Piping
Figure 13 Typical Liebert XDR piping—non-interlaced connection
DRAWING IS NOT TO SCALE
Return
Supply
Liebert XDP/
Liebert XDC A
TOP VIEW
Liebert XDR A Liebert XDR A Liebert XDR A Liebert XDR A
6.3Connection Methods and Points
Refer to site specific drawings for general locations of the piping connections. For Liebert XDR con- nection locations, refer also to Figures 14, 17 and 21.
The assembly and connection means used for piping in the Liebert XD system are the same as those used in conventional refrigeration systems. Observe all standard practices during installation and startup to prevent damage and contamination. All piping must be ASTM Type ACR copper.
The Liebert XDR has supply and return piping access on the top of each module. Supply piping con- nection is 1/2" OD copper pipe, and return piping connection is 7/8" OD copper. The
Both supply and return couplings may be supplied with optional
For Liebert XDRs with removable couplings, the supply piping connection is 1/2" OD and the return piping connection is 7/8" OD. Both the Liebert XDR and the Liebert XD Flex Pipe with removable cou- plings have a
6.4Insulation
To minimize the possibility of condensation, insulate all piping between the Liebert XDR and the Lie- bert XDP or Liebert XDC.
6.5Venting the Holding Charge for
The Liebert XDR in either
NOTE
This procedure is for modules with
To vent the holding charge:
1.Find the Schrader valve that retains the nitrogen holding charge in the Liebert XDR. The valve is inside the rear door, on the supply line (see Figure 14 for
2.Vent the holding charge in the circuit by depressing the pin in the Schrader valve on the supply line.
3.Replace and secure the cap on the Schrader valve that was opened.
15