Outback Power Systems GS8048 manual Offset

Page 21

Operation

Offset

This function is designed to use excess battery energy to power the loads, even when an AC source is present. This allows the system to take advantage of renewable energy sources, in effect “offsetting” dependence on the AC source.

When a renewable source of energy raises the batteries above a designated reference point (or “target”), the inverter exports power to the loads in order to bring the voltage back down or to prevent it from rising further.

The inverter uses several set points as targets for the offset function, particularly the battery charger settings. In the MATE3, the Absorb Voltage, Float Voltage, and Equalize Voltage settings are all used as reference voltages. While the battery charger is operating, it will regulate the voltage at a level appropriate for the target setting.

If none of the battery charger’s timers are active, the target voltage used by the Radian inverter is Sell Voltage in the Grid-Tie Sell menu. Unlike the other target voltages, the Radian inverter cannot import AC power to raise the batteries to the Sell Voltage set point. It can only use excess DC power, if it is available, and export it as AC power.

(See page 21 for more information on how Offset relates to the battery charger. See the MATE3 Owner’s Manual to change any of these settings.)

NOTES:

If the Radian inverter is in the Grid Tied input mode and more renewable energy is available than can be offset by the loads, the inverter will sell the remainder to the utility grid. Although the inverter can use the Sell Voltage setting as a target in most input modes (see below), it is unable to sell power to the utility grid unless the Grid Tied mode is selected.

If the inverter is in the Support, UPS, Backup, or Mini Grid input modes and more renewable energy is available than can be offset by the loads, it means the inverter is capable of running all of its loads using renewable energy. The inverter will disconnect from the AC source as long as the excess renewable energy is present.

The Offset function is not active when the Generator input mode is selected.

900-0020-01-00 Rev A

19

Image 21
Contents GS8048 Radian Series Inverter/ChargerTrademarks Audience Symbols UsedDefinitions Terms and DefinitionsImportant Safety Instructions General SafetyTable of Contents Table of Contents List of TablesList of Figures Introduction MATE3 System Display and Controller Commissioning Pre-startup ProceduresFunctional Test StartupFirmware Updates Powering DownAdding New Devices CommissioningOperation Input ModesGenerator Operation SupportGrid Tied UPS Uninterruptible Power Supply Mini Grid BackupOperation Inverting FunctionsInput SearchAC Source Acceptance AC Current SettingsTransfer Offset Charging Steps Battery ChargingNo Charging Bulk StageCharging Stages Over Time1 OffsetSilent Float TimerFloat Stage Repeated SilentAbsorption Timer New Charging CycleNew Absorption Stage Equalization Battery Temperature CompensationExamples OutBack HUB4 and MATE3 Multiple-Inverter Installations StackingExample of Parallel Stacking Arrangement Three Inverters Power Save Levels Auxiliary Terminals Operation Operation System Display-Based Functions High Battery TransferAdvanced Generator Start AGS Grid Use TimeTroubleshooting Basic TroubleshootingTroubleshooting Symptom Possible Cause Possible Remedy Troubleshooting TroubleshootingSymptom Possible Cause Possible Remedy Hot or neutral Not be bonded Inverter may be behaving correctly Inverter output is being fed Troubleshooting Error Troubleshooting Message Causes Possible Remedy Error MessagesAC Freq Too High Message Definition Possible RemedyCapacitors Voltage Maximum Disconnect MessagesSell Status Sell Status MessagesSell Status Definition Troubleshooting Specifications for Model GS8048 SpecificationsElectrical Specifications for Model GS8048 Value Mechanical Specifications for Model GS8048Regulatory Specifications Environmental SpecificationsSpecifications Environmental Specifications for All Models ValueDefault Settings and Ranges GS8048 Inverter SettingsFirmware Revision Field Default Minimum Maximum Product Registration OutBack Power TechnologiesProduct Registration Extended WarrantyYear Limited Warranty for Radian Products WarrantyTroubleshooting How to Arrange for Warranty ServiceReturn Material Authorization RMA WarrantyReturning Product to OutBack Out of WarrantyThis page Intentionally Left Blank Index Year WarrantyInput Modes 11, 17, 20, 22 IndexThis page Intentionally Left Blank