•To disable power to a single PDU, turn off the main switch on that PDU.
•To disable power to a single rack, open the main breaker on the dropbox connected to the electrical busway.
•To disable power to a single electrical busway, open the appropriate main breaker for that busway on the corresponding electrical busway panel outside of the HP POD.
Power distribution
The standard HP POD is powered by two electrical busways on the ends of the unit.
Standard HP POD
Feature | Specification |
|
|
Number of busways | 2 |
|
|
Frequency | 60Hz |
|
|
Amps (per busway) | 400A |
|
|
Neutral Ampacity (per breaker) | 480A |
|
|
Amps derated percentage | 20% |
|
|
Max usable amps (per busway) | 320A |
|
|
Voltage (per busway) | 415V |
|
|
Grounding | Aluminum casing |
|
|
Phases | 3 |
|
|
Power management 33