HP Performance Optimized Data Center (POD) 40cp manual Water quality requirements

Page 30

Water quality requirements

Water quality requirements and specifications

Closed-loop water must not contain any lime scale deposits or loose debris.

The water must have a low level of hardness, particularly a low level of carbon hardness. Additionally, the water must not be so soft that it attacks the materials with which it comes into contact.

The chilled water temperature to be supplied to the HP POD is 12º to 24ºC (55º to 75ºF). Freezing water might cause a blockage and damage to the unit. In outside locations subject to freezing temperatures, an additive such as glycol might be necessary to lower the freezing point. However, the heat transfer potential of the water is lower, so the equipment must be derated properly.

Acceptable water quality specifications

Water must be maintained per the following acceptable water quality standards.

Parameter

Range

 

 

pH

8.0–10

 

 

Specific conductance at 25ºC

0–2500 µmhos/cm

(77ºF)

 

 

 

Alkalinity ("M" as CaCO3)

150–1000 ppm

Sulfur (SO4)

0–150 ppm

Chloride (Cl)

0–100 ppm

 

 

Hardness (CaCO3)

0–350 ppm

Calcium hardness (CaCO3)

0–200 ppm

Magnesium hardness (CaCO3)

0–150 ppm

Copper (Cu)

< 0.20 ppm

 

 

Iron (Fe)

< 3.0 ppm

 

 

Aluminum (Al)

< 0.50 ppm

 

 

Sodium (Na)

0–1000 ppm

 

 

Silica (SiO2)

0–150 ppm

Zinc (Zn)

< 1.0 ppm

 

 

Manganese (Mn)

< 0.1 ppm

 

 

Phosphate Ortho- (PO4)

< 3 ppm

Bacteria

< 1000 CFU/ml

 

 

Suspended solids

< 10 ppm

 

 

If your water is out of range, consult a water quality expert.

Water quality requirements 30

Image 30
Contents HP Performance-Optimized Datacenter User Guide Part Number March 2009 First EditionIntended audience Contents Water precautions Water temperature HP POD frequently asked questionsHP POD troubleshooting Acronyms and abbreviations Index Location considerations Site requirementsOptimum environment Moving the HP PODCooling water Power Drain optional Available to connect to central facility infrastructureWork space requirements Temperature considerationsEnvironmental considerations Callout ConnectionGrounding requirements Component documentationLeveling requirements Lightning protectionSafety considerations Safety informationOperator safety Component health Safety considerations Component identification HP POD componentsHP POD components Component Description HP POD emergency components External emergency components Component DescriptionHP POD panel locations Internal emergency components Component DescriptionComponent Description Transformer and switchboard components optional ∗Optional componentWater distribution kit components optional Installation HP POD contentsPreinstallation checklist Required toolsComponent Quantity Part number Installing the HP POD using the optional components Connecting the waterPipe wrench Installation Installation Installation Connecting the power Installation Commissioning the HP POD Installation HP POD cooling system Water supply temperatureCooling system Controlling the fan speedCondensation management HP POD drainsPull the overhead down Leak detection Water quality requirements and specifications Acceptable water quality specificationsWater quality requirements Frost damage Water precautionsWater temperature Plumbing materials to avoidPower management Electrical buswayPower distribution Rack power Panels Electrical busway enclosed circuit breaker Assd panelBMS panel EPO PanelEPO modes Fan control panel Fire alarm control panelEpms panel House panelSecurity panel location Using a building management system BMS Connecting the HP POD to the BMSBuilding management system Managing BMS settings from the HP POD BMS alarmsSafety and security alarms Fire alarm sequence of operationsAlarm Meaning Solution Building management system Optional components Transformers and switchboards Water distribution kitWater distribution kit power requirements Callout SpecificationFrequently asked questions HP POD frequently asked questionsQuestion Answer Drain pans or the water main drain pan. The additional water Troubleshooting HP POD troubleshootingIssue Resolution Electrical specifications SpecificationsHP POD specifications Features SpecificationsWater specifications Feature SpecificationWater supply specifications with a water distribution kit Rack specifications Standard HP POD racks AN982A Feature SpecificationThermal and air flow performance Environmental specifications Water distribution kit specificationsFor more information, see Water specifications on Maintenance Before you contact HP HP contact informationRegulatory compliance notices Bsmi notice Chinese notice Korean class a notice Japanese class a noticeClass a equipment Acronyms and abbreviations National Electrical Manufacturers Association Power distribution unitUninterruptible power system Performance-Optimized DatacenterFire alarm control panel 13, 14, 35 IndexFan Fan control panel 14, 35 Fan speed Safety considerations Index
Related manuals
Manual 21 pages 18 Kb Manual 79 pages 43.3 Kb