The high density HP POD includes an additional electrical busway in the center of the unit.
High density HP POD
Feature | Specification |
|
|
Number of busways | 3 |
|
|
Frequency | 60Hz |
|
|
Amps (per breaker) | 400A |
|
|
Neutral Ampacity (per breaker) | 480A |
|
|
Amps derated percentage | 20% |
|
|
Max usable amps (per busway) | 320A |
|
|
Voltage (per busway) | 415V |
|
|
Grounding | Aluminum casing |
|
|
Phases | 3 |
|
|
Rack power
Power is provided to each of the rack by PDUs. The PDUs can be moved around the HP POD to support component power requirements. The PDUs are powered by the drop boxes attached to each electrical busway.
For more information regarding power shortages to the PDUs or electrical busway drop boxes, see Troubleshooting (on page 49).
Power management 34