Emerson XDR user manual Removable couplings

Page 29

Piping

Figure 22 Removable couplings

Flange

On the Liebert

Flex Pipe

Removable Female Coupling on

 

the end of Liebert XD Flex Pipe

O-Ring

On the Liebert XD Module

Table 4

O-ring part number

Liebert Part #

Size, in.

Fitting

 

 

 

192917P1

1/2

FD57-1224-08-10

 

 

 

192917P2

5/8

FD57-1224-10-11

 

 

 

192917P3

7/8

FD57-1224-14-12

 

 

 

 

6.7.5Connect a Liebert XDR with Liebert XD Flex Pipe to a Liebert XD System

NOTE

Check the entire system for leaks before connecting the Liebert XDR with Liebert XD Flex Pipe to the prefabricated piping mains.

Read all instructions before beginning installation.

NOTICE

Risk of refrigerant loss. Can cause environmental pollution and equipment malfunction.

Before connecting the Liebert XDR with Liebert XD Flex Pipe to the prefabricated piping mains, check the whole system for leaks.

Check the Liebert XDR to ensure that the module has no refrigerant leaks. Read all instructions before beginning installation.

Tools Required

One adjustable wrench with a maximum adjustment size of 2 inches

One torque wrench, half-inch drive

Crowsfoot (supplied with Liebert XDP and Liebert XDC)

Liebert XDP or Liebert XDC user manual

NOTE

This operation requires two or more people.

1.Determine the port location of the supply and return piping overhead.

2.Make sure the service valve for each port is closed

3.Remove caps from only the required ports. Do not remove caps from the unused ports.

4.Remove the pipe plugs that are supplied on the Liebert XD Flex Pipe.

5.Inspect both halves of the coupling and remove any foreign contamination from the sealing surfaces and threads before connecting the fittings.

6.Determine the coupling size by locating the number scribed on the Liebert XD Flex Pipe coupling. See Figure 23.

23

Image 29
Contents Liebert XDR Fluorinated Greenhouse Gas Requirements-European Union Important Safety GuidelinesTable of Contents Specifications Installation Checklist and System Fill for StartupFigures Page Component Locations and Model Number Nomenclature Example XDR20B1RInstallation Considerations Pre-Installation ChecksReferences Packing ListChecking and Unpacking Product/System DescriptionModule Handling Recyclable PackagingUnpacking the Module Removing packaging Remove Liebert XDR from pallet Removing the Liebert XDR from the PalletMove the Liebert XDR Liebert XDR DimensionsOverall dimensions with one-shot coupling pre-charged Overall dimensions with removable coupling Determining Placement in the Conditioned SpaceAirflow Generic airflow diagramMounting the Liebert XDR on the Rack-Mounting Kit Installing the Rack-Mounting Kit onto the RackDoor Safety Catch European Union Fluorinated Greenhouse Gas Requirements System Connection ConfigurationInsulation Connection Methods and PointsRecommended Piping Size Hard-Piped Connection SizesBrazing Preparations Refer to for details Leak-Checking and Evacuation Header SystemDegree Connection TOP View Male coupling on Liebert XD cooling module Tools RequiredHex body, union nut on one-shot coupling Connection Methods-Removable Couplings Removable couplings Return Main Supply Main Oil rings on header and Liebert XD Flex Pipe connectors Do not Overtighten Piping mains without Liebert XD Flex Pipe Disconnect a Liebert XD Flex Pipe from a Liebert XD SystemRemoving the Liebert XDR from a Cabinet Disconnecting the Liebert XD Flex Pipe from the Liebert XDRCharging with Refrigerant Checklist for Proper InstallationStarting the Liebert XD System Fluorinated Greenhouse Gas Requirements MaintenanceSpecifications Page Ne t