Piping

6.7.3Connection Methods—Removable Couplings

The assembly and connection means used for piping in the Liebert XD system are the same as those used in conventional refrigeration systems. Observe all standard practices during installation and startup to prevent damage and contamination.

Both supply and return fittings may be supplied with optional, removable couplings.

Figure 21 Piping location and connection sizes—modules with removable couplings

1-5/16"

 

TOP VIEW

 

7/8"

 

(Rear of Cabinet)

 

(33mm)

 

Refrigerant

Refrigerant

 

(22mm)

 

Return Line

Schrader Valve

Supply Line

 

 

 

 

1-1/2"

 

 

 

2-1/8"

(38mm)

 

 

 

 

 

 

(54mm)

 

 

 

 

5-7/8"

 

 

 

6-1/2"

(149mm)

 

 

 

 

 

 

(165mm)

 

 

 

 

23-1/2" (597mm)

6.7.4Connect Liebert XD Flex Pipe with Removable Coupling to a Liebert XD Cooling Module Tools Required

One adjustable wrench with a maximum adjustment size of 2 inches

One torque wrench, half-inch drive (see Table 3 for sizes)

1.Check the Liebert XD Flex Pipe for proper length.

2.Remove the protector plugs from the Liebert XD Flex Pipe.

3.Remove the protector cap from the couplings on the module.

4.Wipe the fittings and threaded surfaces clean of particles and other foreign substances.

5.Verify the O-ring is in place on the module coupling. Should additional O-rings be required, refer to Table 4.

6.Place the Liebert Flex Pipe assembly so that the flat face of the flange on the Liebert XD Flex Pipe coupling comes into contact with the O-ring on the module coupling.

7.Thread the coupling halves together by hand to ensure that the threads mate properly.

If a torque wrench is not available, continue with the steps below.

Table 3 Torque and wrench sizes for connecting Liebert Flex Pipe to the Liebert XDR with removable couplings

Coupling

Wrench Size, in.

Torque, Union Nut

(mm)

Size, in.

 

Only, ft-lb (Nm)

Union Nut

 

 

 

 

 

 

 

1/2 (Supply)

15/16 (24)

40

(55)

 

 

 

 

1 (Return)

1-5/8 (41)

110

(150)

 

 

 

 

8.Hold the Liebert XD Flex Pipe so that is does not rotate and use the torque wrench to tighten the union nut to the proper value shown in Table 3.

9.Tighten the union nut on the Liebert XD Flex Pipe to the coupling on the module with the adjustable wrench until a definite resistance is felt.

10.Use a marker or pen to draw a line lengthwise across the module coupling to the Liebert XD Flex Pipe. The line should parallel the Liebert XD Flex Pipe.

11.Tighten the nuts an additional quarter-turn, judging the amount by the mark drawn in Step 10.

22

Image 28
Contents Liebert XDR Important Safety Guidelines Fluorinated Greenhouse Gas Requirements-European UnionTable of Contents Installation Checklist and System Fill for Startup SpecificationsFigures Page Example XDR20B1R Component Locations and Model Number NomenclaturePre-Installation Checks Installation ConsiderationsReferences Packing ListProduct/System Description Checking and UnpackingRecyclable Packaging Module HandlingUnpacking the Module Removing packaging Removing the Liebert XDR from the Pallet Remove Liebert XDR from palletLiebert XDR Dimensions Move the Liebert XDROverall dimensions with one-shot coupling pre-charged Determining Placement in the Conditioned Space Overall dimensions with removable couplingGeneric airflow diagram AirflowInstalling the Rack-Mounting Kit onto the Rack Mounting the Liebert XDR on the Rack-Mounting KitDoor Safety Catch System Connection Configuration European Union Fluorinated Greenhouse Gas RequirementsConnection Methods and Points InsulationBrazing Preparations Hard-Piped Connection SizesRecommended Piping Size Leak-Checking and Evacuation Header System Refer to for detailsDegree Connection TOP View Tools Required Male coupling on Liebert XD cooling moduleHex body, union nut on one-shot coupling Connection Methods-Removable Couplings Removable couplings Return Main Supply Main Oil rings on header and Liebert XD Flex Pipe connectors Do not Overtighten Disconnect a Liebert XD Flex Pipe from a Liebert XD System Piping mains without Liebert XD Flex PipeDisconnecting the Liebert XD Flex Pipe from the Liebert XDR Removing the Liebert XDR from a CabinetChecklist for Proper Installation Charging with RefrigerantStarting the Liebert XD System Maintenance Fluorinated Greenhouse Gas RequirementsSpecifications Page Ne t