HP Performance Optimized Data Center (POD) 40cp manual Connecting the power

Page 23

11.(Optional) Connect the HP POD humidifier to the domestic or industrial water drain (1) and supply

(2)lines. For more information about the humidifier, see the product documentation.

12.Perform one of the following:

o If your HP POD is located inside, HP recommends connecting each of the drains to the local drain line.

o If your HP POD is located outside, you can choose to connect to the local drain line, or allow the water to drain off freely in your location. For more information, see Drain locations ("HP POD drains" on page 28).

Connecting the power

IMPORTANT: A licensed electrician must connect the power according the local electric code, consistent with supplier and consulting engineer drawings.

1.Verify that the HP POD, transformer, and switchboard are in their final locations.

2.Make all connections:

o Connect the main power leads from your facility to the transformer (1 to 2).

Each connection is labeled with colored tape, according to local standard requirements. o Connect the transformer to the switchboard (2 to 3).

o Connect the three 3-in flexible conduits from the switchboard to the junction box on the HP POD (3 to 4).

Installation 23

Image 23
Contents Part Number March 2009 First Edition HP Performance-Optimized Datacenter User GuideIntended audience Contents HP POD troubleshooting Water precautions Water temperatureHP POD frequently asked questions Acronyms and abbreviations Index Moving the HP POD Site requirementsOptimum environment Location considerationsAvailable to connect to central facility infrastructure Cooling water Power Drain optionalCallout Connection Temperature considerationsEnvironmental considerations Work space requirementsLightning protection Component documentationLeveling requirements Grounding requirementsOperator safety Component health Safety considerationsSafety information Safety considerations HP POD components Component Description Component identificationHP POD components External emergency components Component Description HP POD emergency componentsComponent Description HP POD panel locationsInternal emergency components Component Description ∗Optional component Transformer and switchboard components optionalWater distribution kit components optional HP POD contents InstallationComponent Quantity Part number Preinstallation checklistRequired tools Pipe wrench Installing the HP POD using the optional componentsConnecting the water Installation Installation Installation Connecting the power Installation Commissioning the HP POD Installation Controlling the fan speed Water supply temperatureCooling system HP POD cooling systemPull the overhead down Condensation managementHP POD drains Leak detection Water quality requirements Water quality requirements and specificationsAcceptable water quality specifications Plumbing materials to avoid Water precautionsWater temperature Frost damageElectrical busway Power managementPower distribution Rack power Panels EPO Panel Assd panelBMS panel Electrical busway enclosed circuit breakerEPO modes House panel Fire alarm control panelEpms panel Fan control panelSecurity panel location Building management system Using a building management system BMSConnecting the HP POD to the BMS BMS alarms Managing BMS settings from the HP PODAlarm Meaning Solution Safety and security alarmsFire alarm sequence of operations Building management system Optional components Water distribution kit Transformers and switchboardsCallout Specification Water distribution kit power requirementsQuestion Answer Frequently asked questionsHP POD frequently asked questions Drain pans or the water main drain pan. The additional water Issue Resolution TroubleshootingHP POD troubleshooting Features Specifications SpecificationsHP POD specifications Electrical specificationsWater supply specifications with a water distribution kit Water specificationsFeature Specification Thermal and air flow performance Rack specificationsStandard HP POD racks AN982A Feature Specification For more information, see Water specifications on Environmental specificationsWater distribution kit specifications Maintenance HP contact information Before you contact HPRegulatory compliance notices Bsmi notice Class a equipment Chinese noticeKorean class a notice Japanese class a notice Acronyms and abbreviations Performance-Optimized Datacenter Power distribution unitUninterruptible power system National Electrical Manufacturers AssociationFan Fan control panel 14, 35 Fan speed Fire alarm control panel 13, 14, 35Index Safety considerations Index