Emerson XDR user manual Hard-Piped Connection Sizes, Brazing Preparations, Recommended Piping Size

Page 22

Piping

6.5.1Brazing Preparations

The assembly and connection means used for piping in the Liebert XD system are similar to those used for conventional refrigeration systems. All piping should be installed with high-temperature brazed joints. Soft soldering is not recommended.

After the holding charge has been vented and before brazing, wrap a wet rag around the copper con- nections before removing the caps to prevent internal component damage. A torch can be used to remove the caps over the ends of the supply and return lines.

During brazing, the lines must be filled with flowing dry nitrogen to prevent excessive oxidation and scale formation inside the piping. Prevailing good refrigeration practices must be employed for piping supports, leak testing, dehydration and charging. Failure to use good system practices may result in damage to the system. Refer to the ASHRAE refrigeration handbook for general good-practice refrigeration.

6.5.2Recommended Piping Size

Connect the main pipes between the Liebert XDR branch piping and the Liebert XDP or Liebert XDC according to Table 1. Elbows and restrictions must be minimized to ensure good fluid flow.

See Table 1 below for recommended pipe sizes and Figure 3 for piping segment locations.

Table 1 Branch piping sizes for pumped refrigerant loop

Pipe Function

Size / Equivalent Pipe Length

From Liebert XDR supply to supply line of

1/2" OD (0.430" ID) for lengths up to 10 feet (3m)

Liebert XDP/Liebert XDC

7/8" OD (0.545" ID) for lengths over 10 feet but less than 25 feet (3-7.6m)

From Liebert XDR return to return line of

7/8" OD (0.545" ID) for lengths up to 10 feet (3m)

Liebert XDP/Liebert XDC

1-1/8" OD (1.025" ID) for lengths over 10 but less than 25 feet (3-7.6m)

NOTE

To minimize the amount of pumped refrigerant required, do NOT oversize the piping.

See Figure 14 for piping recommendations for hard-piping between the Liebert XDR and the header system.

6.6Hard-Piped Connection Sizes

The supply piping for the refrigeration circuit is 1/2" OD copper pipe. The return piping for the circuit is 7/8" OD copper.

The Liebert XDR modules that are intended for hard-piping connections will have copper caps sol- dered in place and a holding charge of nitrogen.

Figure 14 Piping location and connection sizes—modules with hard-piped connections

1-5/16" (33mm)

1-1/2" (38mm)

5-7/8" (149mm)

 

TOP VIEW

Refrigerant

(Rear of Cabinet)

Schrader Valve

Return Line

 

1-1/8" Refrigerant (29mm) Supply Line

2-1/8" (54mm)

6-1/2" (165mm)

23-1/2" (597mm)

16

Image 22
Contents Liebert XDR Important Safety Guidelines Fluorinated Greenhouse Gas Requirements-European UnionTable of Contents Installation Checklist and System Fill for Startup SpecificationsFigures Page Example XDR20B1R Component Locations and Model Number NomenclatureReferences Pre-Installation ChecksInstallation Considerations Packing ListProduct/System Description Checking and UnpackingRecyclable Packaging Module HandlingUnpacking the Module Removing packaging Removing the Liebert XDR from the Pallet Remove Liebert XDR from palletLiebert XDR Dimensions Move the Liebert XDROverall dimensions with one-shot coupling pre-charged Determining Placement in the Conditioned Space Overall dimensions with removable couplingGeneric airflow diagram AirflowInstalling the Rack-Mounting Kit onto the Rack Mounting the Liebert XDR on the Rack-Mounting KitDoor Safety Catch System Connection Configuration European Union Fluorinated Greenhouse Gas RequirementsConnection Methods and Points InsulationBrazing Preparations Hard-Piped Connection SizesRecommended Piping Size Leak-Checking and Evacuation Header System Refer to for detailsDegree Connection TOP View Tools Required Male coupling on Liebert XD cooling moduleHex body, union nut on one-shot coupling Connection Methods-Removable Couplings Removable couplings Return Main Supply Main Oil rings on header and Liebert XD Flex Pipe connectors Do not Overtighten Disconnect a Liebert XD Flex Pipe from a Liebert XD System Piping mains without Liebert XD Flex PipeDisconnecting the Liebert XD Flex Pipe from the Liebert XDR Removing the Liebert XDR from a CabinetChecklist for Proper Installation Charging with RefrigerantStarting the Liebert XD System Maintenance Fluorinated Greenhouse Gas RequirementsSpecifications Page Ne t