HP Performance Optimized Data Center (POD) 40cp manual Frost damage, Plumbing materials to avoid

Page 31

Frost damage

To avoid frost damage, the water temperature must not be allowed to fall below the minimum permissible temperature of +4 ºC (+39.2 ºF) at any point in the water cycle.

The water cycle must be drained completely using compressed air before storage or transportation at freezing temperatures or below.

Plumbing materials to avoid

Do not use the following materials in a closed water system:

Oxidizing biocides

Aluminum components

Brass components with high levels of zinc

Non-stainless steel Iron components

Water precautions

Take the following precautions before installation of the HP POD:

Verify that all foreign matter and particulates are flushed from the system.

Evaluate the short-term and long-term system requirements against the available water capacity.

Ensure that the chilled water loop is properly designed for liquid cooling systems and is separate from the sanitary water systems in your building (bathroom, sink, drinking water).

Ensure facility managers understand the additional load being added to the chilled water supply of the building. Be aware that the added heat load might affect other components being cooled by the chilled water plant.

Water temperature

Without a water distribution kit, the temperature of the water supplied to the HP POD must be 12º to 24ºC (55º to 75ºF). Freezing water might cause a blockage and damage to the unit.

Water quality requirements 31

Image 31
Contents Part Number March 2009 First Edition HP Performance-Optimized Datacenter User GuideIntended audience Contents HP POD frequently asked questions Water precautions Water temperatureHP POD troubleshooting Acronyms and abbreviations Index Moving the HP POD Site requirementsOptimum environment Location considerationsAvailable to connect to central facility infrastructure Cooling water Power Drain optionalCallout Connection Temperature considerationsEnvironmental considerations Work space requirementsLightning protection Component documentationLeveling requirements Grounding requirementsSafety information Safety considerationsOperator safety Component health Safety considerations HP POD components Component identificationHP POD components Component Description External emergency components Component Description HP POD emergency componentsInternal emergency components Component Description HP POD panel locationsComponent Description ∗Optional component Transformer and switchboard components optionalWater distribution kit components optional HP POD contents InstallationRequired tools Preinstallation checklistComponent Quantity Part number Connecting the water Installing the HP POD using the optional componentsPipe wrench Installation Installation Installation Connecting the power Installation Commissioning the HP POD Installation Controlling the fan speed Water supply temperatureCooling system HP POD cooling systemHP POD drains Condensation managementPull the overhead down Leak detection Acceptable water quality specifications Water quality requirements and specificationsWater quality requirements Plumbing materials to avoid Water precautionsWater temperature Frost damageElectrical busway Power managementPower distribution Rack power Panels EPO Panel Assd panelBMS panel Electrical busway enclosed circuit breakerEPO modes House panel Fire alarm control panelEpms panel Fan control panelSecurity panel location Connecting the HP POD to the BMS Using a building management system BMSBuilding management system BMS alarms Managing BMS settings from the HP PODFire alarm sequence of operations Safety and security alarmsAlarm Meaning Solution Building management system Optional components Water distribution kit Transformers and switchboardsCallout Specification Water distribution kit power requirementsHP POD frequently asked questions Frequently asked questionsQuestion Answer Drain pans or the water main drain pan. The additional water HP POD troubleshooting TroubleshootingIssue Resolution Features Specifications SpecificationsHP POD specifications Electrical specificationsFeature Specification Water specificationsWater supply specifications with a water distribution kit Standard HP POD racks AN982A Feature Specification Rack specificationsThermal and air flow performance Water distribution kit specifications Environmental specificationsFor more information, see Water specifications on Maintenance HP contact information Before you contact HPRegulatory compliance notices Bsmi notice Korean class a notice Japanese class a notice Chinese noticeClass a equipment Acronyms and abbreviations Performance-Optimized Datacenter Power distribution unitUninterruptible power system National Electrical Manufacturers AssociationIndex Fire alarm control panel 13, 14, 35Fan Fan control panel 14, 35 Fan speed Safety considerations Index
Related manuals
Manual 21 pages 18 Kb Manual 79 pages 43.3 Kb