Mechanical Considerations
4.3Airflow
The server fans draw air into the equipment enclosure. After heated the air, the server fans force the air across the Liebert XDR’s two coils. The Liebert XDR has a low
Figure 10 Generic airflow diagram
Enclosure /Rack
Shown from Side
Refrigerant
Connections
Liebert XDR
Critical
Equipment
Front
of
Rack
Rear
of
Rack
NOTE
Air bypass and recirculation can severely reduce the cooling effectiveness of the Liebert XDR. Blanking plates must be installed in any voids in the rack to prevent air bypass and air recirculation. Contact the factory for further information. Refer to the user manual supplied with the rack the Liebert XDR is mounted on.
Efficient cooling of rack equipment depends on proper use of blanking plates in any voids in the rack and good cable management. Keep the Liebert XDR’s coils clear of any obstructions that may block the airflow.
Each of the Liebert XDR’s coils removes approximately half the load. For even cooling in partially filled racks, servers should be evenly spaced and blanking plates should be installed on unused rack spaces to prevent recirculation of heated air.
11