Extension Cords
Using extension cords is not recommended. The use of extension cords will cause voltage to drop resulting in power loss to the motor and overheating. Instead of using an extension cord, increase the working reach of the air hose by attaching another length of hose to its end. Attach additional lengths of hose as needed.
If an extension cord must be used, be sure it is:
•a
•in good condition
•no longer than 50 feet
•14 gauge (AWG) or larger. (Wire size increases as gauge number decreases. 12 AWG, 10 AWG, and 8 AWG may also be used. DO NOT USE 16 OR 18 AWG.)
Voltage and Circuit Protection
Refer to the Parts Manual for the voltage and minimum branch circuit requirements.
Certain air compressors can be operated on a 15 amp circuit if the following conditions are met.
1.Voltage supply is
2.Circuit is not used to supply any other electrical needs (lights, appliances, etc.).
3.Circuit is equipped with a 15 amp circuit breaker minimum or 15 amp time delay fuse. NOTE: If compressor is connected to a circuit protected by fuses, use only time delay fuses marked “D” for Canada and "T" for US.
4.Extension cords comply with specifications.
If any of the above conditions cannot be met, or if operation of the compressor repeatedly causes interruption of the power, it may be necessary to operate it from a 20 amp circuit. It is not necessary to change the cord set.
A05581 | 10- ENG |