limit settings in the Grid AC Input Mode and Limits menu. The default is a range of 108 – 132 Vac.

Reconnection delay is 6 seconds. Sell delay is 5 minutes. These settings are not adjustable.

Firmware Revision

This manual applies to Radian series inverter/chargers with a firmware version of 001.000.xxx or higher.

Default Settings and Ranges

 

Table 11

GS8048 Inverter Settings

 

 

 

 

 

 

 

 

 

Field

Item

 

Default

Minimum

 

Maximum

INVERTER Hot Key

Inverter Mode

 

Off

On, Off, or Search

CHARGER Hot Key

Charger Control

 

On

 

On or Off

AC Input Hot Key

AC Input Mode

 

Use

 

Drop or Use

 

Sensitivity (see page 16 for increments)

10

0

 

250

Search

Pulse Length

 

8 AC cycles

4 AC cycles

 

20 AC cycles

 

Pulse Spacing

 

60 AC cycles

4 AC cycles

 

120 AC cycles

 

Input Priority

 

Grid

 

Grid or Gen

AC Input and

Grid Input AC Limit

 

50 Aac

5 Aac

 

55 Aac

Current Limit

Gen Input AC Limit

 

50 Aac

5 Aac

 

55 Aac

 

Charger AC Limit

 

30 Aac

0 Aac

 

30 Aac

 

Input Mode

 

Grid Tied

Generator, Support, Grid Tied, UPS, Backup,

 

 

 

Mini Grid

 

 

 

 

 

Grid AC Input

Voltage Limit Lower

 

108 Vac

70 Vac

 

110 Vac

Mode and Limits

(Voltage Limit)Upper

 

132 Vac

125 Vac

 

140 Vac

 

Transfer Delay

 

6 AC cycles

0 AC cycles

 

240 AC cycles

 

Connect Delay

 

0.2 minutes

0.2 minutes

 

15 minutes

 

Input Mode

 

Generator

Generator, Support, Grid Tied, UPS, Backup,

 

 

 

Mini Grid

 

 

 

 

 

Gen AC Input

Voltage Limit Lower

 

108 Vac

70 Vac

 

110 Vac

Mode and Limits

(Voltage Limit) Upper

 

140 Vac

125 Vac

 

140 Vac

 

Transfer Delay

 

6 AC cycles

0 AC cycles

 

240 AC cycles

 

Connect Delay

 

0.5 minutes

0.2 minutes

 

15 minutes

AC Output

Output Voltage

 

240 Vac

220 Vac

 

260 Vac

Low Battery

Cut-Out Voltage

 

42 Vdc

36 Vdc

 

48 Vdc

Cut-In Voltage

 

50 Vdc

40 Vdc

 

56 Vdc

 

 

 

 

Absorb Voltage

 

57.6 Vdc

52 Vdc

 

64 Vdc

 

(Absorb) Time

 

1.0 hours

0.0 hours

 

24.0 hours

Battery Charger

Float Voltage

 

54.4 Vdc

48 Vdc

 

60 Vdc

 

(Float) Time

 

1.0 hours

0.0 hours

 

24.0 hours

 

Re-Float Voltage

 

50 Vdc

48 Vdc

 

52 Vdc

Battery Equalize

Equalize Voltage

 

58.4 Vdc

56 Vdc

 

68 Vdc

(Equalize) Time

 

1.0 hours

0.0 hours

 

24.0 hours

 

 

 

900-0020-01-00 Rev A

47

Image 49
Contents GS8048 Radian Series Inverter/ChargerTrademarks Audience Symbols UsedDefinitions Terms and DefinitionsImportant Safety Instructions General SafetyTable of Contents List of Tables Table of ContentsList of Figures Introduction MATE3 System Display and Controller Commissioning Pre-startup ProceduresFunctional Test StartupFirmware Updates Powering DownAdding New Devices CommissioningInput Modes OperationGenerator Operation SupportGrid Tied UPS Uninterruptible Power Supply Mini Grid BackupOperation Inverting FunctionsInput SearchAC Source Acceptance AC Current SettingsTransfer Offset Charging Steps Battery ChargingNo Charging Bulk StageCharging Stages Over Time1 OffsetSilent Float TimerFloat Stage Repeated SilentNew Charging Cycle Absorption TimerNew Absorption Stage Equalization Battery Temperature CompensationExamples OutBack HUB4 and MATE3 Multiple-Inverter Installations StackingExample of Parallel Stacking Arrangement Three Inverters Power Save Levels Auxiliary Terminals Operation Operation System Display-Based Functions High Battery TransferAdvanced Generator Start AGS Grid Use TimeBasic Troubleshooting TroubleshootingTroubleshooting Symptom Possible Cause Possible Remedy Troubleshooting TroubleshootingSymptom Possible Cause Possible Remedy Hot or neutral Not be bonded Inverter may be behaving correctly Inverter output is being fed Troubleshooting Error Troubleshooting Message Causes Possible Remedy Error MessagesAC Freq Too High Message Definition Possible RemedyCapacitors Voltage Maximum Disconnect MessagesSell Status Messages Sell StatusSell Status Definition Troubleshooting Specifications for Model GS8048 SpecificationsElectrical Specifications for Model GS8048 Value Mechanical Specifications for Model GS8048Regulatory Specifications Environmental SpecificationsSpecifications Environmental Specifications for All Models ValueGS8048 Inverter Settings Default Settings and RangesFirmware Revision Field Default Minimum Maximum Product Registration OutBack Power TechnologiesProduct Registration Extended WarrantyYear Limited Warranty for Radian Products WarrantyTroubleshooting How to Arrange for Warranty ServiceReturn Material Authorization RMA WarrantyReturning Product to OutBack Out of WarrantyThis page Intentionally Left Blank Index Year WarrantyInput Modes 11, 17, 20, 22 IndexThis page Intentionally Left Blank