10.0SPECIFICATIONS

Table 6

Liebert XDR specifications

 

 

 

 

 

 

 

 

 

 

 

 

Models

 

XDR20B1- *

 

XDR20B1P *

 

XDR20B1R *

 

 

(Pre-Charged R-134a)

 

 

 

 

 

 

 

Cooling Capacity, Nominal,

 

 

20.5 kW (5.8 tons)

 

rated at 104ºF (40°C) EAT & 2400ft3/m (68m3/m)

 

 

 

 

 

 

 

 

Conditions

 

55°F (13°C) entering fluid temperature

 

 

50°F (10°C) or lower dew point

 

 

 

 

 

Dimensions, inches (mm)

 

 

 

 

 

 

Height, Including Pipe Connections

82-3/8 (2093)

 

83-1/2 (2121)

 

80 (2032)

 

 

 

 

 

 

 

 

Width With Handles Attached

 

27-3/8 (695)

 

 

 

 

 

 

 

 

 

Handles Removed

 

23-1/2 (597)

 

 

 

 

 

 

 

 

 

Depth

 

6-1/2 (165)

 

 

 

 

 

 

 

 

 

Shipping Length

 

90 (2286)

 

 

 

 

 

 

 

 

 

Shipping Width

 

30-1/2 (775)

 

 

 

 

 

 

 

 

 

Shipping Depth

 

15-1/2 (394)

 

 

 

 

 

 

 

 

 

Max Shipping Depth (4 modules)

 

62 (1575)

 

 

 

 

 

 

 

 

Weight, lb (kg)

 

 

 

 

 

 

Module Only

130 (59)

 

133 (60)

 

130 (59)

 

 

 

 

 

 

 

 

Shipping

225 (103)

 

228 (104)

 

225 (103)

 

 

 

 

 

 

Pipe Connections

 

 

 

 

 

 

Refrigerant Supply

 

 

1/2" OD Type ACR

 

 

 

 

 

 

 

 

Refrigerant Return

 

 

7/8" OD Type ACR

 

 

 

Exterior Finish

Black Matte, Heat-Fused Powder Coat

Safety

 

 

 

CSA, CE Approved

 

*Refer to Figure 2 for the complete part number.

Table 7

Rack mounting kit

 

 

 

Rack

 

Part #

Knurr Miracel

198163G1

Dell PowerEdge 4210

199050G1

 

 

 

HP 10642

 

199051G1

 

 

APC AR3100

199054G1

 

 

 

Table 8

Liebert XD Flex Pipe one-shot assemblies, supply and return

 

 

 

 

 

 

 

 

 

 

Length

Liebert P/N

Liebert P/N

Minimum Bend Radius

Description

Straight Connection

90-Degree

in (mm)

 

 

ft (m)

Assembly

Connection Assembly

 

 

 

 

Supply

Return

 

 

 

 

 

 

 

 

 

 

 

 

10 (3.0)

186566G2

186565G2

 

 

Liebert XD

8 (2.5)

186566G3

186565G3

7 (178)

9 (229)

Flex Pipe Kit

6 (1.8)

186566G1

186565G1

 

 

 

 

 

 

 

 

 

 

 

4 (1.2)

186566G4

186565G4

 

 

 

 

 

 

 

 

 

Table 9

Liebert XD Flex Pipe removable assemblies, supply and return

 

 

 

 

 

 

 

 

 

 

Length

Liebert P/N

Liebert P/N

Minimum Bend Radius

Description

Straight Connection

90-Degree Connection

in (mm)

 

 

ft (m)

Assembly

Assembly

 

 

 

 

Supply

Return

 

 

 

 

 

10 (3.0)

187865G2

187864G2

 

 

Liebert XD

 

8 (2.5)

187865G3

187864G3

7 (178)

9 (229)

Flex Pipe Kit

6 (1.8)

187865G1

187864G1

 

 

 

 

4 (1.2)

187865G4

187864G4

 

 

32

Image 38
Contents Liebert XDR Important Safety Guidelines Fluorinated Greenhouse Gas Requirements-European UnionTable of Contents Installation Checklist and System Fill for Startup SpecificationsFigures Page Example XDR20B1R Component Locations and Model Number NomenclatureReferences Pre-Installation ChecksInstallation Considerations Packing ListProduct/System Description Checking and UnpackingRecyclable Packaging Module HandlingUnpacking the Module Removing packaging Removing the Liebert XDR from the Pallet Remove Liebert XDR from palletLiebert XDR Dimensions Move the Liebert XDROverall dimensions with one-shot coupling pre-charged Determining Placement in the Conditioned Space Overall dimensions with removable couplingGeneric airflow diagram AirflowInstalling the Rack-Mounting Kit onto the Rack Mounting the Liebert XDR on the Rack-Mounting KitDoor Safety Catch System Connection Configuration European Union Fluorinated Greenhouse Gas RequirementsConnection Methods and Points InsulationRecommended Piping Size Hard-Piped Connection SizesBrazing Preparations Leak-Checking and Evacuation Header System Refer to for detailsDegree Connection TOP View Tools Required Male coupling on Liebert XD cooling moduleHex body, union nut on one-shot coupling Connection Methods-Removable Couplings Removable couplings Return Main Supply Main Oil rings on header and Liebert XD Flex Pipe connectors Do not Overtighten Disconnect a Liebert XD Flex Pipe from a Liebert XD System Piping mains without Liebert XD Flex PipeDisconnecting the Liebert XD Flex Pipe from the Liebert XDR Removing the Liebert XDR from a CabinetChecklist for Proper Installation Charging with RefrigerantStarting the Liebert XD System Maintenance Fluorinated Greenhouse Gas RequirementsSpecifications Page Ne t