6.7.7Disconnecting the Liebert XD Flex Pipe from the Liebert XDR

NOTICE

Risk of improper reuse of Liebert XD Flex Pipes with one-shot connections. Can cause refrigerant leaks.

Liebert XD Flex Pipes with one-shot connections must not be removed from the Liebert XDR unless they are being replaced with Liebert XD Flex Pipes with one-shot couplings. Do not reuse Liebert XD Flex Pipes with one-shot connections. Reuse may result in refrigerant leaks.

Tools Required

Two adjustable wrenches with a maximum adjustment size of 2 inches

1.Reclaim the refrigerant in the Liebert XD Flex Pipe and in the module by attaching a refrigerant reclaim device to the Schrader valve. For help finding the Schrader valve, see Figures 14, 17 and 21.

2.Hold the Liebert XD Flex Pipe so it does not rotate.

For the Liebert XD Flex Pipe with one-shot couplings, additionally, hold the brass body of the cou- pling so it does not rotate while loosening the couplings. Failing to do so may cause damage.

3.Loosen the Liebert XD Flex Pipe coupling from the module with a wrench.

4.Replace the dust plug on the Liebert XD Flex Pipe.

5.Replace the dust cap on the Liebert XD module.

6.Lay the Liebert XD Flex Pipe with removable couplings aside where it will not be damaged. Discard or recycle the one-shot Liebert XD Flex Pipes.

NOTICE

Risk of permanent damage to the Liebert XD Flex Pipes. Do not fold or bend pipe tightly.

6.7.8Removing the Liebert XDR from a Cabinet

! WARNING

Risk of 130-pound (59 kg) module falling. Can cause equipment damage, personal injury or death.

Removing a Liebert XDR from above a cabinet will require two properly trained and qualified people. Read all instructions before beginning.

1.Reinstall the four removable installation handles.

2.Loosen the bolts holding the Liebert XDR on the cabinet.

3.With the help of another person, lift the Liebert XDR from the cabinet or hanging bracket onto a stable surface.

28

Image 34
Contents Liebert XDR Important Safety Guidelines Fluorinated Greenhouse Gas Requirements-European UnionTable of Contents Installation Checklist and System Fill for Startup SpecificationsFigures Page Example XDR20B1R Component Locations and Model Number NomenclatureReferences Pre-Installation ChecksInstallation Considerations Packing ListProduct/System Description Checking and UnpackingRecyclable Packaging Module HandlingUnpacking the Module Removing packaging Removing the Liebert XDR from the Pallet Remove Liebert XDR from palletLiebert XDR Dimensions Move the Liebert XDROverall dimensions with one-shot coupling pre-charged Determining Placement in the Conditioned Space Overall dimensions with removable couplingGeneric airflow diagram AirflowInstalling the Rack-Mounting Kit onto the Rack Mounting the Liebert XDR on the Rack-Mounting KitDoor Safety Catch System Connection Configuration European Union Fluorinated Greenhouse Gas RequirementsConnection Methods and Points InsulationBrazing Preparations Hard-Piped Connection SizesRecommended Piping Size Leak-Checking and Evacuation Header System Refer to for detailsDegree Connection TOP View Tools Required Male coupling on Liebert XD cooling moduleHex body, union nut on one-shot coupling Connection Methods-Removable Couplings Removable couplings Return Main Supply Main Oil rings on header and Liebert XD Flex Pipe connectors Do not Overtighten Disconnect a Liebert XD Flex Pipe from a Liebert XD System Piping mains without Liebert XD Flex PipeDisconnecting the Liebert XD Flex Pipe from the Liebert XDR Removing the Liebert XDR from a CabinetChecklist for Proper Installation Charging with RefrigerantStarting the Liebert XD System Maintenance Fluorinated Greenhouse Gas RequirementsSpecifications Page Ne t