Emerson XDR user manual Do not Overtighten

Page 32

Piping

Figure 27 Detail view of Liebert XD Flex Pipe and prefabricated piping port

Tighten with torque wrench.

DO NOT OVERTIGHTEN!

Flex Pipe

Service Valve

Note: Make sure the valve is closed before attaching Liebert XD Flex Pipe to the system.

Hold threaded coupler here with a wrench to keep the brass body on

the female connector

from rotating while tightening collar with a torque wrench.

11.Repeat Steps 3 through 10 for the remaining Liebert XD Flex Pipe.

12.For a Liebert XDR module with removable couplings, open the return and then supply service valves. If the Liebert XDR is pre-charged DO NOT open either of the service valves.

13.Refer to the Liebert XDC or Liebert XDP user manual for procedures for evacuation, leak check, charging and startup.

If adding a one-shot, pre-charged Liebert XD module with one-shot pre-charged Liebert XD Flex Pipes to an operational Liebert XD system, after connecting to the header system:

1.Open the return service valve.

2.Open the supply service valve.

Figure 28 Liebert XD prefabricated piping assembly and Liebert XD Flex Pipe

Return Service Valve Make sure valve is open after system leak check

Supply Service Valve.

Make sure valve is open after system

leak check

Return

Main

Supply Main

Return Liebert

XD Flex Pipe from

Liebert XDR

Supply Liebert XD Flex Pipe from Liebert XDR

26

Image 32
Contents Liebert XDR Important Safety Guidelines Fluorinated Greenhouse Gas Requirements-European UnionTable of Contents Installation Checklist and System Fill for Startup SpecificationsFigures Page Example XDR20B1R Component Locations and Model Number NomenclaturePre-Installation Checks Installation ConsiderationsReferences Packing ListProduct/System Description Checking and UnpackingRecyclable Packaging Module HandlingUnpacking the Module Removing packaging Removing the Liebert XDR from the Pallet Remove Liebert XDR from palletLiebert XDR Dimensions Move the Liebert XDROverall dimensions with one-shot coupling pre-charged Determining Placement in the Conditioned Space Overall dimensions with removable couplingGeneric airflow diagram AirflowInstalling the Rack-Mounting Kit onto the Rack Mounting the Liebert XDR on the Rack-Mounting KitDoor Safety Catch System Connection Configuration European Union Fluorinated Greenhouse Gas RequirementsConnection Methods and Points InsulationRecommended Piping Size Hard-Piped Connection SizesBrazing Preparations Leak-Checking and Evacuation Header System Refer to for detailsDegree Connection TOP View Tools Required Male coupling on Liebert XD cooling moduleHex body, union nut on one-shot coupling Connection Methods-Removable Couplings Removable couplings Return Main Supply Main Oil rings on header and Liebert XD Flex Pipe connectors Do not Overtighten Disconnect a Liebert XD Flex Pipe from a Liebert XD System Piping mains without Liebert XD Flex PipeDisconnecting the Liebert XD Flex Pipe from the Liebert XDR Removing the Liebert XDR from a CabinetChecklist for Proper Installation Charging with RefrigerantStarting the Liebert XD System Maintenance Fluorinated Greenhouse Gas RequirementsSpecifications Page Ne t