HP Performance Optimized Data Center (POD) 40cp manual Water specifications, Feature Specification

Page 51

Feature

Specification

 

 

Number of input circuit breakers

2: 1 per panel

 

 

Protection percentage

80%

 

 

Amps (per breaker)

400A

 

 

Fire alarm panel connections

The electrical layout of the fire alarm system is as described in the schematic drawing supplied with the

HP POD.

Water specifications

Water supply specifications without a water distribution kit

Feature

Specification

 

 

 

Facility input temperature to HP POD

12º to 24ºC (55º to 75ºF)

 

 

 

Operating pressure

137,895 to 172,369 Pa (20 to

 

25 psi)

 

 

 

Rated pressure max

1,034,213 Pa (150 psi)

 

 

 

HP POD pressure drop

110,316 Pa (16 psi)

 

 

 

HP POD water flow rate

908.5 l/min (240 gal/min)

 

 

 

Cooling water supply and return

(2) 10.16 cm (4 inch) 150#

connections

flange

 

 

 

Humidifier

3.79 l/hr (1 gal/hr) domestic

 

water from an alternate supply

 

source

 

 

 

Water supply specifications with a water distribution kit

 

 

 

Feature

 

Specification

 

 

 

Facility input temperature to the water

 

4º to 10ºC (40º to 50ºF)

distribution kit

 

 

 

 

 

Water distribution kit temperature output to

 

12º to 24ºC (55º to 75ºF)

the HP POD

 

 

 

 

 

Operating pressure

 

137,895 to 172,369 Pa (20

 

 

to 25 psi)

 

 

 

Rated pressure max

 

1,034,213 Pa (150 psi)

 

 

 

HP POD pressure drop

 

110,316 Pa (16 psi)

 

 

 

Water distribution kit pressure drop

 

34,474 Pa (5 psi) max

 

 

 

Water flow rate to the water distribution kit

 

757 to 1,893 l/min (200 to

 

 

500 gal/min) based on a

 

 

facility operating delta T

 

 

range of 6°to 12°C (10º–

 

 

20ºF)

 

 

Water distribution kit flow rate to the HP POD

908.5 l/min (240 gal/min)

 

 

Cooling water supply and return connections

(2) 10.16 cm (4 inch) 150#

 

 

flange

 

 

 

Specifications 51

Image 51
Contents Part Number March 2009 First Edition HP Performance-Optimized Datacenter User GuideIntended audience Contents Water precautions Water temperature HP POD frequently asked questionsHP POD troubleshooting Acronyms and abbreviations Index Moving the HP POD Site requirementsOptimum environment Location considerationsAvailable to connect to central facility infrastructure Cooling water Power Drain optionalCallout Connection Temperature considerationsEnvironmental considerations Work space requirementsLightning protection Component documentationLeveling requirements Grounding requirementsSafety considerations Safety informationOperator safety Component health Safety considerations Component identification HP POD componentsHP POD components Component Description External emergency components Component Description HP POD emergency componentsHP POD panel locations Internal emergency components Component DescriptionComponent Description ∗Optional component Transformer and switchboard components optionalWater distribution kit components optional HP POD contents InstallationPreinstallation checklist Required toolsComponent Quantity Part number Installing the HP POD using the optional components Connecting the waterPipe wrench Installation Installation Installation Connecting the power Installation Commissioning the HP POD Installation Controlling the fan speed Water supply temperatureCooling system HP POD cooling systemCondensation management HP POD drainsPull the overhead down Leak detection Water quality requirements and specifications Acceptable water quality specificationsWater quality requirements Plumbing materials to avoid Water precautionsWater temperature Frost damageElectrical busway Power managementPower distribution Rack power Panels EPO Panel Assd panelBMS panel Electrical busway enclosed circuit breakerEPO modes House panel Fire alarm control panelEpms panel Fan control panelSecurity panel location Using a building management system BMS Connecting the HP POD to the BMSBuilding management system BMS alarms Managing BMS settings from the HP PODSafety and security alarms Fire alarm sequence of operationsAlarm Meaning Solution Building management system Optional components Water distribution kit Transformers and switchboardsCallout Specification Water distribution kit power requirementsFrequently asked questions HP POD frequently asked questionsQuestion Answer Drain pans or the water main drain pan. The additional water Troubleshooting HP POD troubleshootingIssue Resolution Features Specifications SpecificationsHP POD specifications Electrical specificationsWater specifications Feature SpecificationWater supply specifications with a water distribution kit Rack specifications Standard HP POD racks AN982A Feature SpecificationThermal and air flow performance Environmental specifications Water distribution kit specificationsFor more information, see Water specifications on Maintenance HP contact information Before you contact HPRegulatory compliance notices Bsmi notice Chinese notice Korean class a notice Japanese class a noticeClass a equipment Acronyms and abbreviations Performance-Optimized Datacenter Power distribution unitUninterruptible power system National Electrical Manufacturers AssociationFire alarm control panel 13, 14, 35 IndexFan Fan control panel 14, 35 Fan speed Safety considerations Index