HP Performance Optimized Data Center (POD) 40cp manual Maintenance

Page 54

Maintenance

Periodic maintenance

Perform periodic inspections of the POD to ensure there is no sign of overheating. During periodic inspections, pay special attention to electrical connections and wiring.

Electrical busway maintenance

Periodically tighten the electrical busway connections. HP recommends tightening the electrical busway connections every six months.

Inspect the busway drop boxes for loose connections, and tighten if necessary.

Water system maintenance

HP does not maintain your water system quality.

Consult a water treatment specialist to perform the following maintenance:

Flush the HP POD

How often you must flush the HP POD depends on how often you shutdown the HP POD and the water quality.

Maintain water quality

The water treatment specialist should periodically take a water sample and add new chemical treatments to the HP POD water or water distribution kit as needed to maintain the specified water quality ("Water quality requirements" on page 30).

Air filter replacement

There are twelve 14 in x 36 in x 1 in air filters inside the HP POD.

If you have the optional air filter sensor (on page 44) installed, you will be notified through your BMS when you need to change a filter.

If you do not have the sensor installed, HP recommends periodically inspecting and changing each air filter.

Air and water heat exchanger maintenance

The air and water heat exchanger requires no maintenance. If particulates are present in the cooling water, a filter must be fitted immediately upstream from the water inlet fittings. Check the functionality of the condensation drainage system regularly. Regularly perform visual inspections for leaks (annually).

Maintenance 54

Image 54
Contents HP Performance-Optimized Datacenter User Guide Part Number March 2009 First EditionIntended audience Contents Water precautions Water temperature HP POD frequently asked questionsHP POD troubleshooting Acronyms and abbreviations Index Location considerations Site requirementsOptimum environment Moving the HP PODCooling water Power Drain optional Available to connect to central facility infrastructureWork space requirements Temperature considerationsEnvironmental considerations Callout ConnectionGrounding requirements Component documentationLeveling requirements Lightning protectionSafety considerations Safety informationOperator safety Component health Safety considerations Component identification HP POD componentsHP POD components Component Description HP POD emergency components External emergency components Component DescriptionHP POD panel locations Internal emergency components Component DescriptionComponent Description Transformer and switchboard components optional ∗Optional componentWater distribution kit components optional Installation HP POD contentsPreinstallation checklist Required toolsComponent Quantity Part number Installing the HP POD using the optional components Connecting the waterPipe wrench Installation Installation Installation Connecting the power Installation Commissioning the HP POD Installation HP POD cooling system Water supply temperatureCooling system Controlling the fan speedCondensation management HP POD drainsPull the overhead down Leak detection Water quality requirements and specifications Acceptable water quality specificationsWater quality requirements Frost damage Water precautionsWater temperature Plumbing materials to avoidPower management Electrical buswayPower distribution Rack power Panels Electrical busway enclosed circuit breaker Assd panelBMS panel EPO PanelEPO modes Fan control panel Fire alarm control panelEpms panel House panelSecurity panel location Using a building management system BMS Connecting the HP POD to the BMSBuilding management system Managing BMS settings from the HP POD BMS alarmsSafety and security alarms Fire alarm sequence of operationsAlarm Meaning Solution Building management system Optional components Transformers and switchboards Water distribution kitWater distribution kit power requirements Callout SpecificationFrequently asked questions HP POD frequently asked questionsQuestion Answer Drain pans or the water main drain pan. The additional water Troubleshooting HP POD troubleshootingIssue Resolution Electrical specifications SpecificationsHP POD specifications Features SpecificationsWater specifications Feature SpecificationWater supply specifications with a water distribution kit Rack specifications Standard HP POD racks AN982A Feature SpecificationThermal and air flow performance Environmental specifications Water distribution kit specificationsFor more information, see Water specifications on Maintenance Before you contact HP HP contact informationRegulatory compliance notices Bsmi notice Chinese notice Korean class a notice Japanese class a noticeClass a equipment Acronyms and abbreviations National Electrical Manufacturers Association Power distribution unitUninterruptible power system Performance-Optimized DatacenterFire alarm control panel 13, 14, 35 IndexFan Fan control panel 14, 35 Fan speed Safety considerations Index