HP Performance Optimized Data Center (POD) 40cp manual Environmental specifications

Page 53

Environmental specifications

Features

Specifications

 

 

Operating temperature

-18ºC to 54ºC (0ºF to 130ºF)

 

 

Non-operating

2ºC to 54ºC (35ºF to 130ºF)

temperature*

 

 

 

Transit temperature**

-30ºC to 60ºC (-22ºF to 140ºF), up to 72 hours

 

 

Operating humidity

15% to 80% relative noncondensing

 

26ºC (79ºF) maximum wet bulb temperature

 

 

Non-operating humidity*

5 to 95% relative noncondensing

 

39ºC (102ºF) maximum wet bulb temperature

 

 

Operating altitude

-76.2 to 3,048 m (-250 to 10,000 ft)

 

 

Non-operating altitude

-76.2 to 9,144 m (-250 to 30,000 ft)

 

 

*For non-operating specifications, consider the temperature of computer and IT equipment inside the HP POD. **The HP POD must be drained before it is moved to a new location.

For areas prone to freezing, consult HP for applicable operating solutions and evaluate water lines as described in the Frost damage (on page 31) section of this document.

Water distribution kit specifications

Feature

Specification

 

 

Dimensions

10 ft x 8 ft x 9 ft

 

 

Tank capacity

7.8 gal

 

 

Pumps electrical

480V, 3-phase, 60 Hz

 

 

Pumps flow

240 gal/min

 

 

Chemical pot feeder

10 gal

capacity

 

 

 

For more information, see Water specifications (on page 51).

Specifications 53

Image 53
Contents Part Number March 2009 First Edition HP Performance-Optimized Datacenter User GuideIntended audience Contents HP POD troubleshooting Water precautions Water temperatureHP POD frequently asked questions Acronyms and abbreviations Index Optimum environment Site requirementsLocation considerations Moving the HP PODAvailable to connect to central facility infrastructure Cooling water Power Drain optionalEnvironmental considerations Temperature considerationsWork space requirements Callout ConnectionLeveling requirements Component documentationGrounding requirements Lightning protectionOperator safety Component health Safety considerationsSafety information Safety considerations HP POD components Component Description Component identificationHP POD components External emergency components Component Description HP POD emergency componentsComponent Description HP POD panel locationsInternal emergency components Component Description ∗Optional component Transformer and switchboard components optionalWater distribution kit components optional HP POD contents InstallationComponent Quantity Part number Preinstallation checklistRequired tools Pipe wrench Installing the HP POD using the optional componentsConnecting the water Installation Installation Installation Connecting the power Installation Commissioning the HP POD Installation Cooling system Water supply temperatureHP POD cooling system Controlling the fan speedPull the overhead down Condensation managementHP POD drains Leak detection Water quality requirements Water quality requirements and specificationsAcceptable water quality specifications Water temperature Water precautionsFrost damage Plumbing materials to avoidElectrical busway Power managementPower distribution Rack power Panels BMS panel Assd panelElectrical busway enclosed circuit breaker EPO PanelEPO modes Epms panel Fire alarm control panelFan control panel House panelSecurity panel location Building management system Using a building management system BMSConnecting the HP POD to the BMS BMS alarms Managing BMS settings from the HP PODAlarm Meaning Solution Safety and security alarmsFire alarm sequence of operations Building management system Optional components Water distribution kit Transformers and switchboardsCallout Specification Water distribution kit power requirementsQuestion Answer Frequently asked questionsHP POD frequently asked questions Drain pans or the water main drain pan. The additional water Issue Resolution TroubleshootingHP POD troubleshooting HP POD specifications SpecificationsElectrical specifications Features SpecificationsWater supply specifications with a water distribution kit Water specificationsFeature Specification Thermal and air flow performance Rack specificationsStandard HP POD racks AN982A Feature Specification For more information, see Water specifications on Environmental specificationsWater distribution kit specifications Maintenance HP contact information Before you contact HPRegulatory compliance notices Bsmi notice Class a equipment Chinese noticeKorean class a notice Japanese class a notice Acronyms and abbreviations Uninterruptible power system Power distribution unitNational Electrical Manufacturers Association Performance-Optimized DatacenterFan Fan control panel 14, 35 Fan speed Fire alarm control panel 13, 14, 35Index Safety considerations Index