HP Performance Optimized Data Center (POD) 40cp manual EPO modes

Page 37

To enable remote access to the EPO system, switch to Bypass mode.

Callout

Component

Description

 

 

 

1

Power On LED

Indicates the EPO is functional, and

 

 

operating in Test mode, Armed mode,

 

 

or Bypass mode.

 

 

 

2

EPO Armed mode LED

Indicates the EPO is operating in

 

 

Armed mode.

 

 

 

3

Reset button

Resets the EPO system after an EPO

 

 

alarm has been triggered.

 

 

 

4

Three way key-operated

Sets the EPO operating mode (Test,

 

switch

Armed, or Bypass).

 

 

 

5

System alarm/ EPO

Indicates an EPO alarm has been

 

shutdown

triggered and non-emergency HP POD

 

(red)

power has been shut off.

 

 

 

 

 

6

System Test mode LED

Indicates the EPO is undergoing a

 

(amber)

system test.

 

 

 

 

 

7

EPO Bypass mode LED

Indicates the EPO is in Bypass mode.

 

(green)

 

 

 

 

After an EPO alarm, reset the EPO system:

1.Use the button key release mechanism to restore the EPO alarm buttons to their normal state.

2.Reset the main breaker in the House panel.

3.Reset the electrical busway breakers.

4.Press the Reset button on the EPO panel.

EPO modes

The EPO panel operates in three modes: Armed, Test, and Bypass. The operating mode is determined by the status of a key-operated selector switch on the EPO panel. The switch status can be reported to a monitoring system that is external to the POD.

Power management 37

Image 37
Contents Part Number March 2009 First Edition HP Performance-Optimized Datacenter User GuideIntended audience Contents HP POD frequently asked questions Water precautions Water temperatureHP POD troubleshooting Acronyms and abbreviations Index Optimum environment Site requirementsLocation considerations Moving the HP PODAvailable to connect to central facility infrastructure Cooling water Power Drain optionalEnvironmental considerations Temperature considerationsWork space requirements Callout ConnectionLeveling requirements Component documentationGrounding requirements Lightning protectionSafety information Safety considerationsOperator safety Component health Safety considerations HP POD components Component identificationHP POD components Component Description External emergency components Component Description HP POD emergency componentsInternal emergency components Component Description HP POD panel locationsComponent Description ∗Optional component Transformer and switchboard components optionalWater distribution kit components optional HP POD contents InstallationRequired tools Preinstallation checklistComponent Quantity Part number Connecting the water Installing the HP POD using the optional componentsPipe wrench Installation Installation Installation Connecting the power Installation Commissioning the HP POD Installation Cooling system Water supply temperatureHP POD cooling system Controlling the fan speedHP POD drains Condensation managementPull the overhead down Leak detection Acceptable water quality specifications Water quality requirements and specificationsWater quality requirements Water temperature Water precautionsFrost damage Plumbing materials to avoidElectrical busway Power managementPower distribution Rack power Panels BMS panel Assd panelElectrical busway enclosed circuit breaker EPO PanelEPO modes Epms panel Fire alarm control panelFan control panel House panelSecurity panel location Connecting the HP POD to the BMS Using a building management system BMSBuilding management system BMS alarms Managing BMS settings from the HP PODFire alarm sequence of operations Safety and security alarmsAlarm Meaning Solution Building management system Optional components Water distribution kit Transformers and switchboardsCallout Specification Water distribution kit power requirementsHP POD frequently asked questions Frequently asked questionsQuestion Answer Drain pans or the water main drain pan. The additional water HP POD troubleshooting TroubleshootingIssue Resolution HP POD specifications SpecificationsElectrical specifications Features SpecificationsFeature Specification Water specificationsWater supply specifications with a water distribution kit Standard HP POD racks AN982A Feature Specification Rack specificationsThermal and air flow performance Water distribution kit specifications Environmental specificationsFor more information, see Water specifications on Maintenance HP contact information Before you contact HPRegulatory compliance notices Bsmi notice Korean class a notice Japanese class a notice Chinese noticeClass a equipment Acronyms and abbreviations Uninterruptible power system Power distribution unitNational Electrical Manufacturers Association Performance-Optimized DatacenterIndex Fire alarm control panel 13, 14, 35Fan Fan control panel 14, 35 Fan speed Safety considerations Index