Emerson XDR user manual Leak-Checking and Evacuation Header System, Refer to for details

Page 23

Piping

Figure 15 Hard pipe connection diagram

Return Main (seen from end )

2-1/8" O.D. or 2-5/8" O.D.

Acceptable Arc

7/8” Refrigerant -Grade

Full-Port Ball Valve

Field-Supplied and

Field-Installed

Recommended Arc

Supply Main

(seen from end ) 1-1/8" O.D.

or 1-3/8" O.D.

1/2” Refrigerant -Grade

Full-Port Ball Valve

Field-Supplied and

Field- Installed

Refer to Table 1 for details.

Copper Tubing

Total length of each line from Liebert XDR to Main not to exceed 72" (1829 mm)

Return from

Cooling Module

Top of

Liebert XDR

and

Equipment

Rack

Supply

to Cooling

Module

Rear of

Equipment Rack

6.6.1Leak-Checking and Evacuation

Refer to the Liebert XDC or Liebert XDP user manual for procedures for evacuation, leak check, charging and startup.

6.6.2Header System

The Liebert XDR module system with optional flexible piping requires use of the Liebert XD prefabri- cated piping assembly. The prefabricated piping is compatible with the Liebert XD Flex Pipe required to attach to the Liebert XDR modules. For the details on piping connection locations, see Figure 14.

For additional information, refer to the Liebert X-treme Density System Design Manual, SL-16655, available at the Liebert Web site: www.liebert.com

17

Image 23
Contents Liebert XDR Fluorinated Greenhouse Gas Requirements-European Union Important Safety GuidelinesTable of Contents Specifications Installation Checklist and System Fill for StartupFigures Page Component Locations and Model Number Nomenclature Example XDR20B1RPacking List Pre-Installation ChecksInstallation Considerations ReferencesChecking and Unpacking Product/System DescriptionModule Handling Recyclable PackagingUnpacking the Module Removing packaging Remove Liebert XDR from pallet Removing the Liebert XDR from the PalletMove the Liebert XDR Liebert XDR DimensionsOverall dimensions with one-shot coupling pre-charged Overall dimensions with removable coupling Determining Placement in the Conditioned SpaceAirflow Generic airflow diagramMounting the Liebert XDR on the Rack-Mounting Kit Installing the Rack-Mounting Kit onto the RackDoor Safety Catch European Union Fluorinated Greenhouse Gas Requirements System Connection ConfigurationInsulation Connection Methods and PointsRecommended Piping Size Hard-Piped Connection SizesBrazing Preparations Refer to for details Leak-Checking and Evacuation Header SystemDegree Connection TOP View Male coupling on Liebert XD cooling module Tools RequiredHex body, union nut on one-shot coupling Connection Methods-Removable Couplings Removable couplings Return Main Supply Main Oil rings on header and Liebert XD Flex Pipe connectors Do not Overtighten Piping mains without Liebert XD Flex Pipe Disconnect a Liebert XD Flex Pipe from a Liebert XD SystemRemoving the Liebert XDR from a Cabinet Disconnecting the Liebert XD Flex Pipe from the Liebert XDRCharging with Refrigerant Checklist for Proper InstallationStarting the Liebert XD System Fluorinated Greenhouse Gas Requirements MaintenanceSpecifications Page Ne t